4tech MiniCom Guardian Instruction manual

Quick Start Manual MiniCom®Guardian
Temperature
Humidity
Power supply ®
Monitoring
This kit contains:
MiniCom Guardian
Combined sensor for Temperature and Humidity
1 meter blue CAT5 cable
Power supply 230V AC/4,5V DC
Battery Unit
DIN mounting Rail
Quick Start Manual (this)
An innovative monitoring system for your environment
4tech AS, Solbraaveien 49, N-1383 Asker, Norway
Phone: +47 32 79 22 30 - Fax: +47 31 40 03 20
mail: sales@4tech.no - www.4tech.no
Please visit
WWW.4tech.no
for further information.
You need to:
Order a SIM Card from your local Network supplier!
SIM
MiniComGuardianQuickStart.INT1.0

Install the Guardian control unit in a dry indoor
environment.
1. Remove the front cover, and insert the SIM card
into your Guardian control unit (located in the
battery compartment).
2. Make sure the SIM-lid is properly mounted. (Slide
forward and you should hear a click.)
3. Mount the battery plug, and fit the battery into the
slot.
4. Mount the DIN rail with screws or two folded tapes
where you decide to mount your Guardian.
5. Mount your Guardian control unit onto the DIN rail
6. Mount the sensor (The blue box) at the location to
be monitored.
7. Attach the sensor to the Guardian control unit in
the left hand socket by using the blue CAT5 patch
cable.
8. Connect the power supply to the right hand socket
of the Guardian. Important: Connect your
Guardian to the same power outlet as your UPS or
server is connected to.
1 Installation Slide until you hear
the “click”
Temperature
Humidity
Power supply ®
Monitoring
server is connected to.
2 Enter PIN code
When the Guardian is first started with a SIM-card, and
the PIN code is enabled, it will ask for a PIN code
with a sequence of audio signals. (PIN code is only
requested for the first start up)
Enter the pin code using the red button. Each digit
is entered by pressing the button the corresponding
number of times (1= 1 push, 5= 5 pushes and
0= 10 pushes). Each digit will be repeated from
Guardian before the next digit can be registered.
Please note: If you make a mistake, wait until you get
the same sequence of signals and start again.
Please note: If you enter the wrong PIN code three
times, and have to enter PUK code, we recommend
to insert the SIM card in your mobile phone to enter
the PUK-code.
3 Configuration
Before you start to configure your Guardian we
suggest that you register the telephone number and
serial number. (The telephone number is identified by
your SIM-card, and the serial number is located on a
label on the back side of your Guardian)
Power
CAT5 Patch

The MiniCom Guardian is configured using simple SMS
commands. Several commands may be sent as one
single SMS separated by spaces.
Example (max/min values equals factory presets):
ID=”Server room” MINTEMP=18 MAXTEMP=26
MINHUM=10 MAXHUM=60 PHN=1,[your phone
number]
This command sets the “name” of the Guardian to
“Server room”, the minimum temperature limit to 18°C,
the maximum temperature limit to 26°C, the relative
humidity minimum limit to 10% and the relative humidity
maximum limit to 60%. Alarms will be sent to your
phone number. Please note that the ID requires double
quotation marks (“ “) if the string includes spaces.
1. Send the configuration commands to the Guardian
phone number
as
shown in the example
.
Temperature
Humidity
Power supply ®
Monitoring
Telephone no:
Serial no:
phone number
as
shown in the example
.
The command results in the following response from
Guardian: Server room:
Temp: 23,8’C (min:18 max:26)
Humidity: 42% (min:10 max:60)
No active alarms
A second response from the MiniCom Guardian:
MID=MC <serial number> OK
The number is the serial number on your Guardian. The
“OK” is an acknowledge that the commands have been
accepted. If anything was erroneous, you will get the
“ERROR” response.
2. Set MiniCom Guardian distinctive phone number by
sending: PH=the inserted SIM card number
The command results in following response from the
Guardian:
MID=MC<serial number> OK
Please visit
WWW.4tech.no
for further information.

Command example Description
MAXTEMP=30.5 Set the maximum accepted temperature limit (°C) for triggering the
MAXTEMP alarm. The limit is set to 30.5 °C.
MINTEMP=-5 Set the minimum accepted temperature limit (°C) for triggering the
MINTEMP alarm. The limit is set to -5 °C.
MAXHUM=80 Set the maximum accepted humidity limit (% rel) for triggering the
MAXHUM alarm. The value is set to 80%.
MINHUM=10 Set the minimum accepted humidity limit (% rel) for triggering the
MINHUM alarm. The value is set to 10%.
NOLIMITS
Reset
all
limits
(min
and
max
for
temperature
and
humidity)
.
Temperature
Humidity
Power supply ®
Monitoring
It is important to connect the Gardian to the power supply you want to monitor. If you
experience power outage the Guardian will give you an alarm: Main power missing, temp,
hum, and active alarms. The Guardian is now operating on battery, and continues to monitor
your environment for several hours. When power is restored, you receive a new SMS: Main
Power OK, temp, hum, and active alarms. We recommend to change the battery every 2
years. You even receive an SMS when this time is reached.
The MiniCom Guardian monitoring power supply:
Configuration commands:
NOLIMITS
Reset
all
limits
(min
and
max
for
temperature
and
humidity)
.
PH=+4712345678 Set the phone number to the inserted SIM card. Used to synchronise
the system clock by sending SMS to itself. The phone number is set to
“+4712345678”.
PHN=2,12345678 Set the phone number at position 2 to the given number (12345678).
You can configure up to four different phone numbers for alarm
notifications.
PHN=4, Delete phone number at position 4.
INFO Send INFO to get the current status information and a list of active
alarms.
CONFIG Get the current configuration.
4tech AS, Solbraaveien 49, N-1383 Asker, Norway
Phone: +47 32 79 22 30 - Fax: +47 31 40 03 20
mail: sales@4tech.no - www.4tech.no
Download the complete user manual at www.4tech.no