
5 | UPStealth® 2 User Manual
Warnings and Cautions
UPS
Battery Panel / Module
UPS Input & Output Values
To avoid re, shock, or death; turn o power at circuit breaker or fuse and test that power is o before wiring,
servicing, or removing.
Read this manual prior to installation and operation. If you have any questions about safe installation, operation or
maintenance, contact ZincFive’s Support Department.
Carefully unpack the components. Report any shipping or other damage at once.
Never let live battery wires touch the UPS, the enclosure, or any other metal objects.
Use proper lifting techniques when lifting or moving the UPS or its components.
At high ambient temperature conditions, the UPS’surface can be very hot to the touch when operating.
Ensure ventilation to the left and right sides of the UPS enclosure.
To be installed and/or used in accordance with electrical codes and regulations.
Before installation, verify the input voltage and current requirements of the load are met by the UPS’output. Verify
the line voltage and current meet the UPS input requirements.
To avoid electric overload, do not exceed output rating.
Battery installation and servicing should be done or supervised by personnel knowledgeable about
batteries and the required precautions.
Battery Panel / Module must not be installed in a sealed enclosure, ventilation must be provided.
Use proper lifting techniques when lifting or moving the batteries.
Never dispose of batteries in a re.
Never open or damage the batteries.
A battery can present a risk of electrical shock and high short-circuit current. The following precautions should
be observed when working on batteries:
Remove watches, rings, or other metal objects.
Use tools with insulated handles.
Disconnect the AC input to the Battery prior to connecting or disconnecting battery terminals.
Ensure that the Battery is OFF before connecting or disconnecting battery interconnect cables. The
Battery Panel / Module indicator LED will be OFF.
Never short pins inside battery cable connectors.
Input Voltage Range
85-140ac User Programmable
Input Frequency
60Hz nominal
+10% (54-66Hz)
Output Power 1,000VA Typical
Operating Temperature Range (-37°C to 74°C) (-34°F to 165°F)
Intelligent Two-Stage Operation
Stage One: Line Conditioner, Waveform Monitoring and Switchover to Battery Backup
Stage Two: Waveform Monitoring, Return to AC Power
Switchover Thresholds
AC Voltage: Programmable From 85-140Vac in 1V steps
AC Waveform Analysis
AC Frequency: 60Hz + 6Hz
Transfer Time from AC Power to Battery Backup Typical 8ms
Size 3.6"H X 17"W X 10.8"D
UPS Connection System
AC cable from PIM IEC 320 C20 (male)
AC cable to PIM IEC 320 C19 (female)
Battery connection system - 7 pin DSUB for up to 6 battery systems
Display 64 x 128 Pixels LCD Display with White LED Backlight
Ports Ethernet RJ45 - 10/100Mbps, TCP/IP
Dry Relay Contacts 8 Independent Programmable Form C Relays (default state: NO) Class 2 Only
Alarm Functions
AC Power Failure
Daily Time Trigger
Flash Trigger Timed After Power Failure
Battery Capacity
UPS Fault
Audible Indicators
System Startup
Cold Start
Inverter On/Off
Inverter Output Over Current
AC Miswire
Rotating Dial, Pushing Enter or Back Button On Front Panel
UPS Fault
Cold Start Simple Push-button Activation of Cold Start On Battery Power
Battery Management System
Digital Battery Bus
Compartmentalized Battery Strings
Redundant Isolated Battery Strings Managed in Parallel Upon Discharge
Integrated Temperature Compensated Charging
Redundant Performance
Multiple Mounting Configurations Rack, Shelf or Hanging
Notifications All Alarm Functions Available On (SNMP, SMTP, Relay)
Local and Remote Control Front Panel Navigation Dial and Button
Embedded Webserver Software for Remote Connectivity and Control
Internal Battery Backed-Up Real-Time Clock Operates for Life of System
AC Power Event Log Stores Previous 1000 Events with Waveforms
Firmware updates Remote over TCP/IP
Input Voltage Range 120Vac nominal
Input Frequency 60Hz nominal
Output Voltage 120Vac nominal
Operating Temperature Range (-37°C to 74°C) (-34°F to 165°F)
Size 6.0"H X 10.0"W X 4.0"D
Mounting Single Rail Rack Mount, Shelf Mount, Panel Mount
AC Power Interface Utility and Cabinet Load:
- Terminal Block for 10AWG (#8 Screw)
AC Power Connections
To UPS IEC320 C19 (female)
From UPS IEC320 C20 (male)
To Battery Panel/Module IEC 320 C19 (female)
Breakers Combined UPS Test Switch and 15A Input Breaker
UPS Output 20A Breaker
Test Outlet NEMA Receptacle 5-15
Automatic Bypass Switch Double Pole Double Throw (DPDT)
Contact Rating: 120/240 Vac @ 30A continuous
Visual Red indicator: PIM is In Bypass Mode
*All Specifications Valid at 25°C *All Specifications Subject to Change