Ksenia intro Manual

intro - Door Controller
Installation and Configuration
Manual
www.kseniasecurity.com

Ksenia Security SpA reserves the right to change or update the
information contained in this document at any time and without
notice and is not responsible for any errors or omissions.
Manuale Utente Amministratore
www.kseniasecurity.com
code R30057.111 12/2023

intro Installation and Configuration Manual
3 R30057.111
Overview .......................................................................................................................5
Architecture solution .................................................................................................... 6
Technical data ............................................................................................................... 6
Quantity data ................................................................................................................ 7
Description of the product ........................................................................................... 7
Labels on plastic box and terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Jumper settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Status LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
External power supply description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Installation .................................................................................................................. 10
Mounting options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Wiring the system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Wiring intro SYSTEM BUS to lares 4.0 KS-BUS 11
Wiring intro PERIPHERALS BUS with ergo-X/volo/volo-in devices 11
Wiring LOCK1 output 12
Wiring input terminals 12
Wiring outputs terminals 13
Wiring External power supply supplied by Ksenia and Battery 14
intro module configuration ........................................................................................ 15
intro BUS Peripheral menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Real time data 15
Step-by-step configuration of intro module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Enabling DOTL and FD alarms 19
Enabling lock status reading 19
Configuring two devices to authenticate users authorized to pass through the gate . . . . . . . . . . 19
Configuring users authentication and authorization to pass through the gate . . . . . . . . . . . . . . . 20
Configuring User Profiles (Installer only) 20
Configuring Access Permissions and Gate Association 20
Configuring users and authorize them to pass through the gate 21
Commands - Open door . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Diagnostic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

intro Installation and Configuration Manual
R30057.111 4

intro Installation and Configuration Manual
5 R30057.111
Overview
intro module (code KSI2800000.300) is a BUS peripheral that was designed to realize an effective
integration process between Security and Access Control functions of lares 4.0 platform. Protecting
residential structures access, buildings and/or restricted areas of them, by unauthorized persons is its main
purpose.
intro module, completely developed, from design to final production, by Ksenia in Italy, is a BUS peripheral
connected to the lares 4.0 control panel via KS-BUS and it represents the physical core of the Access Control
system designed by Ksenia.
Each single intro module allows you to wire up and manage a complete gate structure with:
• door with a third-party electronic lock;
• magnetic contact (external or internal if provided inside the lock) to control the opening/closing of the
door;
• two devices(*) with RFID reader (volo, volo-in readers or ergo-X keypad) placed near the door,
necessary to authenticate authorized users;
• RTE (Request To Exit) button installed inside the restricted area to unlock it;
• a preconfigured output for optical (flashing lamp) or acoustic (buzzer) for DOTL (Door Open Too Long)
and FD (Forced Door) alarms.
intro module is equipped with:
• two BUS, one for connecting lares 4.0 KS-BUS and one for connecting two peripherals(*) chosen
between volo, volo-in or ergo-X keypad;
• one output to control the lock with 30Vdc -8A relay;
• one output for programmable function with 30Vdc -8A relay;
• 4 more outputs at 30Vdc -1A (two of which for programmable function), out of 6 total;
• one input to monitor the BOLT physical status;
• one input for connecting the magnetic contact of the door;
• one input for connecting the RTE (Request To Exit) button;
• two inputs to monitor the presence or absence of mains power and battery charge(**);
• 2 more programmable inputs with programmable balancing, out of 7 total.
intro module can be remotely configured via the Ksenia SecureWeb cloud and uses a new logic
programming to facilitate the configuration work of specialized personnel in the most effective way.
(*) The connection of other peripherals, in addition to those indicated, is not recommended.
(**) If the power supply provides this information.

