MULTI-LOOP REPEATER
Installation Manual

Smart Connect Multi-loop Repeater Installation Manual
www.zetaalarmsystems.com
2
Contents
Introduction .................................................................................................................................................................................................. 3
About the Smart Connect Multi-loop Repeater ........................................................................................................................................ 3
Overall Features ........................................................................................................................................................................................ 3
Document Conventions................................................................................................................................................................................. 3
Circuits and Zones ..................................................................................................................................................................................... 3
System Components ..................................................................................................................................................................................... 4
Panel Installation and Dimensions ................................................................................................................................................................ 5
Enclosure Dimensions ............................................................................................................................................................................... 5
Panel Construction Details ........................................................................................................................................................................ 5
Locating the Fire Alarm Control Panel....................................................................................................................................................... 5
Mounting the Enclosure............................................................................................................................................................................ 6
Mounting Hole Dimensions....................................................................................................................................................................... 6
Planning Cable Entry ................................................................................................................................................................................. 6
Cable Grounding........................................................................................................................................................................................ 7
DC Power Wiring ....................................................................................................................................................................................... 7
Initial Power Up......................................................................................................................................................................................... 9
Field Wiring ................................................................................................................................................................................................... 9
RS485 Network Wiring Overview .............................................................................................................................................................. 9
Wiring Recommendations for Network Wiring ....................................................................................................................................... 10
Network Specifications............................................................................................................................................................................ 10
Operation .................................................................................................................................................................................................... 11
Fault Finding................................................................................................................................................................................................ 11
Appendix A: SPECIFICATIONS ...................................................................................................................................................................... 11

Smart Connect Multi-loop Repeater Installation Manual
www.zetaalarmsystems.com
3
Introduction
About the Smart Connect Multi-loop Repeater
The Zeta Smart Connect Multi-loop Repeater Panel can be used to monitor, operate and program Smart Connect Multi-loop fire alarm
control panels (FACPs) from anywhere within the networked system.
The Repeater features a 4.3” colour touch screen display that provides easy-to understand system messages. The Repeater is
ergonomically designed with a LED, button and menu setup that perfectly replicates a Smart Connect Multi-loop Control Panel. This will
make the Repeater feel familiar to use for those who are trained/experienced in using the Smart Connect system.
It can operate as part of a networked system of up to 64 panel’s peer-to-peer, with powerful programming options that allow
configurable control over whether messages from specific panels are transmitted around the network or remain local.
The 32-bit microcontroller (MCU) at the heart of panel rapidly processes logical decisions based on the status of the smoke detection
and other initiating devices to control the system outputs. The Windows based software configuration tool Smart Connect is used to
configure the system’s operation based on the customer specified operating requirements, and reduce commissioning/installation
times.
The Smart system continuously checks all software and hardware for proper operation. It checks all control panel electronic hardware,
system memory components, and the system program. A hardware watchdog circuit is provided to ensure that System programs are
functioning properly. If a problem develops with the program or processor, the watchdog circuit places the System into a system fault
condition and tries to reset it.
The Smart Connect Multi-loop Repeater enclosure can be surface or flush mounted.
Overall Features
4.3” colour touch screen display.
8032 Event Log.
Up to 64 panel peer-to-peer network.
13 status LED indicators.
5 function button controls.
Fully functioning Repeater provides the ability to program a networked Smart Connect Multi-loop control panel from the
front screen.
Accommodates wiring lengths up to 1000 metres from the control panel for added design and install flexibility.
Network can we wired in either a bus or a ring topology if a redundant path is required.
8 password protected access accounts available (1 admin level, 7 user level).
Uncluttered and intuitive interface allows alarms, supervisory, and trouble events to be easily viewed.
Document Conventions
Circuits and Zones
Circuit = this refers to an actual electrical interface, initiating (detection), indicating (signal), or relay.
Zone = this is a logical concept for a fire alarm protected area, and will consist of at least one circuit.
The terms zone and circuit are used interchangeably throughout this manual.
On the Smart Connect Multi-loop systems, circuits can be either conventional or addressable inputs or outputs. Both hardwired
conventional inputs and outputs, and addressable inputs and outputs may be grouped together to form logical zones.

