
CUT-OUT REQUIREMENTS
The control box can be placed in various positions as above.
All dimensions are in mm.
The hole in the bench top for the side burner needs to be 394 2mm X 484 2mm.
The hole for the control box needs to be 204 2mm X 154 2mm
Minimum 210mm clearance below the bench top is required. It is
recommended to use a non-combustible barrier at least 210mm below the
bench top between any gas cylinder below.
maxmax
max
max
max
min
min
Installation must be in
accordance with Australian
Standard AS5601 and any
local regulations.
Bench top must be a non-combustible material.
Minimum clearance
from combustible materials:
1000mm overhead,
300mm sides and rear.
+
-
+
-
+
-
+
-
10
Gas cylinder compartments must have permanent openings ventilating
directly to the outside of the appliance, and consisting of either—
(a) perforations, uniformly distributed over the height of the enclosure and
with a total free area of not less than 25% of the sidewall area; or
(b) separate openings at high and low level, such that—
(i) the total free area at high level is not less than 20 000 mm2 and is within
125 mm of the top of the cylinder compartment; and
(ii) the total free area at low level is not less than 20 000 mm2, and—
(A) at least 25% of the required area is within 15 mm of the base of the
cylinder compartment;
(B) the total required area is within 125 mm of the base of the cylinder
compartment; and
(C) the openings cannot be obstructed by the cylinder(s).