Galletti PERFORMA MPE Series User manual

MPE D
7 kW - 76 kW
R410A
eco
TECHNICAL MANUAL FOR CHILLERS AND HEAT PUMPS
EN
Air condensed duct water chillers and heat pumps
PERFORMA MPE series
DUCTABLE VERSION

MPED
2
Serie Grandezza Organismo Notificato N° certificato Procedura di valutazione di conformità Categoria PED Marcatura
Range Size Notified body certificate Conformity Compliance Module PED category Marking
MCC - MCC H 6-7-9-12-15 0425 Modulo D1 ICE
MCC - MCC H 18-22-25-33-37 0425 Modulo D1 II CE + PED
MCW - MCW / H 5-7-10-12-15-18-20 0425 Modulo D1 ICE
MCW - MCW / H 22-27-31-39 0425 Modulo D1 II CE + PED
MPE - MPEH 4-5-7-8-10-13-15-18 0425 Modulo D1 ICE
MPE - MPEH 20-24-27-28-32-35-40-54-66 0425 Modulo D1 II CE + PED
MPE - MPEH T30-T34-T40-T45-T54-T61-T69-T76 0425 Modulo D1 II CE + PED
MPE D - MPE D H 7-8-10-13-15-18 0425 Modulo D1 ICE
MPE D - MPE D H 20-24-27-28-32-35-40-54-66 0425 Modulo D1 II CE + PED
MPE D - MPE D H T30-T34-T40-T45-T54-T61-T69-T76 0425 Modulo D1 II CE + PED
MPI 15 0425 Modulo D1 ICE
MPI 27 0425 Modulo D1 II CE + PED
MPI DC 8-10-14-15-18 0425 Modulo D1 ICE
MPI DC 23-27-29 0425 Modulo D1 II CE + PED
HWMC 10 0425 Modulo D1 ICE
HWMC 13-18-23-29 0425 Modulo D1 II CE + PED
MCP 7-9 0425 Modulo D1 ICE
MCP 10-13-15-18-27-32-40-T18-T22-T24-T30 0425 Modulo D1 II CE + PED
LCE - LCE H 42-52-62-72-82-91/2/4-101/2/4-121/2/4-
141/2/4-161/2/4-174-194-214 0425 Modulo D1 II CE + PED
LEW
41-42-51-52-61-62-71-72-81-82-91-92-
111-112-131-132-141-144-161-162-164-
181-182
0425 Modulo D1 II CE + PED
2422/0
All copying, even partial, of this manual is strictly forbidden RG66012163 - Rev 00
TABLE OF CONTENTS
1 The series�������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������4
2 Constructive features��������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������5
3 Layout of components ������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������6
4 Models and configurations ���������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������13
5 Technical characteristics������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������15
5�1 Rated technical data water chillers������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������15
5�2 Rated technical data heat pumps��������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������17
5�3 Air flow rate setting����������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������19
6 Performance�������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������20
6�1 Integrated capacities ��������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������21
7 Sound level���������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������21
8 Operating limits ��������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������22
8�1 Cooling mode ������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������22
8�2 Heating mode ������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������22
8�3 Thermal carrier fluid���������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������22
9 Calculation factor������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������23
9.1 Changeinoperatingparameterswith∆totherthan5°C ����������������������������������������������������������������������������������������������������������������������������������������������������������������23
9�2 Water and glycol mixture��������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������23
10 Pressure drop �����������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������24
10�1 Pressure drops, water side�����������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������24
10�2 Pressure drops of Y filter��������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������28
11 Available head ����������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������29
12 Water circuit�������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������33
12�1 Water content within the system and charging of expansion tank ��������������������������������������������������������������������������������������������������������������������������������������������������33
12�2 Water content within the system and charging of expansion tank ��������������������������������������������������������������������������������������������������������������������������������������������������36
13 Electrical data and connections��������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������37
14 Overall dimensions���������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������39
15 Installation clearance requirements �������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������46
15�1 Positioning of vibration dampers���������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������������47
DECLARATION OF CONFORMITY
Galletti S�p�A� with head office in Via Romagnoli 12/a Bentivoglio (Bologna) - Italia, declares herewith under its own responsibility that all water chillers and heat pumps
series: (see table below) units for air-conditioning systems for civil conditioning application, are produced in accordance with following directives: CEE 73/23, 89/392,
91/368, 93/44, 93/68, 89/336, 97/23 (PED)�
These units are made by assembly of components (compressors, heat exchangers with braze welded plates, liquid receiver, pipelines , regulating and safety valves),
each component, if requested by the law, has its own declaration in accordance with the directives in force: the determination of the units belonging category is the result
of the analyse of all components subjected to the PED directive and correspond to the highest class between the used components�
For each unit series the conformity of the assembly has been evaluated by notified bodies through the application of procedure for evaluation (forms) according to the
annex II of the 97/23 PED directive, as reported in the following table:
Bentivoglio, 02/07/2014
Galletti S.p.A.
Luca Galletti

3
All copying, even partial, of this manual is strictly forbiddenRG66012163 - Rev 00
Serial number
Code
Date of production
Cooling capacity (W)
Heating capacity (W)
Power supply
Power input (kW)
Weight (kg)
Max power input (kW)
Max running amperage (A)
HP Power input (kW)
Refrigerant
Max refrigerant pressure (bar)
Max refrigerant temperature (°C)
Made in Italy
CATEGORIA 1
Galletti S.p.A. via L.Romagnoli 12/a
40010 Bentivoglio (BO) Italia
UNIT IDENTIFICATION
The unit data are reported on the rating label in this page�
THE LABEL SHOWS THE FOLLOWING DATA:
- Series and size of the unit
- Date of manufacture
- Main technical data
- Manufacturer
- The label is applied on the unit, usually on the enclosing panels beside
the condenser coil�
IMPORTANT: NEVER REMOVE THE LABEL
- Serial number of the unit
- The serial number permits to identify the technical characteristics and
the components installed
- Without this datum it will be impossible to identify the unit correctly
TRANSLATION OF ORIGINAL INSTRUCTIONS
The technical and dimensional data reported in this manual may be modified in view
of any product improvement�
WATER CHILLERS AND HEAT PUMPS ARE IN ACORDARCE WITH THE
LAW 97/23/CE (PED) FILLING IN D1 FORM, APPROVED BY THE THIRD
NOTIFIED BODY ICIM N°0425.

