
YORKINTERNATIONAL
FORM150.63-NM2
11
1
fieldwired to CTB1terminals 13to 16. CTB1 terminal is
located in the control panel. Refer to Figure 5 and unit
wiringdiagram.
SeeAirProvingSwitch and RemoteStart-
Stop Contacts sectionsbelow.
Suction Pressure Control cannot be used unless the
optional suction transducers are installed on the unit
(standardonYCUL0211 -YCUL0275).
Suction Temperature Sensors (optional)
This is a field installed option that provides individual
displays of suction line temperature for each system at
thecondensingunit.Thisoptionperformsno control func-
tion,but simply providesthe suction linetemperaturefor
eachrefrigerant system asmeasured at thecondensing
unit.
On the microboard, the connections are field wired to
J5, pins 7, 12, & 1 for System 1; J5, pins 8,13 & 2 for
System 2. Refer to Figure 9 and unit wiring diagram.
The sensors should be attached to the suction line with
copper straps, and heat conducting compound should
beused toensure goodheat transfer.
Air Proving Switch
Theairprovingswitch is fieldwiredtoCTB1 terminals 13
to14 toprevent operationof therefrigerant circuitwhen
the supply air blower is not operating.
Ifseparate evaporator blowers are used with respectto
eachrefrigerant system inthe condensing unit,thentwo
airprovingswitchesmustbewiredinseriesacrossCTB1
terminals13-14(onefor each evaporator blower).Refer
toFigure 5 and unit wiring diagram.
WhenusingZoneThermostatsinSuctionPressure Con-
trol mode, the air proving switch(es) should be wired in
serieswith therespective ZoneThermostats.
Remote Start/Stop Contacts
Toremotely start and stop thecondensing unit,dry con-
tacts can be wired in series with the air proving switch
andCTB1- terminals 13to14. Refer toFigure5and unit
wiringdiagram.
Remote Emergency Cutoff
Immediate shutdown of the condensing unit can be ac-
complished by opening a field installed dry contact to
break the electrical circuit between terminals 5 to L on
terminalblockCTB2.CTB2islocatedinthepowerpanel.
The unit is shipped with a factory jumper installed be-
tweenterminals 5 to L, which must be removed if emer-
gency shutdown contacts are installed. Refer to Figure
6and unit wiring diagram.
Evaporator Blower Start Contacts
Forconstantfan operation: TerminalblockCTB2 - termi-
nals 23 to 24, are normally open contacts that can be
used to switch field supplied power to provide a start
signalto theevaporator blower contactor.
Refer to Figure 6 and unitwiring diagram.
CompressorRunContacts
Contactsareavailabletomonitor“CompressorRun”sta-
tus. Normally-open auxiliary contacts from each com-
pressorcontactorare wired inparallelwith CTB2 -termi-
nals 25 to 26 for system 1, and CTB2 - terminals 27 to
28for system2 (YCUL0125- YCUL0275).Refer toFig-
ure6 and unit wiring diagram.
Alarm Status Contacts
Normally-open contacts are available for each refriger-
ant system. These normally-open contacts close when
the system is functioning normally. The respective con-
tactswill openwhen the unitis shutdown on aunit fault,
orlocked outon a system fault. Fieldconnections areat
CTB2terminals 29to 30 (system1), and terminals 31 to
32 (system 2). Refer to 6 and unit wiring diagram.
PWM Input
The PWM input allows reset of the discharge air tem-
peraturesetpoint(whenunitisprogrammedforDischarge
Air Temperature Control mode) by supplying a “timed”
contact closure. Field wiring should be connected to
CTB1- terminals 13to 20.Adetailed explanationis pro-
vided in the Unit Control section. Refer to Figure 5 and
unitwiring diagram.
Load Limit Input
Loadlimitingisafeaturethatpreventstheunitfromloading
beyond a desired value. The unit can be “load limited”
either 33%, 50%, or 66%, depending on the number of
compressorsontheunit. The field connectionsarewired
to CTB1- terminals 13 to 21, and work in conjunction
withthe PWMinputs. A detailedexplanation isprovided
in the Unit Control section. Refer to Figure 5 and unit
wiringdiagram.
When using the Load Limit feature, the
PWM feature will not function - SIMUL-
TANEOUS OPERATION OF LOAD LIMIT-
ING AND TEMPERATURE RESET (PWM
INPUT)CANNOT BE DONE.