Acorn Safety S0470 Manual

www.acornsafety.com
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS
WALL MOUNT SHROUDED EYE/FACE WASHES
TECHNICAL ASSISTANCE TOLL FREE TELEPHONE NUMBER
1.800.591.9360
TECHNICAL ASSISTANCE FAX: 1.626.855.4894
ACORN SAFETY
P.O. BOX 3527
CITY OF INDUSTRY, CA 91744-0527
UNITED STATES OF AMERICA
Models S0470 / S0470-BF / S0480 / S0480-BF
Manual #7109-103-001 Revised: 05/06/13
NOTES TO THE INSTALLER:
1. Please leave this documentation with the owner of the fixture when finished.
2. Please read this entire booklet before beginning the installation.
3. Check your installation for compliance with plumbing, electrical, ANSI Z358.1 and
other applicable codes.
LIMITED WARRANTY
UNITED STATES AND CANADA
Acorn Safety warrants that its products are free from defects in material or workmanship under normal use and
service for a period of one year from date of shipment or 18 months after the date of shipment from factory ,
whichever comes first. Acorn's™ liability under this warranty shall be discharged solely by replacement of repair of
defective material, provided Acorn™ is notified in writing within one year from date of shipment, F.O.B. Industry,
California.
This warranty does not cover installation or labor charges and does not apply to materials, which have been
damaged by other causes such as mishandling or improper care or abnormal use. The repair or replacement of the
defective materials shall constitute the sole remedy of the Buyer and the sole remedy of Acorn™ under this warranty.
Acorn™ shall not be liable under any circumstances for incidental, consequential or direct charges caused by defects
in materials, or any delay in the repair or replacement thereof. This warranty is in lieu of all other warranties
expressed or implied. Product maintenance instructions are issued with each unit and disregard or non-compliance
with these instructions will constitute an abnormal use condition and void the warranty. Stainless steel must be
protected on job sites during construction and must be properly maintained after the water has been introduced into
the safety product or Acorn's™ warranty is void.
Acorn Safety a division of Acorn Engineering ™Company

ROUGH-IN FOR MODEL S0470/S0480
1. Read the installation instructions prior to beginning the installation.
2. Separate parts from packaging and verify all necessary parts are accounted for and undamaged. Obtain missing or
damaged parts from Acorn Safety prior to beginning installation.
3. Flush water supply lines prior to installation. This will remove unwanted debris from the lines and prevent unwanted
blockages in the safety equipment.
4. In order to comply with ANSI Z358.1, the safety equipment must be inspected periodically. An inspection tag is
provided for documentation purposes.
5. All employees at risk of injury/contamination should be informed and trained in the use of this and any other safety
equipment. The signage provided should be highly visible, posted in a well lit area within the area served by the
safety station.
Installation & Operation Manual
PRELIMINARY STEPS
Manual #7109-103-001 Page 2 of 6 Revised: 05/06/13
Acorn Safety a division of Acorn Engineering ™Company
A1-1/4" [38] OD WASTE OUTLET
1/2" NPT SUPPLY INLET
Ø1/4" [6] OD MOUNTING HOLE
B
C
Ø1/4" x 1-1/4" LONG [Ø6 x 38 LONG]
D
MOUNTING SLOTS
GENERAL DIMENSIONS:
1. ALL DIMENSIONS ARE IN INCHES [MM].
2. REFER TO ADA FOR CLEAR FLOOR/GROUND SPACE AND APPROACH REQUIREMENTS.
*3. ANSI Z358.1 REQUIRES NOZZLES TO BE MOUNTED BETWEEN 33" - 45" [838 - 1143] ABOVE THE FINISHED
FLOOR.
4. ANSI Z358.1 REQUIRES A MINIMUM DISTANCE OF 6" [152] FROM WALL OR OBSTRUCTION.
85
8"
[219]
57
8"
[149]
141
2"
[368]
13
8"
[36]
31
2"
[88]
10"
[254]
113
4"
[298]
47
8"
[124]
33
8"
[86]
15
8"
[41]
107
8"
[276]
61
4"
[159]
7
8"
[22]
47
8"
[124]
237
8" [606]
MIN FOR ANSI
Ø12" [Ø305] MIN
FROM WALL OR
OBSTRUCTION
D
C
B
A
*33" - 45"
[838 - 1143]
55
8" [142] TO
SUPPLY INLET

