AMFLOW®
A6 VALVE ACTUATOR

A6 Quick Start: H1
CONTENTS
Copyright©2016 A & H Enterprises, Inc.
All rights reserved
00000329-0900-013 * Rev. A, 07/16
Page 2 of 17
AMFLOW®
Contents
1. What is Included
2. Installation: Actuator
3. Installation: Valve
4. Wiring: H1
5. Caution Information
6. Safety Information
7. Support
8. Representatives

A6 Quick Start: H1
WHAT IS INCLUDED
Copyright©2016 A & H Enterprises, Inc.
All rights reserved
00000329-0900-013 * Rev. A, 07/16
Page 3 of 17
AMFLOW®
What is included with your Amflow®product?
☐ACTUATOR: A6
Actuator
Adjustment Handle
Adjustment Handle Mounting Screw & Lockwasher
Installation Manual & Service Manual

A6 Quick Start: H1
INSTALLATION
Copyright©2016 A & H Enterprises, Inc.
All rights reserved
00000329-0900-013 * Rev. A, 07/16
Page 4 of 17
AMFLOW®
Installation: Actuator
Step 1
Cut-out panel for mounting per instructions in Installation
Manual.

A6 Quick Start: H1
INSTALLATION
Copyright©2016 A & H Enterprises, Inc.
All rights reserved
00000329-0900-013 * Rev. A, 07/16
Page 5 of 17
AMFLOW®
Step 2
Attach actuator base plate assembly to front of panel.
Step 3
Mount actuator to base plate assembly using M6x16 SHCS.

A6 Quick Start: H1
INSTALLATION
Copyright©2016 A & H Enterprises, Inc.
All rights reserved
00000329-0900-013 * Rev. A, 07/16
Page 6 of 17
AMFLOW®
Step 4
Prior to installing valve, confirm handle is in manual position.
AUTOMATION MODE
(Handle at Side)
MANUAL MODE
(Handle at Front)

A6 Quick Start: H1
INSTALLATION
Copyright©2016 A & H Enterprises, Inc.
All rights reserved
00000329-0900-013 * Rev. A, 07/16
Page 7 of 17
AMFLOW®
Installation: Valve
Step 1
Place FLANGE ADAPTOR onto VALVE STEM prior to installation.
Step 2
Insert VALVE ADAPTOR LINK into FLANGE ADAPTOR.
Place valve into BEARNG HOUSING.
VALVE ADAPTOR LINK
FLANGE ADAPTOR
BEARING HOUSING
VALVE ADAPTOR LINK

A6 Quick Start: H1
INSTALLATION
Copyright©2016 A & H Enterprises, Inc.
All rights reserved
00000329-0900-013 * Rev. A, 07/16
Page 8 of 17
AMFLOW®
Step 3
While valve is being inserted into BEARING HOUSING; rotate
valve to align VALVE ADAPTOR LINK while handle is in manual
mode.
Step 4
Once properly aligned and engaged, tighten three (3)
SETSCREWS to lock valve in place.
SETSCREWS
SETSCREWS

A6 Quick Start: H1
INSTALLATION
Copyright©2016 A & H Enterprises, Inc.
All rights reserved
00000329-0900-013 * Rev. A, 07/16
Page 9 of 17
AMFLOW®
Controls: Applicable to AM7E-001 Valve Only
There are two controls used to operate the AM7E-001 flow control valve:
The first control is the SWITCH by which the operator can select
a high or low flow range.
The second is the flow rate ADJUSTMENT KNOB. This control
knob allows the operator to set a desired flow rate in either the
high flow or low flow range.
AM7E-001 ADAPTOR with
SWITCH
View of AM7E-001
looking up from bottom of OUTLET BODY
toward bottom of ADAPTOR

A6 Quick Start: H1
WIRING
Copyright©2016 A & H Enterprises, Inc.
All rights reserved
00000329-0900-013 * Rev. A, 07/16
Page 10 of 17
AMFLOW®
ACTUATOR WIRING: H1
Step 1
Provide 24VDC supply capable of providing up to 3 amps
current.
Step 2
Requires a minimum of 5 connections for H-1 operation.
Step 3
Requires a minimum of 9 connections for set-up , Industrial
Ethernet and H-1 communication.
Terminal block wiring reference for field connections
WARNING
Incorrect wiring may damage the unit!

A6 Quick Start: H1
COMMUNICATIONS
Copyright©2016 A & H Enterprises, Inc.
All rights reserved
00000329-0900-013 * Rev. A, 07/16
Page 11 of 17
AMFLOW®
H1 COMMUNICATION SET-UP
CAUTION
Parameters are pre-set at the manufacturer.
Step 1
Connect Industrial Ethernet cable between actuator and DHCP
server or DHCP router
Step 2
Launch flash enable internet web browser.
Step 3
Type in web address found on actuator.
Step 4
Follow set-up procedures.
NOTE
DHCP “Dynamic Hosting Configuration Protocol” is a method that automatically
assigns IP addresses to devices connected to a network without manually
configuring everything connected to a computer or server. Due to the wide variety of
computers, networks, servers, routers and operating systems, a “DHCP” device is
highly recommended for a quick and easy set-up. The “DHCP” device is either a
server or router depending upon the end users network configurations.
If an end user is manually configuring their network, they should contact their IT
department.

