4B F500 Elite User manual

F500 Elite.
FIELDBUS ADAPTER.
Watchdog NTC to Profibus DP
communications.
(Software Version 9.5.x)
Approvals: Suitable for use in Hazardous Locations
Zone21 / Cat2D / CL II Div 1 GPS E, F & G (V4)
When powered with a Class2 power supply.
Zone22 / Cat3D / CL II Div 2 GPS F & G (V46)

Watchdog NTC to F500 PGW CAI REV0 July 2014
2
CONTENTS
INTRODUCTION
1SPECIFICATIONS
2INSTALLATION INSTRUCTIONS
3ELECTRICAL WIRING
4OPERATING INSTRUCTIONS
FAULT FINDING
CONTACT INFORMATION
DRAWINGS
A CONNECTING THE F500 ELITE TO AN AC SUPPLY
B CONNECTING THE F500 ELITE TO A DC SUPPLY
C F500 ELITE TO WATCHDOG ELITE CONNECTIONS
D F500 ELITE TO VT100 SERIAL TERMINAL CONNECTIONS
E GENERAL CONNECTION DETAIL
APPENDIX A –SETTING THE MODULE SWITCHES

Watchdog NTC to F500 PGW CAI REV0 July 2014
3
Dear 4B Customer:
Congratulations on your purchase. 4B appreciates your business and is pleased you have chosen our
products to meet your needs.
Please read in its entirety and understand the literature accompanying the product before you place the
product into service. Please read the safety precautions carefully before operating the product. With each
product you purchase from 4B, there are some basic but important safety considerations you must follow to
be sure your purchase is permitted to perform its design function and operate properly and safely, giving you
many years of reliable service. Please read and understand the Customer Safety Responsibilities listed
below. Failure to follow this safety directive and the Operation Manuals and other material furnished or
referenced, may result in serious injury or death.
SAFETY NOTICE TO OUR CUSTOMERS
A. In order to maximize efficiency and safety, selecting the right equipment for each operation is vital.
The proper installation of the equipment, and regular maintenance and inspection is equally
important in continuing the proper operation and safety of the product. The proper installation and
maintenance of all our products is the responsibility of the user unless you have asked 4B to
perform these tasks.
B. All installation and wiring must be in accordance with Local and National Electrical Codes and other
standards applicable to your industry. (Please see the article “Hazard Monitoring Equipment
Selection, Installation and Maintenance” at www.go4b.com.) The installation of the wiring should
be undertaken by an experienced and qualified professional electrician. Failure to correctly wire
any product and/or machinery can result in the product or machine failing to operate as intended,
and can defeat its design function.
C. Periodic inspection by a qualified person will help assure your 4B product is performing properly.
4B recommends a documented inspection at least annually and more frequently under high use
conditions.
D. Please see the last page of this manual for all warranty information regarding this product.
CUSTOMER SAFETY RESPONSIBILITIES
1. READ ALL LITERATURE PROVIDED WITH YOUR PRODUCT
Please read all user, instruction and safety manuals to ensure that you understand your product operation
and are able to safely and effectively use this product.
2. YOU BEST UNDERSTAND YOUR NEEDS
Every customer and operation is unique, and only you best know the specific needs and capabilities of your
operation. Please call the 24-hour hotline at 309-698-5611 for assistance with any questions about the
performance of products purchased from 4B. 4B is happy to discuss product performance with you at any
time.