Smart Connect Multi-loop Repeater Installation Manual
www.zetaalarmsystems.com
4
Typical Smart Network Fire Alarm Wiring
System Components
Display PCB (MMP/DSP)
4.3” colour touch screen display
32-bit microcontroller (MCU)
USB connection to PC software
2 key switch inputs
Termination PCB (MMP/REP_COM)
CPU reset button
RS485 IN & OUT terminals
28VDC IN & OUT terminals

Smart Connect Multi-loop Repeater Installation Manual
www.zetaalarmsystems.com
5
Panel Installation and Dimensions
Enclosure Dimensions
See table 1 for full dimensions.
Table 1
Panel
A
B
C
D
E
F
Top
Knock
outs
Side
Knock
outs
Bottom
Knock
outs
Max
Battery
Size
SMART/REP
230mm
340mm
307mm
96mm
70mm
200mm
5
0
0
N/A
Panel Construction Details
All components are manufactured from Zintec.
All parts 0.9 mm.
The paint colour for the main box and door is RAL9005 Black Leatherette.
The internals are RAL9005 Black Leatherette.
The repeater enclosure can be semi flushed into a wall or surface mounted.
Locating the Fire Alarm Control Panel
The control panel should be installed per BS5839-1:2017 recommendations: -
The panel should be close to the main entrance of the building, so that it can be viewed by any fire-fighting personnel entering the
building.
It should be fitted to a sturdy wall that will not flex unnecessarily.
It should ideally be mounted at eye level, for it to be viewed without need of a ladder.
It should be installed in a dry, weatherproof place, preferably NOT in direct sunlight.
It should be easily accessible, so that the responsible person can perform their regular fire alarm checks.

Smart Connect Multi-loop Repeater Installation Manual
www.zetaalarmsystems.com
6
The panel must be in a clean, dry position, which is not subject to excessive shock or vibration and at least 2 meters away from pager
systems or any other radio transmitting equipment. The operating temperature range is -5°C (23°F) to 40°C (104°F); maximum humidity
is 95%. The panel will withstand vibrations between 5 & 150 Hz.
Mounting the Enclosure
Fix the enclosure to the wall using all the mounting points provided:
SMART/REP: 3 x Mounting Points. See Fig 1
Check the build and condition of the wall to decide a suitable screw fixing. The mounting holes are designed for No 8 roundhead or
countersunk woodscrews (or similar). Remove any debris from the enclosure. Take care not to damage the panel during installation.
Mounting Hole Dimensions
Fig 1
Planning Cable Entry
The Knock-out cable entries can be easily removed by tapping with a suitable screwdriver or chisel from outside the enclosure back
box. Alternatively, the entry can be drilled out, using a 20mm hole cutter. Care should be taken if using a drill. Consider removing the
PCBs to prevent damaging them.
The repeater comes with 5 cable entry holes. If another entry hole is required, it is strongly recommended that the panel door is
removed to avoid accidental damage. Also, the PCB’s should be removed and stored in a safe place. This would also help while fixing
the back box to the wall.
ATTENTION: DO NOT DRILL ANY ENTRY HOLES INTO THE PCB SECTIONS OF THE ENCLOSURE

Smart Connect Multi-loop Repeater Installation Manual
www.zetaalarmsystems.com
7
Cable Grounding
The Repeater has no internal earth bars. It is recommended that network wiring is connected to ground at a Smart Connect control
panel (only one side of the network wiring should be grounded).
DC Power Wiring
The SMART/REP needs to be powered by a 28VDC external EN54 approved power supply. The cables used for this must be fire rated.
Recommendations
The DC supply to the Repeater should be fixed wiring, using Fire resisting 3-core cable (Between 1 mm² and 2.5mm²), or equivalent.
The AC supply to the PSU should be fed from an isolating double (or single) pole switch fused spur, and fused at 5A. This should be
secure from unauthorized operation and be marked ‘FIRE ALARM: DO NOT SWITCH OFF’. The supply must be exclusive to the repeater.
Connecting the DC Power
The incoming DC power cable should be kept separate from the RS485 network cables to help minimise interference.
It is advisable to apply power to the repeater before connecting any network cables, to check for correct operation, and to familiarise
yourself with the repeater panels’controls.
If a knockout is removed, fill the hole with a suitable cable gland. If any knockout is removed, but subsequently not used, it should be
covered up.
Figure 2: Termination PCB Layout
ATTENTION: MAKE SURE ANY SPARE ENTRY HOLES THAT HAVE BEEN OPENED, BUT NOT USED ARE COVERED WITH
SUITABLE GROMMETS OR BLANKING SCREWS.
ATTENTION: DO NOT DRILL ANY ENTRY HOLES INTO THE DOOR SECTION OF THE ENCLOSURE.
(Not used)

Smart Connect Multi-loop Repeater Installation Manual
www.zetaalarmsystems.com
8
Figure 3: 28V DC wiring
Figure 4: 28V DC terminal wiring
ATTENTION: CHECK POLARITY IS CORRECT BEFORE TURNING THE POWER ON.

