AccuTherm US-5461P-ACCU1 User manual

Temperature and Humidity Controller
US-5461P-ACCU1
Instruction Manual
This is the instruction manual for this controller unit,please
store it properly. Please read manual before operation.
応用電子工業株式会社

2
Contents
1. Introduction
P. 3
2. System Configuration
P. 4
3. Operation Menu
P. 5
4.「Monitor」Display Screen
P. 6
4-1. Control Mode (Program control)
P. 6
4-2. Control Mode (Fix control)
P. 7
5.「Mode Set」Display Screen
P. 8
5-1. Operation Mode(Fix/Program)option
P. 8
5-2. Operation Startup(Instant/Pre-set 01/01 00:00)option
P. 8
5-3. Key Lock(Enable/Disable)option
P. 8
5-4. Power down(Stop/Cold start/Warm start)option
P. 8
6.「Graph」Display Screen
P. 9
6-1. PV Graph
P. 9
6-2. SV Graph and Historical Graph
P. 9
7.「Program Setting」Display screen
P. 10
7-1. Program Edit
P.10
7-2. Standby Mode
P. 13
7-3. Time Signal/ Time control screen
P. 13
7-4. Program name setting
P. 14
8.「Assistance Setting」Operation Menu
P. 15
9.「Event History」Operation Menu
P.15
10.「Administration Right」Operation Menu
P.16
11.「Equipment information」Operation Menu
P.16

3
1.Introduction
Thank you for purchasing our US-5461P-ACCU1Temperature and humidity controller. To ensure accurate and
proper usage of this equipment, please read and understand this instruction manual before operation.
Please observe the following warnings/ cautions before the operation of this device.
To ensure safety in handling the instrument, please be sure to observe the following warnings/cautions as well as the
precautions in this manual.
Warning
General
To prevent an electric shock, be sure to disconnect this instrument from the main power supply
when wiring it.
Protective
grounding
(1)To prevent an electric shock, be sure to provide protective grounding before providing power
supply to this instrument.
(2)Do not cut off the protective grounding conductor or disconnect protective grounding.
Power
supply
Check that the power supply voltage of this instrument matches that of the supply source.
Rated power voltage range : 100-240VAC
Rated power frequency : 50/60Hz
Environment
Do not operate this instrument in atmosphere containing inflammable, explosive or corrosive gas,
or in environments where water or steam may come in contact with the product
Input/output
wiring
To prevent electric shock, be sure to provide wiring after turning off the power.
caution
Input/output
wiring
Do not use the open terminals for other purposes such as relay.
Inside of
instrument
Do not disassemble the inside of the main unit.

4
2.System Configuration
HMI Interface
Display
MAIN BOARD
(US-5461)
I/O BOARD
(P-791)

5
3. Operation Menu
This device works on a touch-screen panel for operation and control. All function can be selected from
「Menu Selection」
Operation Menu
Monitor
Setting
Program
CURVE
OPTION
History
Authorisation
1. Set Present Value, Control mode and Operate status
2. For RUN, PAUSE, HOLD, ADVANCE, STOP function
3. “NEXT” icon is to view the present DRY/WET value, the output percentage,
The output condition and the running time ; RUN, STOP,
ADVANCE, HOLD can operate under such circumstance
4. when in control mode, the「Set」button allows you to set the control value
5. The「Curve」button allows you to view, set and operate the PV and SV graph
for both present and historical data
1. Operation Detail (Fixed/Programmable)
2. Operation Detail (Fixed) – setting value and SLOP setting of Temp and Humi
3. KEY LOCK (YES/NO)
4. Power down setting (STOP/cold start/start continuity)
5. Action when stop control(STOP/Normal –end conttol Temp)
1. Program editing 4. Cycle condition setting
2. Testing program file name editing 5. Standby Control Setting
3. Time control Setting
1. Date/ Time setting 3. Controller Unit Version
2. Wait Setting (TEMP. / HUMI.)
1. PV, SVgraph and historical eventrecord
2.Temperature/Humidity/Time
For viewing of past event record
User authorization setting

