manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. ADEMCO
  6. •
  7. Smoke Alarm
  8. •
  9. ADEMCO 5808 User manual

ADEMCO 5808 User manual

fi
Toreplacebatteries:
1. Removethedetectorfromitsmountingplatebytwistingthedetectorcounter-
clockwise.Removebatteries,ifreplacing,anddispose properly.
2. Installtwonew3-voltCR123ALithiumbatteriesinthebatterycompart-
ment. Followthepolaritydiagraminsidethecompartment.
3. Reinstall the smoke detector onto the mounting plate by turning the
detector clockwise.
4. Test the detector as described in the TESTING TRANSMITTER SIG-
NAL section of this manual. The LED should flash about once every 40
seconds to indicate normal operation. If the batteries are not installed
correctly, the smoke detector will not operate and the batteries may be
damaged.Ifthedetectordoesnotappeartobesendingasignalduring
anyofthetests,checkforcorrectbatteryinstallation.
Test Module
Port
Indicator Light
Pulsing: Normal/Thermal Alarm
Fast Blink: Smoke Alarm
None: Call for Service
Test Switch
Figure1. 5808Wireless Smoke/ Heat Detector
PROGRAMMING
Thesmokedetector’sIDmustbeenrolledintheQEDcontrolpanelduring
installationofthesystem.TheQEDcontrolpanelshouldbeprogrammed
toenrollthe 5808asan“RF”unit(mustbeprogrammedas“supervisedRF”
for UL installations). Put the QED control panel in the program
mingmodeand performthefollowing:
With the QED control panel, program the detector as loop 1 and either
manuallyentertheserialnumberthatisonthelabelofthe 5808,orpress
thetestswitchtocauseatransmission. Additionaltransmissionswillcause
the“Confirm”display toappearonthekeypad display.
SeetheQEDcontrolunit’sinstallationinstructionsforfurtherdetails.
Beforeinstallingdetectors,pleasethoroughlyreadtheseinstallationinstruc-
tionsandManualI56-407,
GuideforProperUseofSystemSmokeDetectors,
whichprovidesdetailedinformationondetectorspacing,placement,zoning,
wiring, and special applications. Copies of this manual are available from
ADEMCO.
NOTICE:Thismanualshouldbeleftwiththeowner/userofthisequipment.
IMPORTANT:Thisdetectormustbetestedandmaintainedregularlyfollowing
NFPA72requirements.Thedetectorshouldbecleanedatleastonceayear.
WARNING: Do not use the maintenance signal as an indication that the
detectorhasreachedthelimitsofitsnominalsensitivityrange.Maintenance
onlyindicatesthatthedetectormayneedcleaningorcannolongerrespond
to smoke and shall not be used as a sensitivity indicating means.
GENERAL DESCRIPTION
The5808photoelectronicsmoke/heatdetectorwithbuilt-inwirelesstransmit-
ter is intended for use with wireless alarm systems that support QED 5800
seriesdevices.RefertoQEDcontrolcommunicatorinstallationinstructions
forcompatibility.The 5808smoke/heatdetectorcanbeusedwith5881series
(L,M,H)and5881EHreceiversforresidentialinstallations.The 5808smoke/
heatdetectorcanbeusedwiththe5881EHreceiverforcommercialinstalla-
tions. The transmitter can send alarm, tamper, maintenance (when QED
control panels are equipped to process maintenance signals), and battery
conditionmessagestotheQEDsystem'sreceiver. Themaintenancesignal
willeitherindicatethatthephotochamberrequirescleaningorthatthedetector
can no longer respond to smoke and may need replacement. Refer to the
wirelesssystem'sinstructionsforthemaximumnumberoftransmittersthatcan
besupported.
The 5808soundsitsbuilt-in hornwhensmokereachesthedetector(the
LEDalsoflashesrapidly)orwhentheairtemperaturereaches135°F(the
LEDflashesnormally,aboutonceevery40seconds).Amessageisalso
senttothewirelessQEDcontrolpanelandthesmokedetector'sIDnumber
is displayed at the console. The alarm message is transmitted every 4
secondsuntilthesmokeconditionhasclearedandthedetectorhasreset.
About1secondafterthehornstops,aRESTOREmessageistransmitted
totheQEDcontrolpanelandtheIDnumbercanbeclearedfromthepanel.
Duringnormal,maintenance,andlowbatteryconditions,theLEDflashes
approximatelyonceevery40seconds.