Installation & Operation Manual
Manual #7109-103-001
ROUGH-IN FOR MODELS S0470-BF/S0480-BF
Page 3 of 6 Revised: 05/06/13
Acorn Safety a division of Acorn Engineering ™Company
*33" - 45"
[838 - 1143]
85
8"
[220]
1
2"
[14]
115
8"
[295]
57
8"
[149]
171
2"
[445]
113
4"
[298]
87
8"
[225]
47
8"
[124]
GENERAL DIMENSIONS:
1. ALL DIMENSIONS ARE IN INCHES [MM].
2. REFER TO ADA FOR CLEAR FLOOR/GROUND SPACE AND APPROACH REQUIREMENTS.
*3.) ANSI.Z358.1 REQUIRES NOZZLES TO BE BETWEEN 33" - 45" [838 - 1143] ABOVE THE FINISHED
FLOOR.
4. ANSI Z358.1 REQUIRES A MINIMUM DISTANCE OF 6" [152] FROM WALL OR OBSTRUCTION.
1-1/4" [38] NPT
WASTE OUTLET
1"
[27]
33
8"
[85]
33
8"
[86]
7
8"
[22]
55
8"
[143]
47
8"
[124]
A
B
C
D
1-1/4" [38] OD WASTE OUTLET
1/2" NPT SUPPLY INLET
Ø1/4" [6] OD MOUNTING HOLE
Ø1/4" x 1-1/4" [Ø6 x 38] LONG
MOUNTING SLOT
A
B
C
D
25" [635]
MIN FOR ANSI
8-5/8" [218] TO
SUPPLY INLET
Ø12" [Ø305] MIN
FROM WALL OR
OBSTRUCTION

Installation & Operation Manual
Manual #7109-103-001
INSTALLATION INSTRUCTION:
Supplies required: (not provided by Acorn)
1. Wall fasteners for signage & possible eye/face wash
mounting.
2. Pipe sealant or Teflon tape for sealing water connections.
IMPORTANT: FLUSH WATER SUPPLY LINES PRIOR
TO CONNECTION TO SAFETY EQUIPMENT.
NOTES:
• Use hand tools and wrenches in a manner which will prevent
marring finished surfaces. Strap wrenches or tools with
plastic jaw linings are highly recommended.
• Refer to Rough-in for location of supply and drain lines.
• Fragments of Teflon tape or pipe sealant residue can with the
proper
operation of this unit. Ensure pipe sealant
methods do not cause contamination in the system.
STEP ONE: LOCATE & DRILL MOUNTING HARDWARE
HOLES
1. Locate the eye/face was against the wall at the
recommended height. (NOTE) The eye/face was needs to be
mounted into studs or heavy duty wall anchors, supplied by
the installer.
2. From underneath the eye/face wash, mark the mounting
holes for drilling.
3. Drill the holes to fit the appropriate hardware. supplied by the
installer.
STEP TWO: MOUNT THE UNIT
1. Hole the eye/face wash against the wall and install the
mounting hardware into the previously drilled holes.
2. Make sure the eye/face wash is level and tighten all
hardware.
STEP THREE: PLUMBING & TESTING
1. Plumb the drain tube to the existing drain line.
2. Plumb a ½”line to supply to the ½” ball valve, ensure that no
debris are in the line
3. Turn on potable water supply.
4. Turn eye/wash wash on and inspect system for leaks, verify
wash heads flow properly.
STEP FOUR: SINAGE & INSPECTION
1. Position sign with clear visibility, in close proximity to safety
equipment and mark mounting hole locations.
2. Select appropriate 1/4” anchors, screws and washers
(Supplied by others) to install signage.
3. Attach inspection tag supplied, with plastic zip tie.
BACKSIDE MOUNTING HOLES
SHOWN FOR REFERENCE
MOUNTING HOLE
LOCATION 4X
INSPECTION
TAG
MOUNTING SCREWS &
HARDWARE TYPICAL 2X
(PROVIDED BY INSTALLER)
Page 4 of 6 Revised: 05/06/13
Acorn Safety a division of Acorn Engineering ™Company