6
4.「monitor」operation instruction
4.1 Control Mode=「Program control」:
4-1-1. Top Right hand corner □
a shows the status of controller(RUN/STOP)
4-1-2. Top Left hand corner □
b to return to the menu selection page
4-1-3. Bottom Left hand corner □
c「CURVE」,to check, the present and past record of PV and SV graph
4-1-4. Bottom corner “NEXT”to check and view current humidty bulb value, input/ output, current status,
and to stop, hold, jump and continue operation.
4-1-5. you could press “JUMP” jump to next step. (you need to press twice when you set up “WAIT”
fuction)
4-1-6. you could press “HOLD”to hold the time.
4-1-7. you could press ”START” to make the controller start to operate and press “STOP” to make the controller
stop operating
4-1-8. The controller will show below when ALARM occur
Program-Data Detail
Program-Stop
Program-process Operation
Message display
a
b
c

7
4-2. Control Mode=「Fix mode」:
4-2-1. Top Right hand corner □
a shows the status of controller(RUN/STOP)
4-2-2. Top Left hand corner □
b to return to the menu selection page
4-2-3. Bottom Left hand corner □
c「CURVE」,to check, the present and past record of PV and SV graph
Fix-In:Stop
Fix-In:Progress
Output :Fix
Control
a
b
c

8
4-2-4. Bottom corner “NEXT”to check and view current humidty bulb value, input/ output, current status,
and to stop, hold, jump and continue operation.
4-2-5. you could press “JUMP” jump to next step. (you need to press twice when you set up “WAIT”
fuction)
4-2-6. you could press “HOLD”to hold the time.
4-2-7. you could press ”START” to make the controller start to operate and press “STOP” to make the controller
stop operating
4-2-8. The controller will show below when ALARM occur
5.「Setting」menu instruction
5-1. Control Mode( Fixed/ Program)options
To decide the control mode between fixed or programmable option
When in Fixed mode, able to set between wet/ dry target temperature and slope requirement
When in Program mode, able to set the number of segment and group

9
5-2. END mode( STOP/ NORMAL ℃)options
To set up the temperature after program stop.
STOP – controller stop immediately when program end
NORMAL ℃- Controller will stop after reach the setting temperature(0~50℃).
5-3. KEY LOCK( YES / NO)options
The ICON LOCK for RUN and STOP.
5-4. Resume operation( Stop / Cold Start/ Warm Start )options
Stop:To interrupt power reset function (To prevent machine from auto-resume, please select this
function)
Cold Start:To resume operation from the beginning stage
Warm Start:To resume operation from where it has been interrupted
6.「CURVE」Operation menu
6-1. Realtime Curve
Top Left corner「menu selection」to return to the main selection pag;Top Right corner「MONITOR display」
to return to “MONITOR” page
Right corner”TEMP”to select the temperature range(-100~200)
Right corner”HUMI”to set the humidity value range(0~100%)
Right corner「Time」to select the timing range(biggest range: 1~3 hr)

10
Real time curve shows the operation curve whithin 3 hour. And the curve will be disappear when controller stop
6-2. Curve setting and historical records
Top Left corner「menu selection」to return to the main selection page;Top Right corner「MONITOR
display」to return to “MONITOR” page
The prorram setting curve could display max 10 segment in one page
Right corner”TEMP”to select the temperature range(-100~200)
Right corner”HUMI”to set the humidity value range(0~100%)
Right corner”TIME”to set the time period range(history curve: 3H/6H/12H/1D)
Right corner “CLR”to delete and clear the graph display screen
Right corner「Read LDF」to select recorded graph data
You could press “READ FILE”to select and read the history cuve which be saved before.
7.「Program Setting」Instruction Menu
T
7-1. Program Edit
Program for Temperature/ Humidity/ time/ Stand by/ message/ Cycle data can be edited and stored
Program setting curve
History cureve

11
according in this program individually.
Enter as below:
Setting Procedure 1 : make sure the program number and start setting the program. Set the temperature value,
humidity value, time period, temperature waiting time, humidity waiting time and time signal (4 units)
※ The program with max 10 groups, 100 segments
Setting Procedure 2: Set setting value with keyboard. ※setting range : -100~200℃
Seting Procedure 3:Set setting value with keyboard. ※setting range : 0.0~99.9%
※humidity setting value will not be setted if temperature setting value out of range(0℃<temperature<100℃)
※The humidity value will disappear in “monitor”screen if the humidity setting value is 0.