Watchdog NTC to F500 PGW CAI REV0 July 2014
4
3. SELECT A QUALIFIED AND COMPETENT INSTALLER
Correct installation of the product is important for safety and performance. If you have not asked 4B to
perform the installation of the unit on your behalf, it is critical for the safety of your operation and those who
may perform work on your operation that you select a qualified and competent electrical installer to
undertake the installation. The product must be installed properly to perform its designed functions. The
installer should be qualified, trained, and competent to perform the installation in accordance with Local and
National Electrical Codes, all relevant OSHA Regulations, as well as any of your own standards and
preventive maintenance requirements, and other product installation information supplied with the product.
You should be prepared to provide the installer with all necessary installation information to assist in the
installation.
4. ESTABLISH AND FOLLOW A REGULAR MAINTENANCE AND INSPECTION SCHEDULE FOR
YOUR 4B PRODUCTS
You should develop a proper maintenance and inspection program to confirm that your system is in good
working order at all times. You will be in the best position to determine the appropriate frequency for
inspection. Many different factors known to the user will assist you in deciding the frequency of inspection.
These factors may include but are not limited to weather conditions; construction work at the facility; hours of
operation; animal or insect infestation; and the real-world experience of knowing how your employees
perform their jobs. The personnel or person you select to install, operate, maintain, inspect or perform any
work whatsoever, should be trained and qualified to perform these important functions. Complete and
accurate records of the maintenance and inspection process should be created and retained by you at all
times.
5. RETAIN AND REFER TO THE OPERATION MANUAL FOR 4B’S SUGGESTED MAINTENANCE
AND INSPECTION RECOMMENDATIONS
As all operations are different, please understand that your specific operation may require additional
adjustments in the maintenance and inspection process essential to permit the monitoring device to perform
its intended function. Retain the Operation Manual and other important maintenance and service documents
provided by 4B and have them readily available for people servicing your 4B equipment. Should you have
any questions, please call the 4B location who supplied the product or the 24-hour hotline number in the
USA -309-698-5611.
6. SERVICE REQUEST
If you have questions or comments about the operation of your unit or require the unit to be serviced please
contact the 4B location who supplied the product or send your request via fax (309-698-5615), email (4b-
[email protected]), or call us via our 24-hour hotline number in the USA - 309-698-5611. Please have
available product part numbers, serial numbers, and approximate date of installation. In order to assist you,
complete the following information after the product has been placed into service and fax this page to 309-
698-5615.
SITE NAME:
SITE LOCATION:
CONTACT NAME:
CONTACT NUMBER:
PART NUMBER:
SERIAL NUMBER:
DATE OF INSTALL:

Watchdog NTC to F500 PGW CAI REV0 July 2014
5
F500 FIELDBUS ADAPTER.
INTRODUCTION
This version of the F500 Elite Fieldbus adapter had been designed to work as a Watchdog
Elite communications gateway and has been designed specifically to allow up to 7
Watchdog NTC control units to be networked together through their own built in
communications system. The network data can then be passed through the Fieldbus
adapter to a Profibus DP network. The communications control unit is housed in a self-
contained wall-mounting enclosure, and will operate from 100-240v AC or from 24v DC.
1. SPECIFICATIONS
1.1 The Control Unit
A plastic enclosure houses the electronics and terminal connectors. The unit contains a
printed circuit board to accommodate power supply circuitry, microprocessor, Fieldbus
card and terminals. The design is capable of accommodating 8 of the most common
Fieldbus interfaces.
Electrical Supply –100-240VAC +/- 10% 50/60Hz
- 24VDC +/- 10%
Power Consumption - 12 WATTS
Terminals - Power 4mm² 14 AWG max
- Communications, as appropriate to the Fieldbus
module.
Protection - NEMA4X,IP66
Height - 9.7”, 246mm
Width - 7.4”, 188mm
Depth - 4”, 102mm
Fixing Centres - 8.75” high x 4” wide, 222mm x 102mm
Cable Entry - 2 Holes 11/8” DIA, 28mm, ¾” CONDUIT
Weight - 3lbs, 1.3Kg
Approvals
For V4 Model
1180 Ex tb IIIC T125° Db IP66 TAMB -20°C to +50°C IECEx BAS05.0026X
1180 Ex II 2D Ex tb IIIC T125° Db IP66 TAMB -20°C to +50°C Baseefa04ATEX0131X
CSA - Class II Div. 1, Groups E, F & G
(F5004V4CAI-PGW - When Powered with a Class 2 Power Supply)
For V46 Model:
1180 Ex tc IIIC T125° Dc IP66 TAMB -20°C to +45°C IECEx BAS11.0018X
1180 Ex II 3D Ex tc IIIC T125° Dc IP66 TAMB -20°C to +45°C Baseefa11ATEX 0033X
CSA - Class II Div. 2, Groups F & G (F5004V46CAI-PGW)

Watchdog NTC to F500 PGW CAI REV0 July 2014
6
Power Dissipation in Watts
ATEX category 2D: 12 Watts
ATEX category 3D: 25 Watts
CSA (F5004NV4CAI-PGW): 12 Watts
CSA (F5004NV46CAI-PGW): 12 Watts
Approval Safety Information
To Open the Lid:
1. Disconnect power (isolate ALL circuits)
2. Untighten the lid securing screws
3. Carefully open the lid ensuring that the gasket is not damaged and remains in place
To Close the Lid:
1. Check that the gasket is correctly fitted into the box groove and is undamaged.
2. Tighten the lid screws.
3. Check that the lid and box are correctly mated.
Special conditions of use:
1. The equipment shall be suitably earth bonded via the PCB mounted earth
terminal inside the equipment enclosure.
2. Warning: The equipment is a potential static hazard, clean only with a damp
cloth.
3. Do not allow dust layers to build up on the equipment.