MPED
4All copying, even partial, of this manual is strictly forbidden RG66012163 - Rev 00
PERFORMA (MPE) water chillers and heat pumps are designed for outdoor
installation in both residential and industrial applications�
The range uses R410A refrigerant, which assures high levels of performance
with relatively low energy consumption and features 19 models in the chiller
and heat pump version, with cooling capacities ranging from 7 to 66 kW and
heating capacities from 8 to 75 kW�
BEYOND CONVENTIONAL WORKING LIMITS
The finned block heat exchangers have been optimised for R410A and use 8
mm copper pipes, which permit a better heat exchange and quiet operation
of the fans�
Their generous sizing guarantees the production of chilled water even with
outdoorairtemperaturesashighas51°Candallmodelsoftherangeassure
an average energy efficiency ratio (EER) of 2�95 in the cooling mode and
heating efficiency (COP) of 3�25, corresponding to the Eurovent Energy
Efficiency Class A
EFFICIENCY IN ALL CONDITIONS
The actual thermal load of an air conditioning system is less than 60% of the
rated load capacity 90% of the time; the MPE T version with single-circuit
dual compressor answers this demand by offering high efficiency during
operation under partial load conditions (ESEER>4) and also guarantees the
unit’s operation at the worst temperature conditions�
In such conditions the microprocessor controller activates the capacity control
mode, doubling the condensing surface available to the single compressor�
The axial-type fans with airfoil-shaped blades and 6- and 8-pole motors with
electronic speed control (optional) guarantee quiet operation and optimal
performance of the unit in all conditions�
1 LA SERIE
T54
T61
T69
T76
SELF-ADAPTIVE
The electronic control system allows the setpoint to be adjusted automatically
according to the outdoor temperature in order to reduce consumption and
broaden the working temperature range�
The unit can also function in systems with a low water content, even without
the use of a storage reservoir, thanks to the automatic adjustment which
limits the number of compressor starts and thus extends the life of the
compressors themselves
OFF
Tw,in [°C]
t [s]
ON
15,5
15
14,5
14
13,5
13
12,5
12
11,5
ON ON
ON ON ON
OFF
420s
OFF OFF
600s
OFF
SMART DEFROST SYSTEM
The exclusive defrost system (optional feature available with the advanced
controller) can correctly identify an impairment of performance in the outdoor
exchanger due to the formation of ice and minimise the process time in
relation to normal operation of the unit�
Time Defrost start time
MAX
Evaporationing Temperature
Variation
RADIAL FANS
The impellers are made in a single piece with an alloy of special materials
developed so as to ensure high rotational speeds, and thus a high power
density of the fan� The impellers’ design was developed using complex
simulation models optimized through experimental tests performed on
prototypes� The result is a uniform air flow over the impeller’s entire cross
section, in order to guarantee very low pressure loss� A uniform air flow
profile also results in fewer noise sources and, therefore, extremely low
noise levels during operation�
The MPE DUCTED radial fans can be equipped with a permanent magnet
(brushless) electric motor, controlled by an inverter, which enables continuous
adjustment in the number of fan revolutions�
The great advantage of brushless motors is the significant reduction in
power consumption, which in instant operations reaches up to 1/3 of that
of conventional motors and at around 50% in integrated operations, with a
corresponding reduction in CO2 emissions!