intro Installation and Configuration Manual
R30057.111 6
Architecture solution
Technical data
• 1 door managed
•2BUSinterfaces:
• System BUS: 3 wires (A, B, -) link to lares 4.0 (NO power from KS-BUS)
• Peripherals BUS: 4 wires (+, A, B, -) link to two local peripherals (volo, volo-in or ergo-X) supporting the
access control function
• Power supply: 11...28 Vdc (from external power supply) (power supply on [+] to BUS Peripheral:
+11...14Vdc max 0,5A)
• Consumption: < 300 mA
• Memory / Data storage: 4Mbyte
• 6 outputs (see note*) characterized as follow:
• 1 preconfigured power relay, maximum rating 30Vdc 8A, to control the lock door
• 1 power relay, maximum rating 30Vdc 8A, for programmable function
• 1 preconfigured relay for Gate status, maximum rating 30Vdc - 1A
• 1 preconfigured relay for Alert, maximum rating 30Vdc - 1A
• 2 relays, maximum rating 30Vdc - 1A, for programmable function
• 7 inputs: 5 preconfigured inputs and 2 inputs (NC/NO or Balanced) 5V - 20mA
• Tamper protection against opening
• LED status indicator: RGB LED
• Operating temperature: -10... +55 °C (For Indoor Use Only)
• Protection class: IP30
• Dimensions: 105x115x58mm (LxWxH) (6 DIN modules including field connectors)
• Weight: 170 g (PCB including field connectors)
• Mounting: DIN rail mounting or inside a suitable metal or plastic cabinet (it is the plastic cabinet
recommended by Ksenia code KSI2800001.300)
Note: (*) Resistive load. In case of inductive load, if not present, please add an external free-wheeling diode
in order to preserve the contact life.

intro Installation and Configuration Manual
7 R30057.111
Quantity data
* Extended number is available under license, contact our sales team for information.
Technical data, appearance, functionality and other product characteristics may change without notice.
Description of the product
Labels on plastic box and terminals
lares 4.0 models wls 96 16 40 40 wls 140 wls 644 wls
Maximum number of intro modules 4 4 8 8 12 (20*) 16 (30*)
No. Labels Function Description
36 +V DC-IN: positive pole of external power supply source
35 - DC-IN: negative pole of external power supply source
34 cL1 LOCK#1: Common pin of power relay where to connect external
lock power supply (30Vdc max) in the case JP1 is in position 1-2
(factory default)
33 L1 LOCK#1: Output power from contact of power relay to lock#1
32 - Ground terminal
31 cO3 Output#3: common contact of output #3 (30Vdc - 8A max)
30 O3 Output#3: NC or NO (factory setting) dry contact of output #3
(depending on jumper settings)
29 - Ground terminal

intro Installation and Configuration Manual
R30057.111 8
(*) LOW BATTERY and AC MONITOR inputs work correctly with power supply provided by Ksenia.
28 i7 AC MONITOR i7: input #7(*) Closed to ground (-) = OK, Open = KO
27 i6 LOW BATTERY i6: input #6(*) Closed to ground (-) = KO, Open = OK
26 - Ground terminal
25 i5 BOLT STATUS i5: input #5
24 i4 RTE i4: input #4 Normally Open Contact, active when closed to
ground terminal (-)
23 - Ground terminal
22 i3 DOOR STATUS i3: input #3
21 i2 i2: input #2
20 - Ground terminal
19 i1 i1: input #1
18 - SYSTEM BUS Ground terminal reference signal of KS-BUS from lares 4.0 panel
17 B SYSTEM BUS B-wire of KS-BUS cable from lares 4.0 panel
16 A SYSTEM BUS A-wire of KS-BUS cable from lares 4.0 panel
15 - PERIPHERAL BUS Ground terminal reference signal of PERIPHERAL BUS
14 B PERIPHERAL BUS B-wire of PERIPHERAL BUS cable to local controlled peripherals
13 A PERIPHERAL BUS A-wire of PERIPHERAL BUS cable to local controlled peripherals
12 + PERIPHERAL BUS Positive power supply of PERIPHERALS BUS
11 O5 ALERT Output#5: NC or NO (factory setting) dry contact of output #5
(depending on jumper settings)
10 cO5 Output#5: common contact of output #5 (30Vdc - 1A max)
9 O4 GATE STATUS Output#4: NC or NO (factory setting) dry contact of output #4
(depending on jumper settings)
It automatically turns ON when the gate is disabled
8cO4 Output#4: common contact of output #4 (30Vdc - 1A max)
7 - Ground terminal
6 O2 Output#2: NC or NO (factory setting) dry contact of output #2
(depending on jumper settings)
5 cO2 Output#2: common contact of output #2 (30Vdc - 1A max)
4 - Ground terminal
3 O1 Output#1: NC or NO (factory setting) dry contact of output #1
depending on jumper settings)
2 cO1 Output#1: common contact of output #1 (30Vdc - 1A max)
1 - Ground terminal