Watchdog NTC to F500 PGW CAI REV0 July 2014
7
2. INSTALLATION INSTRUCTIONS
The Control Unit
The Control Unit box should be installed in a suitable control or starter switch room. The
box should have sufficient space to open the lid for wiring.
The Control Unit is susceptible to static voltage. Connection of a
clean ground to terminal 29 is essential for optimum
performance. Prior to this connection, static handling
precautions should be taken.
3 ELECRICAL WIRING
Refer to Drawings A, B, C & E
When installing the equipment in an area which is likely to be hazardous from Ignitable
Dusts, use liquid tight conduit and fittings and follow all local codes.
4 OPERATING INSTRUCTIONS
The Fieldbus Adapter is a self contained unit and there are a number of user configurable
options. The adapter is equipped with three communications ports; RS232, RS485 and
Profibus DP.
The RS232 is a simple interface which can be used for diagnostics purposes. The data
from this port is formatted to work with a VT100 display terminal. Any terminal or
terminal emulator capable of supporting the VT series or compatible commands can be
used with this port although the data has been optimised to work with VT100. The
RS232 port operates at a fixed data rate of 9600, N, 8, 1.
The RS485 port is a four wire, twin twisted pair full duplex serial port and has been
specifically configured to work with the Watchdog communications network. You
should not connect any other devices to this port unless you wish to monitor the
Watchdog data directly. If this is the case then contact your supplier for details relating
to the Watchdog communications protocol.
The Profibus interface provides the following:
Transmission media: Profibus bus line, type A or B specified in EN50170
Topology: Slave configuration
Fieldbus Connector: 9 pin female DSUB
Cable: shielded copper; twisted pair
Optically isolated bus A and B termination
Address range 1-99 selected by on board switch
Maximum cyclic I/O data size of 244 bytes
Optional bus termination, switch selectable
Led status indication

Watchdog NTC to F500 PGW CAI REV0 July 2014
8
The above diagram shows the location of the main parts of the Profibus module.
The address switches allow the unit slave address to be set between 01 and 99. The left
hand switch sets the ten’s digit of the address and the right hand switch sets the unit digit
of the address. If you decide to change the address then you must reset the interface by
first removing and then reconnecting power. The default unit address is 77.
The termination switch can be used to add termination resistors to the Profibus interface
if required. If the F500 Profibus interface card is the first or last module on the Profibus
network, then the switch needs to set to ON, otherwise it must be set to OFF.

Watchdog NTC to F500 PGW CAI REV0 July 2014
9
The Profibus connections are shown below and are identical to the standard Profibus
DSUB connections.
The status LED’s are grouped in a single block of four and indicate the following status.
Led 1 Status
Colour
Frequency
Description
-
-
Not Used
Led 2 Status
Colour
Frequency
Description
Green
Solid on
Module is ON-LINE and data exchange is possible
Led 3 Status
Colour
Frequency
Description
Red
Solid on
Module is OFF-LINE and data exchange is not possible.
Led 4 Status
Colour
Frequency
Description
Red
1 Hz
Interface board initialisation failure
Red
2 Hz
Network configuration does not match module configuration
Red
4 Hz
Initialisation failure of the Profibus interface IC
Pin
Signal
Description.
1
N/C
No connection
2
N/C
No connection
3
B line
Positive RxD/TxD according to RS485 specification
4
RTS
Request to send
5
GND BUS
Isolated ground connection
6
+5V BUS
Isolated +5V connection
7
N/C
No Connection
8
A line
Negative RxD/TxD according to RS485 specification
9
N/C
No Connection

