Specifications: Water-cooled Refrigeration
Model HRR012-W HRR018-W HRR024-W HRR030-W
Cooling method Water-cooled refrigeration
Refrigerant R410A (HFC)
Refrigerant charge [kg] 0.25 0.40
Control method PID control
Ambient temperature/Humidity/Altitude
∗1, 14 Temperature: 5 to 40 °C, Humidity: 30 to 70 %, Altitude: less than 3000 m
Circulating fluid system
Circulating fluid∗2Tap water, 15 % ethylene glycol aqueous solution
Set temperature range∗1[°C] 10 to 35
Cooling capacity (50/60 Hz)∗3[W] 1000/1200 1600/1800 2000/2400 2500/3000
Heating capacity (50/60 Hz)∗4[W] 450/500 550/700
Temperature stability∗5[°C] ±0.1
Pump capacity (50/60 Hz)∗6[MPa] 0.13 (at 7 l/min)/0.18 (at 7 l/min)
For OptionT: 0.42 (at 10 l/min)/0.4 (at 14 l/min)
For Option MT: 0.32 (at 10 l/min)/0.32 (at 14 l/min)
Rated flow (50/60 Hz)∗7[l/min] 7/7 For Options T, MT: 10/14
Flow display range [l/min] 3 to 16
Electric conductivity display range [μS/cm]
2 to 48 (Only for Option DM)
Electric conductivity setting range [μS/cm]
5 to 45 (Only for Option DM)
Particle filter nominal filtration rating
[μm] 5
Bypass valve Installed
Tank capacity [L] Approx. 4
Outlet, Return port size Rc1/2
Drain port size Rc1/4, With cap
Leakage protection Drain pan (With water leakage sensor)
Fluid contact material Stainless steel, Copper (Heat exchanger brazing)∗11, Brass∗17, SiC,
Alumina ceramic, Carbon, PP, PE, POM, PA, FKM, EPDM, PVC,
PPS, AS, Fluoropolymer∗12, Ion exchange resin∗12
Facility water system
Temperature range [°C] 5 to 40
Pressure range [MPa] 0.3 to 0.5
Required flow rate (50/60 Hz)∗13 [l/min] 8 121415
Inlet-outlet pressure differential of facility water
[MPa] 0.3 or more
Port size Rc3/8
Fluid contact material Stainless steel, Copper (Heat exchanger brazing), Bronze, Brass, Synthetic rubber
Electrical system
Power supply Single-phase 200 to 230 VAC, 50/60 Hz, Allowable voltage range ±10 %∗15
Circuit protector [A] 10 For Options T, MT: 15
Applicable earth leakage breaker capacity
∗8Rated current: 10 A For Options T, MT:15 A
Sensitivity current: 30 mA
Cable quantity x Size (Including grounding cable)
∗16 3 cores x 14 AWG (3 cores x 2.0 mm2)
Rated operating current
(50/60 Hz)∗3[A] 3.2/3.6 3.3/3.6 4.9/5.1 4.9/5.2
For OptionsT, MT
4.3/5.8 4.4/5.8 6.0/7.3 6.0/7.4
Rated power consumption
(50/60 Hz)∗18
[kW(kVA)]
0.6/0.7 (0.7/0.7) 0.6/0.7 (0.7/0.7) 0.8/1.0 (1.0/1.0) 0.8/1.0 (1.0/1.0)
For OptionsT, MT
0.9/1.1 (0.9/1.2) 0.9/1.1 (0.9/1.2) 1.1/1.2 (1.4/1.4) 1.1/1.2 (1.4/1.4)
Communication function Contact input/output, Serial RS-485/RS-232C
Noise level (50/60 Hz)∗9[dB] 59/60 59/60 61/64 61/64
Accessories∗19 Power supply connector, Particle filter element and maintenance handle, Operation manual
Weight∗10 [kg] 41 45
∗1 It should have no condensation. During seasons or in locations where
the ambient temperature is likely to fall below freezing point, please con-
tact SMC for that case.
∗2
If tap water is used, use water that conforms to Water Quality Standards
of the Japan Refrigeration and Air Conditioning Industry Association (JRA
GL-02-1994 cooling water system - circulating type - make-up water).
∗3
qFacility water temperature: 2 5 °C, wCirculating fluid temperature: 2 0 °C,
eCirculating fluid rated flow, rCirculating fluid: Tap water, tPower supply:
200 VAC, yPiping length: Shortest
For models with high-pressure pump mounted (OptionsT, MT), the cool-
ing capacity will decrease by 300 W.
∗4
qAmbient temperature: 25 °C, wFacility water temperature: 25 °C, eCir-
culating fluid temperature: 20 °C, rCirculating fluid rated flow, tCirculat-
ing fluid:Tap water, yPower supply: 200 VAC, uPiping length: Shortest
∗5 Temperature at the thermo-chiller outlet when the circulating fluid flow is
rated flow, and the circulating fluid outlet and return port are directly
connected. Installation environment and the power supply are within
specification range and stable.
∗6 The capacity at the thermo-chiller outlet when the circulating fluid tem-
perature is 20 °C.
∗7
Required flow rate for maintaining the cooling capacity or temperature stability
The specification of the cooling capacity and the temperature stability may not
be satisfied if the flow rate is lower than the rated flow.
∗8 Purchase an earth leakage breaker with sensitivity current of 3 0 mA/
power supply 200VAC separately.
∗9 Front:1 m, height:1 m, stable with no load, Other conditions JSee ∗3.
∗10
Weight in the dry state without circulating fluids and facility water (for
water-cooled refrigeration)
The weight will increase by 1 kg when Option DM (With electric conductivity
control function + Applicable to DI water piping) is selected.
The weight will increase by 5 kg when Option T (High-pressure pump
mounted) or MT (Applicable to DI water piping + High-pressure pump
mounted) is selected.
∗11 Copper and brass are not included when Option M (Applicable to DI
water piping) or MT (Applicable to DI water piping + High-pressure
pump mounted) is selected.
∗12 For Option DM (With electric conductivity control function + Applicable
to
DI
water piping)
∗13 Required flow rate when a load for the cooling capacity is applied un-
der the conditions in ∗3.
∗14 If the product is used at altitude of 1000 m or higher, refer to “* For al-
titude of 1000 m or higher” on page 25.
∗15 No continuous voltage fluctuation
∗16 To be prepared by the customer
∗17 For Option T (High-pressure pump mounted), this material is included.
∗18
qFacility water temperature: 25 °C, wCirculating fluid temperature: 20 °C,
eCirculating fluid rated flow, rCirculating fluid: Tap water, tPower sup-
ply: 200 VAC, yPiping length: Shortest, uAt the rated cooling load applied
∗19
For Option DM (With electric conductivity control function + Applicable
to DI water piping), a DI filter is attached.
For pipe thread type F, a G thread conversion fitting set is attached.
For pipe thread type N, an NPT thread conversion fitting set is attached.
11