intro Installation and Configuration Manual
9 R30057.111
Jumper settings
Jumper Setting Description Setting Description
JP1 1-2* LOCK#1 - Lock power supply input from
external source through pin cL1
2-3 LOCK#1 - Lock power input from
+V power supply input
JP3 1-2* LOCK#1 - NO contact 2-3 LOCK#1 - NC contact
JP2 1-2* Output#3 - output#3 power supply input
from external source through pin cO3
2-3 Output#3 - output #3 power input
from +V power supply input
JP4 1-2* Output#3 - NO contact 2-3 Output#3 - NC contact
JP5 1-2* Output#1 - NO contact 2-3 Output#1 - NC contact
JP6 1-2* Output#2 - NO contact 2-3 Output#2 - NC contact
JP7 1-2* Output#4 - GATE STATUS - NO contact 2-3 Output#4 - GATE STATUS - NC
contact
JP8 1-2* Output#5 - ALERT - NO contact 2-3 Output#5 - ALERT - NC contact
JP9 Open* input#2 - Std input Closed Reserved for future use
JP10 Open* input#1 - Std input Closed Reserved for future use
TAMPER Open* Trouble Closed Idle
Note: (*) Factory setting.

intro Installation and Configuration Manual
R30057.111 10
Status LED
External power supply description
• KIT Ksenia code KSI7101260.000: UPS kit 13.8V/60W, , for intro prewired on terminal blocks and
complete with fuse holder.
• KIT Ksenia code KSI7102460.000: UPS kit 27.6V/60W for intro prewired on terminal blocks and
complete with fuse holder.
Installation
Mounting options
1. on a DIN bar inside a suitable box for installation;
2. Ksenia Kit code KSI2800001.300: intro with white plastic cabinet with front opening and screw closure
and, depending on the type of lock, select between the 13.8V UPS kit (KSI7101260.000) or the 27.6V UPS kit
(KSI7102460.000).
RGB LED - Color Signaling description
Steady Red DOTL (Door open too long) or FD (Forced
Door) alarm
Blinking Red Inactive Gate (disabled)
Steady Green Door is opening
Blinking Green Active Gate (enabled)

intro Installation and Configuration Manual
11 R30057.111
Wiring the system
Wiring intro SYSTEM BUS to lares 4.0 KS-BUS
Note: DO NOT connect [+] terminal of lares 4.0 KS-BUS
Wiring intro PERIPHERALS BUS with ergo-X/volo/volo-in devices

intro Installation and Configuration Manual
R30057.111 12
Wiring LOCK1 output
Wiring input terminals
1st option:
Lock power supply directly from intro
2nd option:
Lock power supply from other source than intro

intro Installation and Configuration Manual
13 R30057.111
The intro module provides 7 inputs, 5 of which are programmed with functions already defined as
summarized in the following table:
NOTE: i1 and i2 terminals are inputs NO/NC or balanced, freely programmable.
Wiring outputs terminals
Input label Function Description
i3 DOOR STATUS To be connected to an external magnetic contact (or, if
present, internal to the electronic lock) it is necessary to
detect the status of the door (Open/Closed).
i4 RTE To be connected to an RTE emergency button, inside the
restricted area, it is used to open the door (Pressed / Not
Pressed).
i5 BOLT STATUS If provided by the electronic lock, must be connected to the
bolt of the lock to detect:
Open = Bolt unlocked without multiple locking points
Closed = Bolt locked with multiple locking points
i6 LOW BATTERY To be connected to the "Batt. Low" output of the external
power supply:
- Normal = normal battery voltage
- Low = battery voltage lower than 11V (if 12V power supply)
or lower than 21V (if 24V power supply). Valid only when the
main power supply is missing.
NOTE: If the battery is not connected, its status is "Normal".
i7 AC MONITOR To be connected to the "AC OK" output of the external power
supply:
Present = mains power supply present
Absent = mains power supply not present

intro Installation and Configuration Manual
R30057.111 14
The intro module provides 6 outputs, 2 of which are programmed with functions already defined as
summarized in the following table:
NOTE: O1-O2 and O3 terminals are outputs NO/NC (default NO, (depending on jumper settings) and freely
programmable.
Wiring External power supply supplied by Ksenia and Battery
The image shows the connection with the external power supply supplied by Ksenia (UPS Kit 13.8V/60W
code KSI7101260.000 or UPS Kit 27.6V/60W, code KSI7102460.000).
Output label Function Description
O4 GATE STATUS Connected to a lamp (for example) it is automatically activated
when the gate is disabled; jumper 7 - default NO.
O5 ALERT To be connected to a gate alarm lamp (for example) to detect DOTL
or FD alarms; jumper 8 - default NO.