5
All copying, even partial, of this manual is strictly forbiddenRG66012163 - Rev 00
STRUCTURE
Painted galvanised sheet steel structure (RAL9002) for an attractive look and
effective resistance to corrosive agents�
Fastening devices are made of non-oxidizable materials, or carbon steel that
has undergone surface-passivating treatments�
The compressor compartment is completely sealed and may be accessed on
3 sides thanks to easy-to-remove panels that greatly simplify maintenance
and/or inspection�
Sound insulation, available on request, can further reduce the noise emissions
of the unit�
CUSTOMISED HYDRAULIC KIT
- High head pump made entirely of stainless steel, already configured for
use with mixtures of water and ethylene glycol up to 35% and provided
with internal thermal protection�
It is housed in the compressor compartment and is easy to reach thanks
to the removable perimeter panels�
- Expansion tank�
- Safety valve�
- Filling cock (included)�
- Automatic vent valve�
- Water differential pressure switch and outlet water temperature probe
with anti-freeze thermostat function�
- Mechanical Y filter supplied as a standard feature on all models to protect
the evaporator (included)�
COOLING CIRCUIT
- Scroll-type compressor (rotary up to 7 kW) housed in a compartment
that can be sound insulated�
- Brazed plate heat exchangers made of STAINLESS STEEL and optimised
for use with R410A�
- Finned block condenser with 8 mm copper piping and aluminium fins,
characterised by ample heat exchange surfaces�
- Dehydrating filter�
- Flow indicator with humidity indicator�
- Thermostatic valve with external equalisation and integrated MOP
function�
- Cycle-reversing valve (MPED H)�
- Single-acting valves (MPED H)�
- Liquid receiver (MPED H)
- High and low pressure switches�
- Safety valve�
- Schrader valves for checks and/or maintenance�
- Refrigerant pressure gauges (optional)
VENTILATION SECTION
Statically and dynamically balanced centrifugal fans with backward-curved
blades, directly mounted on the electric motor�
All units are equipped with phase-cut speed regulator controlled by the
ratiometric pressure probe or by means of EC fans�
The ventilation compartment is completely insulated with anti-condensation
material and is separated from the compressor/electrical system compartment
for inspection purposes when the unit is working (without interfering with the
finned block exchanger)
The absence of belt drive and the frontally removable fan considerably reduce
maintenance work�
The use of finned block heat exchangers with 8mm diameter pipes reduces
pressure drops on the air side, thus significantly improving the noise levels
of the units�
FINNED BLOCK HEAT EXCHANGER
Made of 8mm diameter copper pipes and aluminium fins, generously sized�
The special engineering of the heat exchangers allows defrost cycles to be
carried out at maximum speed in the models with heat pump operation, which
brings clear benefits in terms of the integrated efficiency of the whole cycle�
ELECTRONIC MICROPROCESSOR CONTROL
The electronic control enables the complete control of the MPED unit� It can
be easily accessed through a polycarbonate flap with IP65 protection rating�
The self-adaptive logic enables the unit to operate even in systems where the
water content is low, without the use of an inertial water storage reservoir� By
reading the outdoor air temperature, it can automatically change the setpoint
to adapt it to the outdoor load conditions or keep the unit running even in the
harshest winter conditions�
The basic controller comes complete with the MODBUS protocol and enables
an immediate connection to ERGO networks�
Main functions
- Control over the temperature of water entering the evaporator�
- Management of the defrosting function (MPED-H)
- Control of fan speed (optional)
- Complete alarm management�
- Dynamic control of the setpoint according to the outdoor air temperature�
- Can be connected to an RS485 serial line for supervisory / teleassistance
operation;
- Option of connecting a remote terminal that duplicates the control
functions�
Devices controlled:
- Compressor
- Fans
- Cycle-reversing valve (MPED-H)�
- Water circulation pump�
- Antifreeze heating elements (optional)
- Alarm signalling relay
On request, it is possible to install the advanced controller whose functions
extend to:
- LAN networks
- Smart Defrost System
ELECTRIC CONTROL BOARD
The electric control board is constructed and wired in accordance with EEC
Directive 73/23, Directive 89/336 on electromagnetic compatibility and
related standards� Made of steel sheet, it is also protected by the enclosing
panels of the machine�
OPTIONS
Incorporable hydronic kits
Condensation control
Low noise execution
Refrigerant pressure gauges
Antifreeze heating elements on the water circuit
Electronic thermostatic valve
Heat recovery 25% (chiller)
Special exchangers (hydrophilic treatment, copper-copper, cataphoresis,
anti-corrosion)
Air flow rate setting system
ACCESSORIES AVAILABLE
Remote control boards
Base vibration dampers
Metal grilles to protect exchangers
2 CONSTRUCTIVE FEATURES

MPED
6
MPED 07 - 08
All copying, even partial, of this manual is strictly forbidden RG66012163 - Rev 00
3 LAYOUT OF COMPONENTS
DESCRIPTION
1. R410A-air heat-exchanger
2. R410A-water heat-exchanger
3. Fans
4. Water differential pressure switch (fan housing)
5. Automatic air purge valve
6. Expansion vessel (fan housing)
7. Water tank (accessory)
9. 4-way valve (MPED H)
10. Thermostatic valve
11. Water safety valve
12. Liquid receiver
13. Pump
14. Compressor
15. Refrigerant filter
16. Low pressure switch and charge port
17. High pressure switch and charge port
18. Water gauge
19. Water charge

7
MPED 10 - 15
All copying, even partial, of this manual is strictly forbiddenRG66012163 - Rev 00
3 LAYOUT OF COMPONENTS
DESCRIPTION
1. R410A-air heat-exchanger
2. R410A-water heat-exchanger
3. Fans
4. Water differential pressure switch (fan housing)
5. Automatic air purge valve
6. Expansion vessel (fan housing)
7. Water tank (accessory)
9. 4-way valve (MPED H)
10. Thermostatic valve
11. Water safety valve
12. Liquid receiver (fan housing)
13. Pump
14. Compressor
15. Refrigerant filter
16. Low pressure switch and charge port
17. High pressure switch and charge port
18. Water gauge
19. Water charge

MPED
8
MPED 18 - 27
All copying, even partial, of this manual is strictly forbidden RG66012163 - Rev 00
3 LAYOUT OF COMPONENTS
DESCRIPTION
1. R410A-air heat-exchanger
2. R410A-water heat-exchanger
3. Fans
4. Water differential pressure switch (fan housing)
5. Automatic air purge valve
6. Expansion vessel (fan housing)
7. Water tank (accessory)
9. 4-way valve (MPED H)
10. Thermostatic valve
11. Water safety valve
12. Liquid receiver (fan housing)
13. Pump
14. Compressor
15. Refrigerant filter
16. Low pressure switch and charge port
17. High pressure switch and charge port
18. Water gauge
19. Water charge

9
MPED 28 - 40
All copying, even partial, of this manual is strictly forbiddenRG66012163 - Rev 00
3 LAYOUT OF COMPONENTS
DESCRIPTION
1. R410A-air heat-exchanger
2. R410A-water heat-exchanger
3. Fans
4. Water differential pressure switch (fan housing)
5. Automatic air purge valve
6. Expansion vessel (fan housing)
7. Water tank (accessory)
9. 4-way valve (MPED H)
10. Thermostatic valve
11. Water safety valve
12. Liquid receiver (fan housing)
13. Pump
14. Compressor
15. Refrigerant filter
16. Low pressure switch and charge port
17. High pressure switch and charge port
18. Water gauge
19. Water charge

MPED
10
MPED 54 - 66
All copying, even partial, of this manual is strictly forbidden RG66012163 - Rev 00
3 LAYOUT OF COMPONENTS
DESCRIPTION
1. R410A-air heat-exchanger
2. R410A-water heat-exchanger
3. Fans
4. Water differential pressure switch (fan housing)
5. Automatic air purge valve
6. Expansion vessel (fan housing)
7. Water tank (accessory)
9. 4-way valve (MPED H)
10. Thermostatic valve
11. Water safety valve
12. Liquid receiver (fan housing)
13. Pump
14. Compressor
15. Refrigerant filter
16. Low pressure switch and charge port
17. High pressure switch and charge port
18. Water gauge
19. Water charge