BATTERY INSTALLATION AND REPLACEMENT
The5808ispoweredbytwo3-voltCR123AorDL123ALithiumbatteries
(included).ThedetectorchecksforlowbatteriesateverynormalLEDflash.
Ifalowbatteryisdetected,thetransmittersendsalowbatterymessageto
theQED control panel,whichbeeps and displaysthedetector's ID. This
conditionwillexistfor a minimum of seven days, and then the detector's
hornwill"chirp"aboutevery40seconds.Thebatteriesshouldbereplaced
BEFOREthechirpsbegin.BESURETOREPLACEBOTHBATTERIES
WITH FRESH ONES.
AD300-00-00 I56-918-06
ADEMCO, 165 Eileen Way, Syosset, New York 11791
AD300-00-00 4 I56-918-06
© ADEMCO 1998
WARNING
LIMITATIONS OF SMOKE DETECTORS/TRANSMITTERS
This smoke detector is designed to activate and initiateactivate and initiate
activate and initiateactivate and initiate
activate and initiate emergency
action, but will do so only when used in conjunction with an authorized
fire alarm system. This detector must be installed in accordance with
NFPA standard 72..
..
.
Smoke detectors will not work without power.Smoke detectors will not work without power.
Smoke detectors will not work without power.Smoke detectors will not work without power.
Smoke detectors will not work without power. AC or DC powered
smokedetectorswillnotworkifthepowersupplyiscutoffforanyreason.
Alarm signal sent by the wireless transmitter in this detector may be
blocked or reflected by metal before reaching the alarm receiver. Even
if the signal path has been recently checked, blockage can occur if a
metal object is moved into the path.
Smokedetectorswillnotsensefires whichstartwheresmokedoesSmokedetectorswillnotsensefires whichstartwheresmokedoes
Smokedetectorswillnotsensefires whichstartwheresmokedoesSmokedetectorswillnotsensefires whichstartwheresmokedoes
Smokedetectorswillnotsensefires whichstartwheresmokedoes
notreachthedetectors.notreachthedetectors.
notreachthedetectors.notreachthedetectors.
notreachthedetectors. Smolderingfirestypicallydonotgeneratealot
ofheatwhichisneededtodrivesmokeuptotheceilingwherethesmoke
detectoris usually located.Forthis reason, theremay be largedelaysin
detecting a smoldering fire with either an ionization-type detector or a
photoelectric-type detector. Either one of them may alarm only after
flaming has initiated, which will generate the heat needed to drive the
smoke to the ceiling.
Smoke from fires in chimneys, in walls, on roofs, or on the other side of
aclosed doormaynot reachthe smoke detectorand alarm it.A detector
cannot quickly detect, or sense at all, a fire developing on another level
ofabuilding.Alarmwarningdevices,such asbellor horns,maynotalert
peopleorwakeupsleepersiftheyarelocatedontheothersideofclosed
or partly open doors, or on another level. Persons may not hear a
warning device over the noise levels of a radio, air conditioner or other
appliances, or traffic. For this reason, detectors shall be located ondetectors shall be located on
detectors shall be located ondetectors shall be located on
detectors shall be located on
every level and in every bedroom within a building.every level and in every bedroom within a building.
every level and in every bedroom within a building.every level and in every bedroom within a building.
every level and in every bedroom within a building. Alarm warning
devices,howeverloud,maynotwarnhearing-impairedpeopleorwaken
deep sleepers.
Smoke detectors shall be located in any room where an alarmSmoke detectors shall be located in any room where an alarm
Smoke detectors shall be located in any room where an alarmSmoke detectors shall be located in any room where an alarm
Smoke detectors shall be located in any room where an alarm
control is located, or in any room where alarm control connectionscontrol is located, or in any room where alarm control connections
control is located, or in any room where alarm control connectionscontrol is located, or in any room where alarm control connections
control is located, or in any room where alarm control connections
to an AC source or phone lines are made.to an AC source or phone lines are made.
to an AC source or phone lines are made.to an AC source or phone lines are made.
to an AC source or phone lines are made. If detectors are not so
located, a fire within any of these rooms could prevent the QED control
from reporting a fire.
Smoke detectors have sensing limitations, too.Smoke detectors have sensing limitations, too.
Smoke detectors have sensing limitations, too.Smoke detectors have sensing limitations, too.
