7bit Synapse User manual

Synapse
MQTT/Modbus TCP/8DI/8DO(R)/32x1-Wire/AC
Industrial digital input/output modulefor
remote processcontrol and data acquisition
Thank you for choosing our product. The 7bit Synapse module designed as a remote
Ethernet DIO, counter and 1-Wire temperature input module for industrial
automation and monitoring applications. MQTT connectivity option allows you to
create cloud-based monitoring & control applications. Built-in AC power supply and
2-port Ethernet switch simplify installation and cabling, extending network length and
allowing to install the module into existing network w/o extra equipment. The setup
is made easy with the web-config page.
Module Synapse is an OPEN-TYPE device. It should be installed in a control
cabinet free of airborne dust, humidity, electric shock and vibration
The device is operating at dangerous voltage rating. High voltage also may
occur at output terminals during it work. Please do not touch these
terminals when the device is powered on. DO NOT connect AC power to any
of input terminals, otherwise serious damage may occur. Please double
check all wiring before Synapse is getting powered up
The following abbreviations are used for Modbus registers functions: C -
Coils, DI - Digital Inputs, HR/IR –Holding/Input Registers, and their data
format: W - Word (2 bytes), DW - Double Word, b –bit. R/W –Read/Write
mode.
1. Technical specifications
Power supply
100 - 220 VAC, 50/60 Hz, Max power consumption: 3W
Communication
2 x Fast Ethernet switch, Modbus TCP, MQTT
INPUTS
Points
8 x DI with single common,
Isolation voltage 5000 Vac / 500 Vdc, 12 - 24 AWG
Type
24 VDC (SINK / SOURCE) or internal isolated DC supply
Counters & Time on
totalizers
8 + 8 / 8 + 8 (for each DI & DO channel), 32-bit capacity,
static memory, 1 kHz max. sw. frequency
Jitter filter
Individual for each channel, adj. 0 ~ 20ms (default 20ms)
OUTPUTS
Points
8xDO, 12 - 24 AWG, two groups DO 1 - 4 and DO 5 - 8
(SSR or Relay or SSR + Relay)
Relay
220 VAC / 30 VDC, 2A.
Max. frequency: 1 Hz, ~10 ms response time
SSRs*
AC, 85 - 220V 2A, Zero-crossing switching.
Max. frequency: 100 Hz
1WIRE
Points
Up to 32 digital thermometers DS18B20
Bus length
Up to 200 m.
ENVIRONMENTAL
Operation -
Storage / Protection
0°C - 55°C, 5 - 90% (w/o condensation), -25°C - 70°C, 5 - 95%
IP40
Weight
200 g.
* made by order
2. Dimensional drawing
3. Wiring
3.1 Ethernet. Synapse has an embedded switch which make easy toconnect numerous
modules simply, connecting them to each other in "daisy chain". As it is true Ethernet
witch, each connection may be up to 100 m. It is also possible to connect the device
at any breaking of existing Ethernet link.
3.2 Digital inputs
Use internal power supply for powering inputs via long cables with caution
due to low voltage and voltage drop you may have unstable DI signaling
3.3 Digital outputs There are 2 groups by 4 outputs, each can be either relay or SSR
(by order) type. Due to Zero-cross detection unit, SSR provides comfort switching for
any AC load in the range 85 - 220V, 2A. Relay outputs is commonly used for dry
contacts and DC signals commutation.
To avoid sparks, limit switching currents and increase switching lifetime for
the outputs, it is strongly recommended to use extra snubber circuits for
inductive loads.
3.4 Safe power on After power on the module can restore its outputs to a previous
state. For many applications it is convenient feature, but for some not. E.g. some parts
of a heavy machine may accidentally move on repower and cause dangerous situation.
To avoid this problem now there is a special setting to choose output state after
repower:
Address
Description
Data
R/W
Default
HR35
Safety state 0 –off, 1 - on
W
R/W
0 (off)
3.5 PWM for triac outputs The duty cycle is set as 0 .. 100 which means how many
periods of AC current from one hundred will power the load. So the time base of the
PWM is 100 * 20 ms (1/50Hz) = 2 seconds. Before using DO for common ON –OFF
control set PWM values to 0.
Address
Description
Data
R/W
Default
DI0 ~ DI7
Digital Inputs
b
R
-
HR20 ~ HR27
Input filters (0 - disabled)
W
R/W
20
Address
Description
Data
R/W
Default
C0 ~ C7
Digital outputs
b
R/W
-
Internal
supply

Address
Description
Data
R/W
Default
HR111 ~ 118
DO1 ~ 8 PWM duty cycle
W
R/W
0 (No)
3.6 Predictive maintenance functions (changeover & time on counters)
Power on cycles and run hours may reduce life-time of the equipment under monitor.
Now it is possible to count them using Synapse onboard counters and totalizers:
Address
Description
Data
R/W
Default
HR0 ~ 14
DI 1 ~ 8 changeover counters
DW
R/W
-
HR60 ~ 74
DI 1 ~ 8 time on totalizers
DW
R/W
-
HR76 ~ 90
DO 1 ~ 8 changeover ounters
DW
R/W
-
HR92 ~ 106
DO 1 ~ 8 time on totalizers
DW
R/W
-
3.7 1-Wire connection The Synapse provides connection for up to 32 digital
temperature sensors DS18B20 via 1-Wirebus with a maximum length 200 m, as shown
at figure below.