11
MPED 30 - 45T
All copying, even partial, of this manual is strictly forbiddenRG66012163 - Rev 00
3 LAYOUT OF COMPONENTS
DESCRIPTION
1. R410A-air heat-exchanger
2. R410A-water heat-exchanger
3. Fans
4. Water differential pressure switch (fan housing)
5. Automatic air purge valve
6. Expansion vessel (fan housing)
7. Water tank (accessory)
9. 4-way valve (MPED H)
10. Thermostatic valve
11. Water safety valve
12. Liquid receiver (fan housing)
13. Pump
14. Compressor
15. Refrigerant filter
16. Low pressure switch and charge port
17. High pressure switch and charge port
18. Water gauge
19. Water charge

MPED
12
MPED 54T - 76T
All copying, even partial, of this manual is strictly forbidden RG66012163 - Rev 00
3 LAYOUT OF COMPONENTS
DESCRIPTION
1. R410A-air heat-exchanger
2. R410A-water heat-exchanger
3. Fans
4. Water differential pressure switch (fan housing)
5. Automatic air purge valve
6. Expansion vessel (fan housing)
7. Water tank (accessory)
8. 4-way valve (MPED H)
9. Thermostatic valve
10. Water safety valve
11. Liquid receiver (fan housing)
12. Pump
13. Compressor
14. Refrigerant filter
15. Low pressure switch and charge port
16. High pressure switch and charge port
17. Water gauge
18. Water charge

13
All copying, even partial, of this manual is strictly forbiddenRG66012163 - Rev 00
4 MODELS AND CONFIGURATIONS
FIELD OF APPLICATION
MPED air-condensed water chillers and heat pumps have been designed to cool and heat water for air conditioning and heating systems in residential or
commercial buildings�
MODELS AND VERSIONS
The MPED series features 19 models of varying capacity in both heat pump and cooling only versions�
All models are charged with R410A refrigerant�
N�B� The choice of some options may preclude the choice of others or make some other fields become mandatory� Contact Galletti S�p�A� for verification�
Complete Unit Code M P E 0 0 9 C 0 A D 0 0 0 0 C 0 0 0 0 0 0
Version 0
Single compressor 0
Tandem T
Model (size) 0 9
Operation C
Water chiller C
Heat pump H
Supply voltage 0
Standard 400 - 3N - 50 0
Single-phase M
400 - 3N - 50 + circuit breakers 2
Single-phase + circuit breakers 4
Refrigerant A
High effic� R410A A
Revision A
Standard initial A
Ducted with radial fans D
Expansion valve 0
Traditional 0
Electronic A
Pump and accessories 0
Absent 0
Pump + expansion tank + filling tap 1
Dual pump + expansion tank + filling tap 2
Inertial buffer tank 0
Absent 0
Present + expansion tank S
Partial heat recovery (the condensation control must be added) 0
Absent 0
Present with pump contact D
Fan regulation C
Condensation control - Rpm adjustment C
Condensation control - BLDC fan E
Antifreeze kit 0
Absent 0
For units with evaporator only E
For units with evaporator, pump and expansion tank P
For units with evaporator, pump, expansion tank and tank S
Sound insulation 0
Absent 0
Compressor and fan compartment soundproofing 1
Compressor silencing housings 2
Opt� 1 + Opt� 2 3
Cooling accessories 0
None 0
Refrigerant pressure gauges M
Remote Controller 0
Absent 0
Output RS485 (Modbus or Carel protocol) 2
Simplified remote control S
BASE microprocessor remote control (modbus disabling) M
ADVANCED microprocessor remote control X
LON FTT10 serial card L
Special coils 0
Standard 0
Copper - copper R
Cataphoresis C
Corrosion-proof B
Hydrophilic I
Protection grille 0
Absent 0
Present G

MPED
14 All copying, even partial, of this manual is strictly forbidden RG66012163 - Rev 00
Complete Unit Code ... 0 1
Compressor options 0
Absent 0
Power factor correction capacitors 1
Soft starter 2
Power factor correction capacitors + Soft starter 3
Air/water low temperature, low pressure switch, crankcase heating element (chiller), coil wire (PDC) 4
Control microprocessor 1
BASE microprocessor 1
ADVANCED microprocessor 2
Advanced microprocessor + kit GSM 3
Advanced microprocessor + clock card 4
ACCESSORIES
OHorizontal air expulsion orientation (vertical STANDARD)
MManual air flow rate setting
AAutomatic flow rate setting (only ADVANCED microprocessor)
– Base rubber vibration dumpers
– Spring vibration dumpers kit
–Simplified remote control
– MYCHILLER BASE (RS485 is a mandatory accessory)
– MYCHILLER PLUS (RS485 is a mandatory accessory)