A6 Quick Start: H1
CAUTION
Copyright©2016 A & H Enterprises, Inc.
All rights reserved
00000329-0900-013 * Rev. A, 07/16
Page 13 of 17
AMFLOW®
Caution
VALVE INSTALLATION
RECOMMENDATION
The purge port on an Amflow®valve should be connected to a “return to
tank line” with a needle valve. This aids in the following:
Helps remove air from valve upon start-up.
Provides a means of cleaning jets with high pressure in the event of
chemical build-up.
IMPORTANT
Proper filtration is critical for low flow applications.
RECOMMENDATION: 50 micron filter
VALVE START-UP
Step 1
Turn adjustment knob counter-clockwise to a soft “Stop”.
Then, turn one (1) revolution clock-wise.
Step 2
Close Inlet Isolation valve of each valve in system
Step 3
Start pump
Adjust system pressure to accommodate pressure requirements
CAUTION
IMPROPER INSTALLATION AND START-UP MAY CAUSE DAMAGE
IMPORTANT
This is especially important for valves configured to flow less than 5 lph

A6 Quick Start: H1
CAUTION
Copyright©2016 A & H Enterprises, Inc.
All rights reserved
00000329-0900-013 * Rev. A, 07/16
Page 14 of 17
AMFLOW®
Step 4
VERY SLOWLY open Outlet Isolation Valve.
Step 5
VERY SLOWLY open Inlet Isolation Valve.
This allows fluid to be introduced gradually.
Once Amflow®valve has been filled with fluid, there is little risk of
damage.
Step 6
Allow sufficient time for media to flush any trapped air out of valve.
Step 6
Once all air is eliminated, begin system operation.
Step 7
Turn valve adjustment handle to ensure that it turns easily.
WARRANTY
Amflow®warranty does not cover Amflow® valves if proper chemical filtration is
not provided. Reference full warranty at back of Installation and Service Manual
provided with your Amflow®product.
PROCEED with CAUTION
This is very important, especially at high system pressures to prevent potential
damage to seals and other internal components of valve.
IMPORTANT:
On valves that are configured to meter less that 10 liters per hour it is very important
that at least 20 minutes be allowed for this step.
Trapped air can cause the set flow rate of valve to diminish slowly.

A6 Quick Start: H1
SAFETY
Copyright©2016 A & H Enterprises, Inc.
All rights reserved
00000329-0900-013 * Rev. A, 07/16
Page 15 of 17
AMFLOW®
Safety SAFETY INFORMATION
Usage
Use products only within range of pressure and temperature conditions
indicated on product data sheet.
Do not use with chemicals which are incompatible with 316SS or with
seal materials.
Equipment is certified for Group 2 Category II.
Equipment should not be used in systems requiring a higher level of
certification.
Faults and Damage
The safety features and integrity of products may be compromised by any of the
following:
External damage to body.
Exposure to pressure loads in excess of maximum rated pressure.
Maintenance performed by improperly trained personnel.
Protection from Pressure Releases
To avoid injury due to release of high pressure, use only adaptors and
fittings rated to withstand appropriate pressure.
Ensure all adaptors and fittings are securely connected.
To avoid a violent release of pressure, slowly bleed off pressure before
attaching or removal from pressure line.
Avoid Mechanical Damage
Caution must be observed not to damage any threaded components
during maintenance procedure.
Such damage could compromise the pressure safety factor of filter.
When replacing seals, care must be exercised to avoid damage to
sealing surfaces.
Damage could lead to a sudden release of pressure during
operation.

A6 Quick Start: H1
SUPPORT
Copyright©2016 A & H Enterprises, Inc.
All rights reserved
00000329-0900-013 * Rev. A, 07/16
Page 16 of 17
AMFLOW®
Support
To order Amflow® products, spare parts or to receive assistance contact:
A & H Enterprises, Inc. (Amflow®)
+425.883.4040
ADDRESS CORRESPONDENCE TO:
A & H Enterprises, Inc.
11812 NE 116th Street
Kirkland, WA. 98033
E-mail: [email protected]
Fax: +425.823.1962
Visit us at www.amflow.com

A6 Quick Start: H1
REPRESENTATIVES
Amflow®
A & H Enterprises, Inc.
11812 NE 116th Street
TEL:
+425.883.4040
Kirkland, WA 98034 USA
FAX:
+425.823.1962
www.amflow.com
EMAIL:
Copyright©2016 A & H Enterprises., Inc. All rights reserved
Page 17 of 17
AMFLOW®
Representatives
AMFLOW®NORGE
Norway, Sweden, Denmark, Netherlands, Germany,
U.K., Italy
Prinsens vei 12
4315 Sandnes
Norway
Telephone:
+47.922.19.656
Fax:
+47.520.00.591
E-mail:
leif.egil.pettersen@amflow.no
AMFLOW CONTROLS ASIA SDN. BHD.
Malaysia, Indonesia, Singapore, India, Thailand,
Vietnam
No. 1701 Block 1, TTDI ADINA
Jalan Judo 13/45, Seksyen 13
40675 Shah Alam, Selangor
Malaysia
Telephone:
(+603) 5523.8418
Mobile:
(+6012) 3323.118
E-mail:
amflowcontrols@gmail.com
SUDIFLOW INTERGRATED SERVICES, LTD.
Nigeria
25 Elelenwo Road
Port Harcourt,
Nigeria
Telephone:
+234.803.309.1405, +705.679.4894
E-mail:
Table of contents
Other A & H Controllers manuals