intro Installation and Configuration Manual
15 R30057.111
intro module configuration
intro BUS Peripheral menu
Real time data
Label Possible values
Gate
(intro module)
Enabled = allows access only to authorized users.
Disabled = access not allowed to users even if authorized.
The gate is automatically disabled when at least one of the configured partitions
is armed.
Door Status
(i3 input – DOOR STATUS)
Open = the magnetic contact is open
Closed = the magnetic contact is closed
Bolt status
(i5 input – BOLT STATUS)
Open = the door is NOT closed with the multiple locking points
Closed = the door is closed with the multiple locking points

intro Installation and Configuration Manual
R30057.111 16
Table describing the logic applied to the “Gate Logical Status” real time:
Logical Gate Status Logical status comparing values of Gate, Door Status (i3 input – DOOR STATUS)
and Bolt Status (i5 input – BOLT STATUS).
Depending on combinations of possible values, it can assume: Open, Forced Open,
Open Too Long, Failure, Enabled, Disabled.
RTE button
(i4 input - RTE)
Pressed = RTE output button is being pressed
Not Pressed = the RTE output button is not being pressed (i4 -RTE input)
Battery
(i6 input - LOW BATTERY)
Normal = normal battery voltage
Low = battery voltage less than 11V (if 12V power supply) or less than 21V (if 24V
power supply).
NOTE: If the battery is not connected, it will show "Normal" because the power
supply only provides charging information when it is powered by battery.
Main Power Supply
(i7 input – AC MONITOR)
Present = mains power supply is present
Absent = mains power supply is absent
Gate Door status Bolt status Gate logical status
Enabled Open Open Open
Forced open
Open too long
Enabled Open Closed Failure
Enabled Closed Open Open
Forced open
Open too long
Enabled Closed Closed Enabled
Disabled Open Open Forced open
Open too long
Disabled Open Closed Failure
Disabled Closed Open Forced open
Open too long
Disabled Closed Closed Disabled

intro Installation and Configuration Manual
17 R30057.111
Step-by-step configuration of intro module
In the following paragraphs, an example of a control access system configuration is described, with the
following devices installed:
• one intro module (therefore 1 gate);
• two peripherals (volo and ergo-X in the example, but also two volo or two volo-in) for authenticating the
users;
• one magnetic contact;
• one RTE button;
• one flashing light to signal the FD (Forced Door) and/or DOTL (Door Open Too Long) alarms.
Step Menu, Fields and Descriptions
1 BUS Peripheral ->
intro
Description
Serial number
The gate is disabled if one of these partitions is armed.
When at least one partition is armed, the gate will turn disabled. No one can pass
through a disabled gate, not even authorized users.
Rooms
You can set one or more rooms to display intro on graphic Maps and lares 4.0 User
App (the door category icon is used).
2i1= (input terminal 1 - freely configurable)
Click on the blue rectangle of i1, the Zones configuration page opens, without
changing the page (*), where you can complete the configuration and where the
Peripheral Association is automatically filled in.
Make your changes of the zone directly in the BUS Peripheral -> intro page or
from the System -> Zones page, from where you can return to the intro
configuration page by clicking on the "Go to peripheral" button.
Note: this zone is like all the others, if you want it to be armed when the gate is
disabled, the configured partition must be equal to, at least, to one of those
configured in the intro device, which disables the gate if armed.
(*) The configuration mode of the Zones directly from the BUS devices page,
without changing pages, has been extended to all peripherals where the graphic
terminals image is already present.
i2= (input terminal 2 - freely configurable)
Same description as i1

intro Installation and Configuration Manual
R30057.111 18
i3= (input terminal 3 - preconfigured as DOOR STATUS)
Although configured, a zone must be associated with terminal i3 for reading the
door status (open or closed) and for triggering the DOTL (Door Open Too Long)
and FD (Forced Door) alarms.
Click on the i3 rectangle to configure the Zone: the Zones configuration page
opens, without changing pages, where the Peripheral Association will be
automatically filled in and where you can complete the configuration.
Note: this zone is like all the others, if you want it to be armed when the gate is
disabled, the configured partition must be equal to, at least, one of those
configured in the intro device, which disables the gate if armed.
i4 (Input Terminal 4 - preconfigured as RTE-Request to exit)
It does not require configuration, default NO, it is sufficient to physically connect
it to an RTE output button.
i5 (Input Terminal 5 - preconfigured as BOLT STATUS)
It does not require configuration, it must only be connected if the electric lock
if provides this information.
i6 (Input Terminal 6 - preconfigured as LOW BATTERY)
It does not require configuration, it is sufficient to connect it with the "Batt. Low"
output of the external power supply supplied by Ksenia.
i7 (Input Terminal 7 - preconfigured as AC MONITOR)
It does not require configuration, it is sufficient to connect it to the "AC OK"
output of the external power supply supplied by Ksenia.
O1 = output terminal 1 (1A) - jumper 5 - default NO, freely configurable from the
Outputs page or by clicking on O1 rectangle, without changing the page.
O2 = output terminal 2 (1A) - jumper 6 - default NO, freely configurable from the
Outputs page or by clicking on O2 rectangle, without changing the page.
O3 = output terminal 3 (8A) - jumper 4 - default NO, freely configurable from the
Outputs page or by clicking on O3 rectangle, without changing the page.
O4 (output terminal 4 - preconfigured as GATE STATUS)
It does not require configuration, jumper 7 - default NO, it is activated
automatically when the gate is disabled.
O5 (output terminal 5 - preconfigured as ALERT)
It does not require configuration, jumper 8 - default NO, it is activated
automatically in case of DOTL or FD alarms
Save and Apply the session as usual, at the end.