15
All copying, even partial, of this manual is strictly forbiddenRG66012163 - Rev 00
5 TECHNICAL CHARACTERISTICS
5.1 RATED TECHNICAL DATA OF WATER CHILLERS
- Coolingcapacity:outdoorairtemperature35°C,watertemperature12°C/7°C
- Sound power level measured according to standards ISO 3741 - ISO 3744 and EN 29614-1
- Sound pressure level measured at a distance of 10 m and a height of 1�5 m above the ground in a free field (fan side)�
- The maximum electrical input is the mains electricity that must be available in order for the unit to work�
- The maximum current absorption refers to the current that will trigger the internal safety devices of the unit� It is the maximum current allowed in the unit� This value may never be exceeded; it must
be used as a reference for determining the size of the power supply line and the related safety devices (refer to the wiring diagram supplied with the units)�
MPED-C 007 M 008 M 008 010 M 010 013 015 018 020 024 027 028
Power supply V-ph-Hz 230-1-50 400-3-50 230-1-50 400-3-50
Cooling capacity (UNI EN 14511) kW 6,66 8,35 8,48 9,17 9,18 12,8 14,9 17,5 19,9 24,2 27,9 27,9
Total power input (UNI EN 14511) kW 2,40 3,51 3,24 3,75 3,81 4,61 5,56 7,01 7,87 8,55 9,37 9,73
EER (UNI EN 14511) 2,78 2,38 2,62 2,45 2,41 2,78 2,68 2,50 2,53 2,83 2,98 2,87
ESEER 2,96 2,87 3,05 2,92 2,93 3,36 3,29 2,92 2,89 3,15 3,16 3,45
Maximum power input kW 3,32 5,28 5,28 7,26 7,81 9,46 11,0 13,7 13,8 13,5 14,4 15,3
Maximum current absorption A 17 11 26 18 33 21 24 26 26 26 28 37
Starting absorbed current A 63 49 98 48 97 63 66 76 105 145 145 145
n°ofcompressors/circuits 1/1 1/1 1/1 1/1 1/1 1/1 1/1 1/1 1/1 1/1 1/1 1/1
Refrigerant charge kg 2,0 2,1 2,1 2,9 2,9 4,0 4,1 3,7 4,2 5,8 6,0 7,5
Low/high pressure switch bar 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42
n°ofaxialfan 11 1 1 11111112
Air flow m3/h 3533 3533 3533 7666 7666 7192 7192 13384 13384 12191 12191 16276
Fan maximum head Pa 157 157 157 320 320 386 386 311 311 430 430 240
Fan net available head Pa 75 75 75 120 120 120 120 180 180 180 180 180
Water flow l/h 1148 1438 1461 1591 1592 2224 2584 3033 3444 4200 4832 4823
Diameter of hydrualic connections " 1 1 1 1 1 1 1 1,25 1,25 1,25 1,25 1,25
Water side pressure drop kPa 6 6 6 34 34 61 38 53 53 51 37 40
Available pressure head kPa 69 67 67 115 115 80 101 126 120 108 116 141
Water content escluding optionals dm31,5 1,5 1,5 3,0 3,0 3,0 3,0 4,0 4,0 4,0 4,0 5,5
Buffer tank dm320 20 20 30 30 30 30 50 50 50 50 125
Expansion tank dm311 1 5 55555558
Height mm 966 966 966 1247 1247 1247 1247 1565 1565 1565 1565 1988
Length mm 751 751 751 1012 1012 1012 1012 1131 1131 1131 1131 951
Depth mm 758 758 758 1224 1224 1224 1224 1274 1274 1274 1274 1823
Inlet + radiated sound power level dB(A) 74 73 73 75 75 74 74 79 79 78 78 80
Outlet sound power level dB(A) 75 75 75 82 82 81 81 84 84 81 81 89
Inlet + radiated sound power level
(LOW NOISE) dB(A) 70 70 70 70 70 71 71 76 76 75 75 77
Inlet + radiated sound pressure level dB(A) 46 45 45 47 47 46 46 51 51 50 50 52
Outlet sound pressure level dB(A) 47 47 47 54 54 53 53 56 56 53 53 61
Unit with pump and tank
transport weight kg 123 127 127 211 211 216 219 265 281 297 313 427
Unit with pump and full tank
operating weight kg 132 136 136 227 227 232 236 301 317 333 350 534

MPED
16 All copying, even partial, of this manual is strictly forbidden RG66012163 - Rev 00
5 TECHNICAL CHARACTERISTICS
5.1 RATED TECHNICAL DATA OF WATER CHILLERS
- Coolingcapacity:outdoorairtemperature35°C,watertemperature12°C/7°C
- Sound power level measured according to standards ISO 3741 - ISO 3744 and EN 29614-1
- Sound pressure level measured at a distance of 10 m and a height of 1�5 m above the ground in a free field (fan side)�
- The maximum electrical input is the mains electricity that must be available in order for the unit to work�
- The maximum current absorption refers to the current that will trigger the internal safety devices of the unit� It is the maximum current allowed in the unit� This value may never be exceeded; it must
be used as a reference for determining the size of the power supply line and the related safety devices (refer to the wiring diagram supplied with the units)�
MPED-C 032 035 040 054 066 T30 T34 T40 T45 T54 T61 T69 T76
Power supply V-ph-Hz 400-3-50
Cooling capacity (UNI EN 14511) kW 31,3 34,7 39,4 51,0 65,6 29,8 33,9 39,3 44,2 54,2 61,4 69,3 75,6
Total power input (UNI EN 14511) kW 11,3 12,7 13,9 19,8 26,2 11,5 13,8 14,8 17,6 21,7 24,7 26,8 30,8
EER (UNI EN 14511) 2,77 2,73 2,83 2,58 2,50 2,59 2,46 2,66 2,51 2,50 2,49 2,59 2,45
ESEER 3,33 3,33 3,44 3,43 3,04 3,63 3,56 3,68 3,57 3,15 3,19 3,43 3,46
Maximum power input kW 17,3 18,5 21,0 28,6 35,2 22,7 25,4 25,3 27,1 30,7 33,2 37,8 42,0
Maximum current absorption A 41 43 47 55 66 50 55 55 58 57 61 69 76
Starting absorbed current A 166 161 183 221 266 103 115 146 156 177 187 202 229
n°ofcompressors/circuits 1/1 1/1 1/1 1/1 1/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1
Refrigerant charge kg 7,5 7,8 10,8 13,0 15,0 7,8 7,8 10,9 10,9 11,0 11,0 16,0 16,0
Low/high pressure switch bar 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42
n°ofaxialfan 2222222222222
Air flow m3/h 16276 16276 15776 20048 20048 16276 16276 15776 15776 24933 24933 24354 24354
Fan maximum head Pa 240 240 285 515 515 267 267 307 307 160 160 200 200
Fan net available head Pa 180 180 180 180 180 180 180 180 180 120 120 120 120
Water flow l/h 5415 6008 6816 8829 11342 5156 5854 6799 7648 9378 10629 11989 13075
Diameter of hydrualic connections " 1,25 1,25 1,25 1,25 1,25 1,25 1,25 1,25 1,25 2 2 2 2
Water side pressure drop kPa 51 40 43 55 59 30 38 45 57 53 66 52 60
Available pressure head kPa 123 128 117 107 92 148 133 116 94 136 119 127 115
Water content escluding optionals dm35,5 5,5 5,5 5,5 7,0 8,0 5,5 5,5 5,5 5,5 7,0 8,0 11,0
Buffer tank dm3125 125 125 125 125 125 125 125 125 125 125 125 125
Expansion tank dm38888888888888
Height mm 1988 1988 1988 1991 1991 1988 1988 1988 1988 2013 2013 2013 2013
Length mm 951 951 951 979 979 951 951 951 951 1182 1182 1182 1182
Depth mm 1823 1823 1823 1823 1823 1823 1823 1823 1823 2100 2100 2100 2100
Inlet + radiated sound power level dB(A) 80 80 82 84 84 79 79 79 79 85 85 85 87
Outlet sound power level dB(A) 89 89 86 85 85 86 86 86 86 88 88 88 88
Inlet + radiated sound power level
(LOW NOISE) dB(A) 77 77 79 81 81 76 76 76 76 82 82 82 84
Inlet + radiated sound pressure level dB(A) 52 52 54 56 56 51 51 51 51 57 57 57 59
Outlet sound pressure level dB(A) 61 61 58 57 57 58 58 58 58 60 60 60 60
Unit with pump and tank
transport weight kg 456 487 516 521 558 448 484 521 555 643 665 685 786
Unit with pump and full tank
operating weight kg 563 595 624 630 665 555 591 629 663 751 773 793 894