Watchdog NTC to F500 PGW CAI REV0 July 2014
10
Input register data map (Cyclic I/O data transfer –Max 244 bytes see page, see
Appendix A for more information).
The Watchdog data is automatically read for up to 7 controllers. The data returned is
processed and stored in the following format. The position of the data is fixed within the
input data table.
The Watchdog data is automatically read for up to 7
controllers. The data returned is processed and
stored in the following format. The position of the
data is fixed within the input data table.
Word 0 (Byte 1) is used to indicate the number of
Watchdogs that are responding to the request for
data. Word 0 (Byte 0) is unused. This only occurs
once in the entire table. The remaining data stored
in the input bytes is constructed as follows.
All the values are stored in Hexadecimal and Word aligned in this example
Number of Watchdogs detected this time (Byte 1,0) Once only
Watchdog current speed (Byte 3,2)
Watchdog current operating status (Byte 5,4)
Under speed alarm and stop in % (Byte 7,6)
Over speed alarm and stop in % (Byte 9,8)
Current calibration value in PPM (Byte 11,10)
Display scaling factor (Byte 13,12)
NTC Temperature 1 and 2 (Byte 15, 14)
NTC Temperature 3 and 4 (Byte 17, 16)
NTC Temperature 5 and 6 (Byte 19, 18)
NTC temperature sensor status 1 and 2 (Byte 21,20)
NTC temperature sensor status 3 and 4 (Byte 23,22)
NTC temperature sensor status 5 and 6 (Byte 25,24)
Sensor 1 and sensor 2 alarm level (Byte 27,26)
Sensor 3 and sensor 4 alarm level (Byte 29,28)
Sensor 5 and sensor 6 alarm level (Byte 31,30)
Number of sensors in use (Byte 33), Relay status (Byte 32)
Persistent alarm value (Byte 35), update counter (Byte 34
The data from each Watchdog is stored in 17 consecutive words (or 34 bytes) of data.
The first two bytes of the group (e.g. word 1) represent the Watchdog speed.
The second two bytes of the group of the group (e.g. word 2) represent the Watchdog
status.
Watchdog
Address
Input
Words
Input
Byte
-
0
0-1
1
1 –17
2 –35
2
18 –34
36 –69
3
35 –51
70 -104
4
52 –68
105 -137
5
69 –85
138 -171
6
86 –102
172 - 205
7
103 –119
206 - 239

Watchdog NTC to F500 PGW CAI REV0 July 2014
11
The Watchdog speed is encoded in the following manner. Four hexadecimal digits are
used to represent the measured speed for the Watchdog. The rightmost three and a half
are the main body of the speed and the upper half of the fourth is the position of the
decimal place within the information. If the most significant two bits are ‘00’ then
decoding of the speed is not required. If the two bits are ‘01’, then the resulting value
should be divided by 10 and if the two bits are ‘10’ then the speed should be divided by
100. The top two bits should never be ‘11’ as this has no meaning.
Bit
7
Bit
6
Description (e.g. most significant bits of the first speed byte 3)
0
0
Bits 5-0 of the first byte and the whole second represent the speed.
0
1
Same as above but the speed and should be divided by 10
1
0
Same as above but the speed and should be divided by 100
1
1
Not used.
An example of this can be seen below.
Watchdog speed = 6E (e.g. byte 3) & 1E (e.g. byte 2). The leftmost digit (6) = ‘0110’ in
binary which can be separated into ‘01’ (bits 7 and 6) for speed scaling and ‘10’ (bits 5
and 4) for the upper speed digit. If you strip off bits 7 and 6 you are left with a decoded
value of 2E & 1E for the speed and ‘01’ or divide by 10 for the scaling. The speed 2E1E
converted to decimal = 11806 and then divided by 10 results in an actual speed of 1180.6.
By default the Watchdog will display speed in pulses per minute but it can be scaled to
display any value required, refer to the Watchdog manual for further detail.
The Watchdog status is encoded as described in the following manner.
Two data bytes are used to represent the status for the Watchdog. The first status byte
(e.g. byte 5) is the status code and the second byte (e.g. byte 4) represents any data which
is associated with the status code. All data is in hexadecimal.
Status Code
(Byte 5)
Status Data
(Byte 4)
What it means.
09
% Complete
Watchdog is calibrating (% complete).
0F
-
Elevator is stopped due to persistent belt slip.
10
-
Elevator is stopped due to persistent over calibration.
11
-
Misalignment detected on Top & Bottom sensors.
22
-
Elevator is stopped and is ready to run (Normal stop
condition)
23
Start-up Delay
In seconds
Elevator is accelerating. (xx seconds remain)
24
Speed %
Elevator running within programmed limits.
25
Speed %
Stop relay has been de-energised (Fault stop
condition)
27
Time to alarm
In seconds
Misalignment detected. (xx seconds to alarm)
2A
Time to alarm
In seconds
Over speeding: Alarm relay about to de-energise (xx
seconds to alarm)
2D
-
Misalignment detected at the top of the elevator.
2F
Time to stop
Over speeding: Stop relay about to de-energise (xx

