15
The pump is installed after the strainer, and
before a combination valve (Flo-Trex). This
combination valve acts as isolation valve,
check valve, and flow balancing valve. The
shell and tube or brazed plate evaporator, is
placed after the combination valve in the
water circuit, with a differential pressure
switch installed across its inlet and outlet.
This pressure switch closes when the
differential pressure increases above the set-
point, which should be set 1-2 psig below the
pressure drop across the heat exchanger at
design flow rate. The closing differential
pressure switch signals the control system to
indicate flow through the heat exchanger and
allow cooling to activate as required to
maintain the setpoint. The water exiting the
shell and tube or brazed plate evaporator,
leaves the unit through the water out
connection.
Glycol
Glycol units require a glycol feeder field
installed to replace fluid that is lost in the
system. Water should not be directly added to
glycol applications as this would dilute the
glycol concentration and thereby increase the
freezing temperature of the fluid.
Compression Tank
As the water temperature in the system
increases, the volume that water displaces
increases. In order to compensate for these
forces, AAON recommends a pre-
pressurized diaphragm compression tank that
is preset for 12 psig.
Pressure Relief Valve
Required pressure relief valve is installed in
the unit. This valve is set at 125 psig. Figure
1 shows inlet pressure versus capacity for this
pressure relief valve. See appendix for
additional information.
Figure 1 - Pressure Relief Valve
Manual and Automatic Air Vent
A manual air vent is supplied in chillers
without pumping packages. The air vent
valve must be in the proper position for
operation. Ensure that the small vent cap on
the automatic air vent is loosened one to two
turns from the closed position, allowing air to
be vented from the system. It is advisable to
leave the cap on to prevent impurities from
entering the valve. See appendix for
additional information.
Dual Pumps
When redundant pumping is required, a
factory installed dualArm pump can be
ordered on units 15 tons and larger. A
dualArm pump is a pump with two
independent motors and pumps in a single
casing. This pump has a swing split-flapper
valve in the discharge port to prevent liquid
recirculation when only one pump is
operating. Isolation valves in the casing allow
one pump to be isolated and removed for
service while the other pump is still
operating.
The controls package will activate the pump
when the unit is given a run command. If the
controls do not recognize flow in 60 seconds,
the second pump will be activated and an
alarm signal will be generated. If the second
pump does not activate, the cooling will be
locked out.