17
All copying, even partial, of this manual is strictly forbiddenRG66012163 - Rev 00
5 TECHNICAL CHARACTERISTICS
5.2 RATED TECHNICAL DATA OF HEAT PUMPS
- Coolingcapacity:outdoorairtemperature35°C,watertemperature12°C/7°C
- Heatingcapacity:outdoorairtemperature7°Cdrybulband6.2°Cwetbulb,watertemperature40°C/45°C
- Sound power level measured according to standards ISO 3741 - ISO 3744 and EN 29614-1
- Sound pressure level measured at a distance of 10 m and a height of 1�5 m above the ground in a free field (fan side)�
- The maximum electrical input is the mains electricity that must be available in order for the unit to work�
- The maximum current absorption refers to the current that will trigger the internal safety devices of the unit� It is the maximum current allowed in the unit� This value may never be exceeded; it
must be used as a reference for determining the size of the power supply line and the related safety devices (refer to the wiring diagram supplied with the units)�
* Seasonal energy efficiency class for LOW TEMPERATURE room heating under AVERAGE climatic conditions [EUROPEAN REGULATION No 811/2013]
MPED-H 007 M 008 M 008 010 M 010 013 015 018 020 024 027 028
Power supply V-ph-Hz 230-1-50 400-3-50 230-1-50 400-3-50
Cooling capacity kW 6,53 8,18 8,31 9,00 9,00 12,5 14,6 17,1 19,5 23,7 26,8 27,3
Cooling power input kW 2,45 3,55 3,29 3,82 3,81 4,76 5,71 7,12 7,86 8,64 9,73 8,56
EER 2,67 2,30 2,53 2,36 2,36 2,63 2,56 2,40 2,48 2,74 2,75 3,19
ESEER 2,96 2,87 3,05 2,92 2,93 3,36 3,29 2,92 2,89 3,15 3,16 3,45
Heating capacity kW 7,79 10,3 9,93 11,0 11,0 15,4 17,8 20,5 23,4 27,7 30,4 31,5
Heating power input kW 2,62 3,84 3,44 4,20 4,20 5,34 6,12 7,72 8,27 8,98 9,75 9,09
COP 2,97 2,68 2,89 2,62 2,62 2,88 2,91 2,66 2,83 3,08 3,12 3,47
SCOP 3,18 2,95 3,15 2,95 2,95 3,25 3,37 2,95 2,95 3,29 3,42 3,35
Energy Efficiency 125 115 123 115 115 127 132 115 115 129 134 131
Energy Efficiency Class* A+ A A+ A A A+ A+ A A A+ A+ A+
Maximum power input kW 3,32 5,28 5,28 7,26 7,81 9,46 11,0 13,7 13,8 13,5 14,4 15,3
Maximum current absorption A 17 11 26 18 33 21 24 26 26 26 28 37
Starting absorbed current A 63 49 98 48 97 63 66 76 105 145 145 145
n°ofcompressors/circuits 1/1 1/1 1/1 1/1 1/1 1/1 1/1 1/1 1/1 1/1 1/1 1/1
Refrigerant charge kg 2,0 2,1 2,1 2,9 2,9 4,0 4,1 3,7 4,2 5,8 6,0 7,5
Low/high pressure switch bar 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42
n°ofaxialfan 11 1 1 11111112
Air flow m3/h 3533 3533 3533 7666 7666 7192 7192 13384 13384 12191 12191 16276
Fan maximum head Pa 157 157 157 320 320 386 386 311 311 430 430 240
Fan net available head Pa 75 75 75 120 120 120 120 180 180 180 180 180
Water flow in cooling mode l/h 1125 1409 1431 1560 1561 2179 2532 2973 3376 4116 4628 4727
Water flow in heat pump l/h 1348 1788 1720 1884 1884 2628 3053 3515 4020 4761 5237 5431
Diameter of hydrualic connections " 1 1 1 1 1 1 1 1,25 1,25 1,25 1,25 1,25
Water pressure drop (cooling) kPa 6 6 6 33 33 59 37 51 51 50 34 39
Water pressure drop (heating) kPa 8 8 8 46 46 85 52 72 71 64 44 50
Available pressure head (cooling) kPa 69 67 67 115 115 80 101 126 120 108 119 141
Available pressure head (heating) kPa 66 63 63 104 104 59 87 106 99 92 105 127
Water content escluding optionals dm3 1,5 1,5 1,5 3,0 3,0 3,0 3,0 4,0 4,0 4,0 4,0 5,5
Expansion tank dm3 20 20 20 30 30 30 30 50 50 50 50 125
Buffer tank dm3 1 1 1 5 5 5 5 5 5 5 5 8
Height mm 966 966 966 1247 1247 1247 1247 1565 1565 1565 1565 1988
Length mm 751 751 751 1012 1012 1012 1012 1131 1131 1131 1131 951
Depth mm 758 758 758 1224 1224 1224 1224 1274 1274 1274 1274 1823
Inlet + radiated sound power level dB(A) 74 73 73 75 75 74 74 79 79 78 78 80
Outlet sound power level dB(A) 75 75 75 82 82 81 81 84 84 81 81 89
Inlet + radiated sound power level
(LOW NOISE) dB(A) 70 70 70 70 70 71 71 76 76 75 75 77
Inlet + radiated sound pressure level dB(A) 46 45 45 47 47 46 46 51 51 50 50 52
Outlet sound pressure level dB(A) 46 45 45 47 47 46 46 51 51 50 50 52
Unit with pump and tank transport
weight kg 126 130 130 215 215 220 224 270 286 302 318 433
Unit with pump and full tank opera-
ting weight kg 135 139 139 232 232 237 241 306 322 338 355 540