Watchdog NTC to F500 PGW CAI REV0 July 2014
12
In seconds
seconds to stop)
31
-
Speed display is over range: check the scaling factor.
32
-
Start elevator to commence calibration procedure.
36
1-4
Watchdog has detected an internal fault.
39
Time to alarm
In seconds
Belt slipping. (xx seconds to alarm)
3A
Time to stop
In seconds
Belt slipping: Stop relay about to de-energise. (xx
seconds to stop)
3B
-
Elevator stopped due to lack of acceleration.
3C
Time to stop
In seconds
Persistent alarm. (xx seconds to alarm)
3D
-
Elevator stopped: Speed has exceeded over speed
limit.
3E
-
Interlock signal off, waiting for zero speed.
3F
-
Elevator stopped: Persistent alarm condition.
40
-
Elevator stopped: Severe under speed.
41
-
Watchdog is not calibrated: Please see the manual.
42
-
Misalignment detected at the bottom of the elevator.
44
-
Wrong access code used when changing setup.
46
Speed %
Elevator speed less than alarm level (slipping)
47
Speed %
Elevator speed more than alarm level ( Over speeding)
49
-
Suspected open circuit or faulty PTC bearing
temperature sensor.
4A
-
Suspected fault on one or more MAS. Could be mains
pickup.
4E
-
Plug switch is open.
50
-
PTC Hot bearing at zone 1.
51
-
PTC Hot bearing at zone 2.
52
-
PTC Hot bearing at zone 3.
53
-
PTC Hot bearing at zone 4.
54
-
PTC Hot bearing at zone 5.
55
-
PTC Hot bearing at zone 6.
56
-
HBS is open circuit at zone 1
57
-
HBS is open circuit at zone 2
58
-
HBS is open circuit at zone 3
59
-
HBS is open circuit at zone 4
5A
-
HBS is open circuit at zone 5
5B
-
HBS is open circuit at zone 6
An example of the status code might be ‘2463’. The first status byte (byte 5) ‘24’ show
that the equipment is running within the specified alarm limits and the second status byte
(byte 4) ‘63’ indicate that the speed is 99% if it’s calibrated value. Where a value is not
shown or a ‘-‘is used in the table, this indicates that any data present in this field should
be ignored.

Watchdog NTC to F500 PGW CAI REV0 July 2014
13
Several different conditions may occur at the same time whilst the Watchdog is
operating. If the Watchdog is running within calibrated range but also detects a motion
sensor fault then the information returned may look something like this.
‘2463’ Running at 99% of calibrated speed.
Followed three seconds later by
2D--’ Misalignment detected at the top of the elevator.
Followed three seconds later by
‘3CAA’ Persistent alarm, 170 seconds to go.
The messages would then repeat with any new values in the status data field.
Due to some limitations in the speeds involved in updating the Watchdog information,
rapid changed of data could be missed or be present for only a very short period of time.
If the Watchdog is placed in one of the two test modes, the messages below will be
returned in the following order.
Bytes 3
and 2
Bytes 5
and 4
The first two bytes show the speed data and the second two
bytes show the status and status data.
xx & xx
06 & xx
Over speed Stop as a percentage of calibrated speed.
xx & xx
05 & xx
Over speed Alarm as a percentage of calibrated speed.
xx & xx
02 & xx
The actual calibrated speed
xx & xx
03 & xx
Under speed Alarm as a percentage of calibrated speed.
xx & xx
04 & xx
Under speed Stop as a percentage of calibrated speed.
-----
07 & --
Performing internal test.
----
4C & --
Testing the Alarm relay.
----
4D & --
Testing the Stop relay.
Codes 4C and 4D are only returned if the extended test is in operation.
Under speed alarm and stop in % (Byte 7, 6)
These two bytes show (in % of calibrated speed) the under speed alarm and stop levels.
These represent the point at which the Watchdog will generate an alarm or stop condition.
Example, if byte 7 is ‘0A’ and byte 6 is ‘14’ then this means that the Watchdog will
generate an under speed alarm at 10% (0A) below calibrated speed and will generate a
stop condition at 20% (14) below the calibrated speed.
Over speed alarm and stop in % (Byte 9, 8)
These two bytes show (in % of calibrated speed) the over speed alarm and stop levels.
These represent the point at which the Watchdog will generate an alarm or stop condition.
Example, if byte 7 is ‘0A’ and byte 6 is ‘14’ then this means that the Watchdog will
generate an over speed alarm at 10% (0A) above calibrated speed and will generate a stop
condition at 20% (14) above the calibrated speed.