Bus topology. Up to 200 meters.
Auto enumeration for 1-Wire sensors. Each DS18B20 has their own unique serial
number. Using a special search algorithm, the Synapse finds and saves the
enumeration scheme for the sensors found in the static memory. New sensors still can
be added to the existing enumeration by:
▪powering on or resetting the module
▪writing non-zero value into HR33 register
Address
Description
Data
R/W
Default
IR0 ~ IR31
Temperatures 1 ~ 32
W
R
-1000*
HR33
Total sensors quantity / Init**
W
R/W
0
* -1000 is displayed if a sensor is not present or damaged
** writing 0 to HR33 clears the enumeration.
4. Configuration
The factory network default settings for the Ethernet interfaces is a DHCP client. So,
after power on and plugging it into your router network it automatically will be added
to your network. You may setup a static DHCP lease for the module, or use manual IP
network setup.
4.1 Configuration mode for IP settings When you have a device with unknown
address and want to make quick IP setup, switch the module to the CONFIGURATOIN
MODE. Hold the reset button during reboot for a few seconds (status LED will be
blinking frequently). The module will start with 192.168.4.1 address. In this mode you
can change setting either with Configuration Web server or with Modbus setting
registers. To switch back to normal mode, reboot the module.
4.2 Configuration Web server In the configuration mode, there is Configuration
web-page available on the 192.168.4.1. Instead of Modbus register, you can use this
page for module setup. The page can be switched off during setup. To enable it again,
use the following register:
Address
Description
Data
R/W
Default
HR39
Configuration Web server enable
W
R/W
1 (yes)
IP configuration It can be done either with the web page or the Modbus registers:
Address
Description
Data
R/W
Default
HR40
Static IP enable
W
R/W
0(no)
HR41 ~ HR44
IP address octets (x.x.x.x)
W
R/W
192.168.1.2
HR45 ~ HR48
Mask octets (x.x.x.x)
W
R/W
255.255.255.0
HR49 ~ HR52
Gateway IP address
octets
W
R/W
192.168.1.1
MQTT configuration
Visit level2.webhmi.com.ua to learn
about IoT applications with Synapse
MQTT capability. Use ready “New device”
tool to quickly create your register set in
Level2 / WebHMI projects.
5. Diagnostics
The normal LED state upon power on is as follows:
▪red POWER - always on.
▪green SYSTEM –is blinking once a second (two times faster in configuration
mode)
▪yellow 1WIRE –blinks when the sensors are polled
The DI/DO LEDs reflects the actual signal states on terminals. During normal boot
process, DI/DO ticks in series.
Use “ping” command to check network connection and Modbus/MQTT testing tools
to test the protocol connection.
In case of troubles with adding temperature sensors, the most probable cause is the
length of 1-Wire bus or its topology (signal or power attenuation, caused too long line,
interference due to side branches etc.). First of all, try to connect sensors with short
wires. If ok, then check wiring (refer to general Maxim 1-Wire recommendations).
Synapse has internal watchdog, which may reboot the device in case of accidental
malfunction. Refer to the following diagnostic registers to check if failures might have
occurred.
In a case the device doesn't working properly, please contact to your supplier.
6. For more information
If you have any questions or problems related to the operation of the 7Bit™
products, please contact to the unified support service +38 (056) 796-96-90,
info@webhmi.com.ua
7. Warranty
The company of “Distributed Data Systems LLC”, the manufacturer of 7Bit Synapse IO
module (hereinafter referred to as the Manufacturer), expresses its great gratitude for
your choice. We did our best to ensure that this product met your requirements, and
the quality corresponded to the best standards. The manufacturer sets the life of the
Synapse IO module to 10 years in case of its proper usage. The service life is calculated
from the date of manufacture of the requirements for warranty obligations and for
free repair (replacement of the product) in the case of failure to comply with the
conditions set forth below. All the terms of the warranty and free repair (replacement)
are in force under the law on consumer protection.
The manufacturer sets a warranty period, counted from the date of sale, and the
period of free repair (replacement), subject to compliance with the rules of operation,
12 months. Replacement of defective parts (assemblies, assembly units) in the product
during the warranty period does not lead to the
establishment of a new warranty period for the entire product, or for replaced parts.
The manufacturer declines all responsibility for the possible harm, directly or indirectly
caused by the Synapse device to people, animals, property in case event that this is
the result of non-compliance with the rules and conditions of use of the product;
Intentional or reckless actions of the buyer
(consumer) or third parties. Also, the Manufacturer declines all responsibility for the
possible damage, directly or indirectly caused by the Synapse device as a result of
alteration, damage, loss of data and information
Date of the manufacturer's QA _____________________________
Date of sell _____________________________________________
Sellers marks ___________________________________________
Buyer's signature ________________________________________
Synapse Quick guide fw ver.: 1.05 07.21
Address
Description
Data
R/W
Default
HR30
Reboot counter
W
R
-1000*
HR31, HR32
Uptime, sec. (low, high)
W
R
HR34
Free memory
W
R