MPED
18 All copying, even partial, of this manual is strictly forbidden RG66012163 - Rev 00
5 TECHNICAL CHARACTERISTICS
5.2 RATED TECHNICAL DATA OF HEAT PUMPS
- Coolingcapacity:outdoorairtemperature35°C,watertemperature12°C/7°C
- Heatingcapacity:outdoorairtemperature7°Cdrybulband6.2°Cwetbulb,watertemperature40°C/45°C
- Sound power level measured according to standards ISO 3741 - ISO 3744 and EN 29614-1
- Sound pressure level measured at a distance of 10 m and a height of 1�5 m above the ground in a free field (fan side)�
- The maximum electrical input is the mains electricity that must be available in order for the unit to work�
- The maximum current absorption refers to the current that will trigger the internal safety devices of the unit� It is the maximum current allowed in the unit� This value may never be exceeded; it
must be used as a reference for determining the size of the power supply line and the related safety devices (refer to the wiring diagram supplied with the units)�
* Seasonal energy efficiency class for LOW TEMPERATURE room heating under AVERAGE climatic conditions [EUROPEAN REGULATION No 811/2013]
MPED-H 032 035 040 054 066 T30 T34 T40 T45 T54 T61 T69 T76
Power supply V-ph-Hz 400-3-50
Cooling capacity kW 30,6 34,0 38,6 51,6 62,3 29,3 33,2 38,5 43,3 53,1 60,2 68,1 74,1
Cooling power input kW 10,1 11,6 12,8 17,7 24,1 10,3 12,6 13,7 16,5 19,2 22,2 24,5 28,5
EER 3,03 2,93 3,02 2,92 2,59 2,84 2,63 2,81 2,62 2,77 2,71 2,78 2,60
ESEER 3,33 3,33 3,44 3,43 3,04 3,63 3,56 3,68 3,57 3,15 3,19 3,43 3,46
Heating capacity kW 35,9 39,5 45,2 61,4 75,8 34,6 39,5 46,7 53,2 60,4 68,1 77,0 85,4
Heating power input kW 10,5 11,6 13,3 18,1 23,3 10,8 12,8 14,1 16,5 19,2 22,6 24,4 27,9
COP 3,42 3,41 3,40 3,39 3,25 3,20 3,09 3,31 3,22 3,15 3,01 3,16 3,06
SCOP 3,36 3,44 3,43 3,27 3,24 3,23 3,30 3,38 3,36 2,95 2,95 2,95 2,95
Energy Efficiency 132 135 135 128 127 127 130 133 132 115 115 115 115
Energy Efficiency Class* A+ A+ A+ A+ A+ A+ A+ A+ A+ A A A A
Maximum power input kW 17,3 18,5 21,0 28,6 35,2 22,7 25,4 25,3 27,1 30,7 33,2 37,8 42,0
Maximum current absorption A 41 43 47 55 66 50 55 55 58 57 61 69 76
Starting absorbed current A 166 161 183 221 266 103 115 146 156 177 187 202 229
n°ofcompressors/circuits 1/1 1/1 1/1 1/1 1/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1 2/1
Refrigerant charge kg 7,5 7,8 10,8 13,0 16,0 7,8 7,8 10,9 10,9 13,0 13,0 19,5 19,5
Low/high pressure switch bar 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42
n°ofaxialfan 2222222222222
Air flow m3/h 16276 16276 15776 20048 20048 16276 16276 15776 15776 24933 24933 24354 24354
Fan maximum head Pa 240 240 285 515 515 267 267 307 307 160 160 200 200
Fan net available head Pa 180 180 180 180 180 180 180 180 180 120 120 120 120
Water flow in cooling mode l/h 5307 5888 6681 8932 10776 5053 5737 6663 7495 9189 10423 11766 12818
Water flow in heat pump l/h 6173 6813 7800 10575 13063 5976 6818 8042 9155 10412 11733 13292 14730
Diameter of hydrualic connections " 1,25 1,25 1,25 1,25 1,25 1,25 1,25 1,25 1,25 2 2 2 2
Water pressure drop (cooling) kPa 49 39 42 56 54 29 37 44 55 51 64 50 58
Water pressure drop (heating) kPa 64 51 54 82 81 39 52 58 74 58 74 56 69
Available pressure head (cooling) kPa 123 128 117 107 92 148 133 116 94 136 119 127 115
Available pressure head (heating) kPa 109 114 99 76 52 131 113 95 65 126 100 110 87
Water content escluding optionals dm3 5,5 5,5 5,5 7,0 8,0 5,5 5,5 5,5 5,5 7,0 8,0 11,0 12,0
Expansion tank dm3 8 8 8 8 8 8 8 8 8 8 8 8 8
Buffer tank dm3 125 125 125 125 125 125 125 125 125 125 125 125 125
Height mm 1988 1988 1988 1991 1991 1988 1988 1988 1988 2013 2013 2013 2013
Length mm 951 951 951 979 979 951 951 951 951 1182 1182 1182 1182
Depth mm 1823 1823 1823 1823 1823 1823 1823 1823 1823 2100 2100 2100 2100
Inlet + radiated sound power level dB(A) 80 80 82 84 84 79 79 79 79 85 85 85 87
Outlet sound power level dB(A) 89 89 86 85 85 86 86 86 86 88 88 88 88
Inlet + radiated sound power level
(LOW NOISE) dB(A) 77 77 79 81 81 76 76 76 76 82 82 82 84
Inlet + radiated sound pressure level dB(A) 52 52 54 56 56 51 51 51 51 57 57 57 59
Outlet sound pressure level dB(A) 61 61 58 57 57 58 58 58 58 60 60 60 60
Unit with pump and tank transport
weight kg 462 493 522 530 570 455 491 528 562 653 674 695 796
Unit with pump and full tank opera-
ting weight kg 569 601 630 640 680 562 598 636 670 761 782 803 904