Revised: 05/06/13
Manual #7109-103-001
Installation & Operation Manual
OPERATION INSTRUCTIONS:
become familiar with the location and operation of the
nearest emergency plumbing fixture. Emergency
plumbing fixtures stations are simple to use and require
hands free operation once the station is activated.
Regular instruction regarding proper care and use will
increase confidence that the units are accessible and
function properly.
The route and area surrounding the Eye Wash should
be clear and unobstructed; the sooner eyes are flushed,
the less likelihood of damage. Eye Wash stations should
be located in close proximity to the hazard and take no
more than 10 seconds to reach. In the case of sever eye
contamination the victim may require assistance to the
Eye Wash station and help flushing their eyes.
Safety plumbing fixture equipment should be operated
weekly for a period long enough to verify operation,
clear the supply line of any sediment build-up and
minimize microbial contamination due to sitting water.
1. To start the Eye Wash, swing spray nozzle assembly
over the basin and push the paddle forward to the
horizontal or fully “ON” position. Flushing should start,
popping the spray nozzle caps open.
2. Lower both eyes into flow. Both eyes should be
flushed to prevent contamination from one eye from
being delivered to unaffected eye. Personnel who
wear contact lenses should remove them immediately
prior to or during the flush to prevent the
contamination from remaining against the cornea
possibly causing unnecessary damage or pain.
3. Using thumb and forefingers, fully open eyelids and
flush eyes thoroughly for approximately 15 minutes or
until medical personnel arrive. Be prepared to let the
doctor know what type of contamination has entered
the eye.
4. When finished return the push paddle to the vertical
or fully “OFF” position and return spray nozzle
assembly to standby position. Flushing fluid should
stop. Once flushing fluid has stopped flowing, return
spray nozzle lids to the closed position to protect from
airborne contaminates.
Employees who work with hazardous materials should
MAINTENANCE GUIDE:
Maintain and inspect in accordance with ANSI Z358.1-
2009
1. Check for obvious signs of wear, broken or defective
equipment. Re-paint if necessary. Replace missing or
defective equipment such as broken push paddles,
missing signs and inspection tags.
2. Remove strainer and washout any debris collected
–replace as required.
3. Operate Eye Wash nozzles using the push paddle to
place ball valve in the fully “ON” position checking for
smooth operation of valve push paddle mechanism at
the same time ensuring that the Eye Wash spray
nozzle caps pop off immediately when actuated. If the
ball valve does not operate smoothly check the
actuating assembly for binding or missing parts. If the
Eye Wash spray nozzle caps do not pop off immediately
when actuated check for correct supply inlet
pressure.
4. While in operation, inspect spray nozzles for clogs or
debris correct or replace as required.
5. Return push paddle to vertical or fully “OFF” position
and swing back to stand by position. To prevent Eye
Wash spray nozzles from becoming contaminated,
always close nozzle lids after each use.
Page 5 of 6
Acorn Safety a division of Acorn Engineering ™Company

Installation & Operation Manual
PARTS LIST
Manual #7109-103-001
ITEM # PART NUMBER DESCRIPTION
7101-100-001 EYEWASH NOZZLE
7101-104-001 FACEWASH NOZZLE
7101-057-001 EYEWASH NOZZLE W/ S/S LID
7101-058-001 FACEWASH NOZZLE W S/S LID
7101-060-001 YOKE STEM ASSEMBLY, BF
7101-003-001 YOKE STEM ASSEMBLY
3 7100-108-000 BOWL STRAINER
7101-019-000 S/S BOWL, SHALLOW
7101-008-000 S/S BOWL, DEEP
5 7101-046-000 S/S BOWL GASKET
6 7101-054-022 DRAIN CASTING
7 7100-218-000 SUPPLY TUBE
7101-214-002 S/S SHROUD, BF
7101-215-002 S/S SHROUD
9 7000-020-199 FLANGE NUT
7100-113-001 CHROME TAILPIECE ASSY
7100-234-001 ELBOW DRAIN ASSY, BF
11 7100-140-001 WATER SUPPLY STRAINER
7101-001-000 CHROMED BALL VALVE
7101-002-001 S/S BALL VALVE
13 7101-224-199 5/16-18 HEX NUT
14 0304-007-000 PADDLE STOP
15 7100-440-000 BUSHING
16 7101-206-001 PADDLE ASSY
17 7100-401-000 INSPECTION TAG
18 7100-402-000 SAFETY EYEWASH SIGN
12
10
8
4
1
2
1
2
3
4
6
7
8
9
10
17
16
15
14
13
12
11
5
10
18
Page 6 of 6 Revised: 05/06/13
Acorn Safety a division of Acorn Engineering ™Company
This manual suits for next models
3
Table of contents
Other Acorn Safety Washer manuals