Watchdog NTC to F500 PGW CAI REV0 July 2014
14
Current calibration value in PPM (Byte 11, 10)
These two bytes represent the current calibration speed value in Pulses Per Minute
(Default). The representation can be changed to other scaled values by using the display
scaling value below. Refer to the Watchdog manual for further details about display
scaling.
Display scaling factor (Byte 13, 12)
These two bytes contain a value which is used by the Watchdog to scale the information
on the display into a format which represents more accurately what the elevator is doing.
The default scaling factor (04B0) results in the display showing the current speed in
PPM. Refer to the Watchdog manual for further details about display scaling.
NTC Temperature 1 and 2 (Byte 15, 14)
These two bytes show the actual temperature of temperature sensors 1 & 2. The values
are in Dec C or Deg F according to the settings on the Watchdog. Refer to the Watchdog
manual NTC section for more detail.
NTC Temperature 3 and 4 (Byte 17, 16) & NTC Temperature 5 and 6 (Byte 19, 18)
See the detail above for temperature sensors 1 and 2
NTC temperature sensor status 1 and 2 (Byte 21, 20)
These two bytes show the current status of temperature sensors number 1 & 2.
If byte 21 is 0 then sensor 1 is NORMAL
If byte 21 is 1 then the temperature of sensor 1 is HIGH so an alarm has been generated.
If byte 21 is 2 then sensor 1 may be OPEN circuit
If byte 21 is 3 then sensor 1 may be SHORT circuit
NTC temperature sensors 2 to 6 operate in an identical manner as described for
sensor 1 above.
Sensor 1 and sensor 2 alarm level (Byte 27,26)
These two bytes represent the alarm value for the temperature sensor. The default values
for this alarm level are ‘9E’(158) when measuring in Deg ‘F’ and ‘50’(80) when
measuring in Deg ‘C’. Refer to the Watchdog manual for further detail regarding this
value.
Sensor 3 and sensor 4 alarm level (Byte 29, 28) & Sensor 5 and sensor 6 alarm level
(Byte 31, 30) operate in an identical manner as described above.
Number of sensors in use (Byte 33)
Byte 33 shows the total number of NTC temperature sensors that are currently being
monitored by the Watchdog. This value ranges from 0 to 6. See the watchdog manual
for further detail.

Watchdog NTC to F500 PGW CAI REV0 July 2014
15
Relay status (Byte 32)
This byte contains information relating to the status of the Watchdog LED’s and Relays.
Although the byte is represented in Hexadecimal converting it to binary helps to explain
the contents a little better.
0000:0000 The left hand four bits are always 0000 and can be ignored.
0000:0000 The right hand four bits contain the following information.
: This bit indicates the condition of the STOP Led (1=ON: 0=OFF)
: This bit indicates the condition of the ALARM Led (1=ON: 0=OFF)
: This bit indicates the condition of the STOP Relay (1=ON: 0=OFF)
: This bit indicates the condition of the ALARM Relay (1=ON: 0=OFF)
Not used and always ‘0000’
When a relay is considered to be ‘ON’ we mean energized and when ‘OFF’ we mean de-
energized.
0000:0000 = 00 then no conditions exist
0000:0010 = 02 then the alarm Led is on
0000:1010 = 0A then the alarm Led and Alarm Relay are active
0000:0011 = 03 then both Led’s are ‘on’ and both Relays are ‘off’ (de-energized)
Persistent alarm value NTC only (Byte 35)
This is how long the temperature alarm will take in seconds before stopping the elevator.
The default value is ‘B4’ 180 seconds. If this value reaches ‘0’ then the elevator will be
stopped.
Update counter (Byte 34)
Every time the F500 successfully receives information from the chosen watchdog, then
this counter value will be incremented by 1. The watchdog treats serial communications
as low priority so occasionally requests for data can be ignored. It is advisable to keep
checking this value so as to know when new data has arrived in the F500. The counter
will increment from 0 to 255 and then return to 0 again in a continuous loop.
Below is an example of the data returned when the F500 is polling Watchdogs