Smart Connect Multi-loop Repeater Installation Manual
www.zetaalarmsystems.com
9
Initial Power Up
It is recommended to initially power up the repeater with no networked panels connected to confirm that the base panel is functioning
as expected. To do this:-
1. Check that the DC cable is connected correctly.
2. Close the panel door
3. Turn on the DC power. The following will be observed:-
a. Power, Fault and System Fault LEDs will light for around 6 seconds
b. Fault and System Fault LEDs will turn off. Power LED will blink a few times
c. LCD will show touch for calibration. Press the screen within 3 seconds to perform a screen calibration. (The screen is
calibrated at the factory, so this step is not usually required)
d. The LCD shows the Zeta logo for a few seconds, while it checks to see what modules are fitted. (Note: the usual
“System Healthy” banner is not shown during the module check.)
e. Leave the panel soak for 100 seconds.
f. If no faults were reported then the panel has passed its power on test. It can now be turned off and the network
cables can be fitted.
Field Wiring
RS485 Network Wiring Overview
Bus Topology
NOTE: The terminal blocks are removable to make wiring easier.

Smart Connect Multi-loop Repeater Installation Manual
www.zetaalarmsystems.com
10
Ring Topology
Wiring Recommendations for Network Wiring
The Smart network can support up to 64 panels.
Network Specifications
RS485 Network
Maximum Network Size
64 Nodes
Maximum Distance Between Nodes
1KM (with screened data cable)
100M (using a standard fireproof cable)*
Communication Protocol
RS485
Network Wiring Typologies
Bus or Ring
*BS 5839-1:2017 requires that network cable be standard fire proof cable (enhanced fire proof cable may be required for specified
installations).
NOTE: It is recommended to install the network in a ring topology for
protection against open circuit and short circuit faults.
RECOMMENDED CABLE: Belden or equivalent

Smart Connect Multi-loop Repeater Installation Manual
www.zetaalarmsystems.com
11
Operation
Refer to the Smart Connect Multi-loop Operation Manual (Doc: GLT-261-7-11).
Fault Finding
Refer to the troubleshooting section in the Smart Connect Multi-loop Operation Manual (Doc: GLT-261-7-11).
Appendix A: SPECIFICATIONS
Code
Description
Smart Connect Multi-loop Repeater
Main Supply
Operating Voltage
28VDC
Quiescent Current
78mA
Maximum Current
100mA
Network
Communication Protocol
RS485
Maximum Network Size
64 Nodes
Maximum Distance Between Nodes
1KM (using 1 screened data cable)
100m (using a standard fireproof cable)
Network Wiring Typologies
Bus
Ring (recommended)
Software
Maximum Event Log
8032 Events
Software Programming
Touchscreen LCD
Display
LCD
4.3” Resistive touch screen. 480 x 272 pixel resolution
LED Indications
2 Red (1 x Fire, 1 x Sounder Active), 1 Green (Power), 10 Yellow (1 x Relay
Delay, 1 x Fault, 1 x Sounder Delay, 1 x Controls Active, 1 x General
Disablement, 1 x General Test, 1 x Sounder Fault/Disablement, 1 x Sounder
Delay, 1 x System Fault, 1 x More Data).
Button Controls
Stop Sounders, Silence Buzzer, Scroll Display, Reset, Start Sounders
Enclosure
Dimensions H x W x D (mm)
230mm x 340mm x 96mm
Weight
2.3kg
Cable Entries
5 (Top entries)
Terminal Wiring Size
1mm2–2.5mm2
Environmental
Operating Temperature
-5°C to 40°C
Relative Humidity
93% Non-condensing
Table of contents
Popular Repeater manuals by other brands

ICP
ICP Protege DIN Rail Module Network Repeater quick start guide

Comba Telecom
Comba Telecom RA-7800 installation guide

Kenwood
Kenwood TKR-851 Service manual supplement

Enecsys
Enecsys Double Repeater user manual

DMP Electronics
DMP Electronics 1100RINT installation guide

Digitus
Digitus DS-55524 Quick installation guide

Digital Monitoring Products
Digital Monitoring Products 1100R installation guide

Tesla
Tesla TERA TRR2 Technical Specifications & Operation Manual

Ferret
Ferret CFR300A Configuration guide

Cabletron Systems
Cabletron Systems IRM supplementary guide

HumanTechnik
HumanTechnik lisa operating instructions

DSE
DSE RKK-KIT1 installation manual