19
All copying, even partial, of this manual is strictly forbiddenRG66012163 - Rev 00
5 TECHNICAL CHARACTERISTICS
5.3 AIR FLOW RATE SETTING
The ducted unit’s nominal operating point varies depending on the pressure drop of the duct downstream from the fan; therefore, for every installation it
is necessary to check that the fan’s air flow rate corresponds with the nominal air flow rate as a function of the duct’s size�
The ducted unit’s nominal operating point is calculated starting from the static pressure difference between the intake section (via an umbrella-handle
shaped capillary tube) and the compartment’s inner section (via 4 measuring points located along the compartment’s circumference)�
The air flow rate is computed on the basis of the static pressure difference according to the following equation:
qv=k∙√∆p
qv in [m3/h],
∆pin[Pa].
Where k is a constant value supplied by the fan manufacturer according to the diameter of the compartment used�
The nominal air flow rate can be set as follows:
• Manually, by means of a base microchiller 2 controller
• Automatically, by means of an Advanced pCO controller
and sets a maximum value for the 0-10V signal of the condensation and evaporation control, which will correspond to the nominal air flow rate�
BASE CONTROLLER
Theinstallerwillvarythefanspeedinordertomeasure,usingadifferentialpressuregauge(belongingtohim/her),the∆pcorrespondingtothenominal
airflowrate.Onboardtheunitwillbeprovidedthetableoftherelationshipbetween∆pandnominalflowrate.
ADVANCED CONTROLLER
Theautomaticcalibrationoftheflowrateisperformedwithaproportional-integrativelogicontheknown∆pvalue.
By means of a differential pressure transducer, the pressure difference between the intake section and the compartment’s inner section can be converted
into a 4-20mA or 0-10V signal to be sent to the microprocessor controller; the internal software will transform this signal into a differential pressure
value�
Theretroactiveactionofthelogicwillcomparethisvaluewiththeknownparameter∆p(dependingontheunitmodel),soastovarythenumberof
revolutionsofthefansand,therefore,theairflowrateuptothedesignvalue.Thepairofvalues,∆pandfanairflowrate,thusdeterminedissetinthe
advanced microprocessor as the nominal operating point, which is useful for establishing the limit value for condensation/evaporation control� The auto-
calibration procedure will be performed with the unit off and will have a preset maximum duration�

MPED
20 All copying, even partial, of this manual is strictly forbidden RG66012163 - Rev 00
6 PERFORMANCE
In order to define the performances of MPED subject to conditions different from rated conditions, a computer program for the correct choice of the units
is provided by Galletti SpA�
With a few input data it will be possible to get information on the behaviour of a MPED referring to the desired operating conditions�
It will be sufficient to enter the following data:
• Inlet air temperature
• Inlet water temperature
• Outlet water temperature
• Ethylene glycol percentage (default 0)
• Directivity factor and distance
Output data
• Cooling / heating capacity
• Water flow rate on user side
• Water pressure drop on user side
• Total power input
• Total Absorbed current
• Compressor Power Input
• Compressor Absorbed current
• EER
• ESEER
• COP
• Pump available head
• Maximum current (FLA)
• Inrush current (LRA)
• Inrush Current with Soft Starter kit
• Sound power level LW
• Sound pressure level Lp
• Air flow rate
• Number of fans
• Fan input power
• Fan input current
• Compressors/Circuits
• Tank Capacity (optional)
• Power supply
The selection report generated by the software includes the drawing with overall dimensions�
This manual suits for next models
1
Table of contents
Other Galletti Chiller manuals
Popular Chiller manuals by other brands

McQuay
McQuay ACZC SE-ST Installation, operation and maintenance manual

AERMEC
AERMEC NRL F Series installation manual

York
York YCAL0019 Installation operation & maintenance

Water Furnace
Water Furnace ENVISION 2 NKW Series manual

Aquacal
Aquacal TropiCal T035 Operation manual

Hitachi
Hitachi SAMURAI Series Service manual

Carrier
Carrier 30HK Installation, Start-Up and Service Instructions

Advantage
Advantage MGD-15W-MGD-ADV-02 instruction manual

Midea
Midea LSBLG365/MCFN Technical & service manual

Kaysun
Kaysun KHP-MO 4 DVP Installation and owner's manual

Samsung
Samsung DVM installation manual

Daikin
Daikin AGZ030E Installation, operation and maintenance manual