12
Seting Procedure 4:Set the time period of segment
※Setting range : 00H00M ~ 99H59M
※The Slop control will be actived if the setting time period is not zero.
Seting Procedure 5: Waiting mode is active or not.
※Set the temperature and humidity waiting mode is active or not
※enter “0”will display “-“and it means the waiting mode is not active, ether “1”will display “T”and
it means the temperature waiting mode is active. “H”means the humidity waiting mode is active.
Seting Procedure 6:Set the time period of waiting, it means controller will go to next segment if the time is
up and the present value is not within the setting range.
※Setting range : 00H00M~99H59M

13
Seting Procedure 7: Set the time signal type.
※There are 10 time siganl type could be set
※time signal type could be set in “time signal setting”screen
Seting Procedure 8: Cycle setting
You could set total, part and link cycle in cycle setting screen if you need
Cycle pattern
Cycle Times range :1~9999
Link pattern setting range 1~9
Part cycle range Max : 5

14
7.2 Program edit
Edit the program which is set before
7.3 Time signal setting
There are ten terms (0-9) in “Time signal time set” screen. NO.0 represent OFF;and NO.1 represent ON,
NO.0 and NO.1 cannot be altered;NO.2-NO.9 can be set according to requirement. Explaination as below:
※ ON DELAY:time signal act after segment counting started and(ON DELAY TIME)period passed。
E.g.:Time Signal Model NO.2 with ON DELAY=1hour, if program time setting is 2 hours, and you choose
time signal mode no.2 in this segment.
The result of procedure:after program started, 1 hour before signal as OFF,1hour later as ON。
※ CUT ON/OFF:use CUTmode or not(CUT TIME setting enable after using Cut mode )。
E.g.:Time Signal Model NO.2 with ON DELAY=1hour and CUT TIME=30min,if program time setting is
2 hours, and you choose time signal mode no.2 in this segment
The result of procedure:after program started, 1hour before as OFF,in the midst of 30mins as ON,
the last 30mins as OFF。
“Time Signal” setting is show as below

15
8. Option Setting
The option setting screen is shown below
8.1 Waiting mode setting
Set the temperatire and humidity waiting parameter.
8.2 Time setting
Set the time of controller
8.3 Language
3 kinds of language could be changed (traditional Chinese, simple chanese, English)
8.4 LCD setting
Set the backlight valume(0~15) and screen saver time(0~99 minutes)
8.5 Version
Could check the version of controller. FW means hardware version and SW means the software
version of HMI
LCD reated setting instrument information

16
9. Event Record History
9.1 Alarm history
This screen list down all the alarm records. A total of 50 events can be stored

17
9.2 Operation history
This screen list down all the operation records. A total of 100 events can be stored
10. DATA LOG
10.1 Link of logger data
Could choose C: for internal memory, D: for external memorry(SD card), E: for external memorry(USB disk)
10.2 record interval
5 sec, 30 sec, 1 min, 5 min, 10 min interval could be choosed
10.3 File save config
Could choose auto or manual record.
10.4 record file edit
Copy, delete and save for record file

18
11. Authority setting
11.1. User:input account ID of operator.
11.2. Password:input password of operarator.
11.3. Authorisation:Administrator and User account can be set:
Administrator has the full operation authorisation
User are only authorize to view and operate program accordingly
Table of contents
Other AccuTherm Controllers manuals
Popular Controllers manuals by other brands

IMI NORGREN
IMI NORGREN R74G Installation & maintenance instructions

TOPP
TOPP C130 Series Installation and use instructions

iX-tech
iX-tech Pro user manual

Franklin
Franklin BAS-1P Installation & operation guide

Aventics
Aventics EV12 operating instructions

Remote Control
Remote Control RCEL Series Instruction