Watchdog NTC to F500 PGW CAI REV0 July 2014
16
Words 1 to 17 (pink) represent Watchdog 1. These are currently all 0 because watchdog
1 isn’t present at this time. Words 18 to 34 (green) represent Watchdog 2. Word 18
which is 0484 HEX tells us that the Watchdog is currently running at 1156 pulses per
minutes. Word 19 which is 2465 HEX tells us that the Watchdog is ‘running (24) at
101% (65) of the calibrated speed. The remainder of the information in the example can
be decoded using the information as previously described. Words 35 to 51 (blue)
represent Watchdog 3. Word 35 which is 0000 HEX tells us that the Watchdog is
currently NOT running. Word 36 which is 4100 HEX tells us that the Watchdog is in
fact NOT calibrated (41), see the Watchdog manual for more detail about calibration.
Diagnostics Display.
The F500 Elite is equipped with a simple RS232 serial interface. This interface can be
used to monitor the communications with the Watchdog Elite. The information displayed
contains diagnostic data about the Fieldbus module and Watchdog number 1. A VT100
or compatible display terminal should be used to display the information.
Above is an example screen image from the diagnostics display. The information
displayed will vary slightly dependent upon the fieldbus interface used.
CBU Version = X.XX –This is the control base unit software version.
API Version = X.XX –This is the application interface software version.
FBI Version = X.XX –This is the Fieldbus interface software version.
ABI Version = X.XX –This is the AnyBus interface software version.

Watchdog NTC to F500 PGW CAI REV0 July 2014
17
Fieldbus type = Profibus DP –This describes the type of Fieldbus module which is
installed in the F500 Elite. If the Fieldbus module is faulty some or all of this data will
change to suggest which area may be at fault. For example, FBI version number might
become 245.55. An unusually large number such as this is not usually associated with a
normally functioning module and would suggest that the Fieldbus interface controller has
failed. In the event of this or any other fault, contact your supplier.
The sequence S2468E indicated that the system has initialised correctly, a deviation from
this indicates that one or more parts of the initialisation process has failed. If this is the
case, recycle power and see if this clears the problem. If you still have problems with the
initialisation of the unit contact your supplier and tell them what you see on the
diagnostics display. The main area of the display shows the complete data from
Watchdog address number 1 as described on pages 9 to 15 of this manual.
Diagnostics LED.
Located on the main circuit board, just above the RS485 connections to the Watchdog
you will find an LED indicator (usually RED). This indicator will flash every time the
F500 attempts to communicate with the Watchdogs. The LED will normally flash at a
consistent rate followed by a very short pause. The short pause indicates that the F500 is
updating the information which it stores internally. A significant deviation from this
sequence is an indication that there is a problem. If this happens, contact your supplier
for further information.

Watchdog NTC to F500 PGW CAI REV0 July 2014
18
CHECK LIST
For problems after initial start-up
1. Is there excessive interference on the electrical power supply? Power
conditioners and surge (spike) suppressor may have to be fitted.
2. Has the wiring for the Watchdog and Fieldbus been routed away from power
cables?
3. Is the F500 Elite circuit properly grounded?
4. Is the Micro-processor control unit overheating, if so mount in temperature-
controlled environment of maximum temperature 104°F (40°C).
5. Check that high powered ‘Walkie Talkie’ radios are not operated immediately
near the control unit or Watchdogs as this will affect the performance.
6. Check that the communications/power cable is connected correctly and in
accordance with DRG A,B,C and E.
7. Check that there is no exception status reported.
8. If only part of the diagnostics data is displayed on the terminal screen then turn
the F500 Elite off then back on again without removing power to the display
terminal.
9. If the Watchdogs are not responding or are intermittent, check that the termination
resistors are correctly fitted.

Watchdog NTC to F500 PGW CAI REV0 July 2014
19
CONTACT INFORMATION
WWW.GO4B.COM

Watchdog NTC to F500 PGW CAI REV0 July 2014
20