intro Installation and Configuration Manual
19 R30057.111
Enabling DOTL and FD alarms
Enabling lock status reading
Configuring two devices to authenticate users authorized to pass through the gate
NOTE: In our example we hypothesized the presence of two peripherals (volo and ergo-X), but, in case you
have a volo-in device, open the menu <BUS Peripheral -> User Interfaces ->volo-in> and configure it in the
usual way.
ATTENTION! It is necessary to associate a zone with the i3 terminal to read the door status and for the DOTL (Door
Open Too Long) and FD (Forced Door) events to be generated.
3 Enable Forced Door Enable/Disable the FD (Forced Door) feature to detect the opening of
the sensor associated to the zone with i3 terminal, without having
opened the door before, and to trigger the FD alarm.
Enable DOTL (Door Open Too Long) Enable/disable the DOTL feature to detect the door, associated to
the zone with i3 terminal, that remains open for a longer period than
the time set in the following field, after which the DOTL alarm is
triggered.
DOTL timeout (minutes) Set the DOTL timer within which the door must close, otherwise the
DOTL alarm is triggered. Possible values: 1…30 minutes, default 1
min.
4 Enable the lock entry status It enables the reading of the lock entry status (bolt open/closed) if
the lock is equipped with it and it is wired.
(Lock status: i5 input - BOLT STATUS)
Time of ON - Lock output (seconds) Time expressed in seconds, resolution in tenths of a second, during
which the lock output (LOCK 1) programmed as monostable, remains
active.
Step Menu Description
1 BUS Peripherals ->User Interfaces ->
Volo
Add a volo reader to the configuration in the usual way.
2 BUS Peripherals ->User Interfaces ->
ergo-X
Add an ergo-X keypad to the configuration in the usual way.

intro Installation and Configuration Manual
R30057.111 20
Configuring users authentication and authorization to pass through the gate
Configuring User Profiles (Installer only)
Configuring Access Permissions and Gate Association
Access Permissions (Administrator User only) - Gate Association (Administrator and Master User)
Note: Having to configure the “WHO” to authorize and the “WHERE” to pass, with this association the administrator
user is able to decide the “WHERE”; for the “WHO”, the administrator must perform the next step "Configuring the
users and authorize them to pass through the gate".
Step Menu Description
1 User Management -> Profiles From Installer:
Add an Employee profile (access level = Standard) and an
Administrator profile (access level = Administrator).
Step Menu Description
1 User Management -> Access
Permissions
From Installer - Administrator User level
or
From lares 4.0 App - Administrator User level
Add two Access Permissions:
Permission-employee:
access from Monday to Friday, two time slots:
09.00-13.00 and 14.00-18.00, excluding holidays.
Permission-admin
: access from Monday to Sunday, All day, including
holidays.
Gates: The list contains the names of the gates configured in the
system by the installer (in our example the list contains only one
intro). The Administrator user has the possibility to associate all
gates to each programmed access permission.
By default, each access permission is associated to all gates, but it is
also possible to individually choose which gate to associate, by
deleting the default setting first.
This manual suits for next models
1
Table of contents
Popular Controllers manuals by other brands

ON Semiconductor
ON Semiconductor NCS36000 operating manual

RADEMACHER
RADEMACHER DuoFern Instruction manual for the electrical connection and for commissioning

Nevco
Nevco 827 Operator instructions

PI
PI M-230 Series user manual

Maverick
Maverick MSC-30BR-WP instructions

Carel
Carel MCHRTF Series quick start guide