Smoke detectors have sensing limitations, too. Ionization detectors
and photoelectronic detectors are required to pass fire tests of the
flaming and smoldering types. This is to ensure that both can detect a
wide range of fires. Ionization detectors offer a broad range of fire-
sensing capability, but they are somewhat better at detecting fast-
flamingfiresthanslow-smolderingfires.Photoelectronicdetectorssense
smolderingfires better than flaming fires,which have little, if any,visible
smoke.Becausefiresdevelopindifferentways,andareoftenunpredict-
able in their growth, neither type of detector is always best, and a given
detector may not always provide early warning of a specific type of fire.
A78-2332-01
5808 Photoelectronic Smoke/Heat Detector with5808 Photoelectronic Smoke/Heat Detector with
5808 Photoelectronic Smoke/Heat Detector with5808 Photoelectronic Smoke/Heat Detector with
5808 Photoelectronic Smoke/Heat Detector with
Built-inBuilt-in
Built-inBuilt-in
Built-inWirelessWireless
WirelessWireless
WirelessTT
TT
Transmitter Installation Instructionsransmitter Installation Instructions
ransmitter Installation Instructionsransmitter Installation Instructions
ransmitter Installation Instructions
SPECIFICATIONSSPECIFICATIONS
SPECIFICATIONSSPECIFICATIONS
SPECIFICATIONS
Power Source: Two 3-volt CR123A Lithium Batteries (included). (Replace with Duracell DL123A, Sanyo
CR123A, Panasonic CR123A, ADEMCO 466, or Varta CR123A.)
Maintenance Limits (Maintenance signal
is activated at either smoke level): Hot Sensitivity: 0.65% ± 0.15% per foot
Cold Sensitivity: less than 6% per foot
Height: 2.5 inches (14 cm)
Diameter: 5.5 inches (64 mm)
Weight: 0.7 lb. (310 g)
Operating Ambient Temperature Range: 4.4° to 37.8° C (40° to 100° F)
Operating Humidity Range: 5% to 95% Relative Humidity
Heat Sensor: 135° F Fixed Temperature Electronic Thermistors
Agency Listings: UL 217; UL 268 – Residential, Commercial Installations
ADEMCO ONE-YEAR LIMITED WARRANTYADEMCO ONE-YEAR LIMITED WARRANTY
ADEMCO ONE-YEAR LIMITED WARRANTYADEMCO ONE-YEAR LIMITED WARRANTY
ADEMCO ONE-YEAR LIMITED WARRANTY
AlarmDevice Manufacturing Company,aDivision of PittwayCorporation
(“Seller”), 165 Eileen Way, Syosset, NY 11791, warrants its security
equipment (the “product”) to be free from defects in materials and
workmanship for one year from date of original purchase, under normal
use and service. Seller’s obligation is limited to repairing or replacing, at
itsoption,freeofchargeforparts,labor,ortransportation,anypartproven
tobedefectiveinmaterialsorworkmanshipundernormaluseandservice.
Sellershallhavenoobligationunderthiswarrantyotherwiseiftheproduct
is altered or improperly repaired or serviced by anyone other than the
seller. In case of defect, contact the security professional who installed
and maintains your security system or the Seller for product repair.
This one year Limited Warranty is in lieu of all other express warranties,
obligations, or liabilities. THERE ARE NO EXPRESS WARRANTIES
WHICH EXTEND BEYOND THE FACE HEREOF. ALL IMPLIED WAR-
RANTIES, OBLIGATIONS, OR LIABILITIES MADE BY SELLER IN
CONNECTION WITH THIS PRODUCT, INCLUDING ANY IMPLIED
WARRANTYOFMERCHANTABILITY,ORFITNESSFORAPARTICU-
LAR PURPOSE OR OTHERWISE, ARE LIMITED IN DURATION TO A
PERIODOF ONEYEAR FROMTHEDATE OFORIGINAL PURCHASE.
ANY ACTION OR BREACH OF ANY WARRANTY, INCLUDING BUT
NOTLIMITEDTOANYIMPLIEDWARRANTYOFMERCHANTABILITY,
MUST BE BROUGHT WITHIN 18 MONTHS OF DATE OF ORIGINAL
PURCHASE. IN NO CASE SHALL SELLER BE LIABLE TO ANYONE
FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR
BREACH OF THIS OR ANY OTHER WARRANTY, EXPRESS OR
IMPLIED, OR UPON ANY OTHER BASIS OF LIABILITY WHATSO-
EVER,EVENIFTHELOSSORDAMAGEISCAUSEDBYTHESELLER’S
OWNNEGLIGENCE ORFAULT. Somestates donotallowlimitationson
how long an implied warranty lasts or the exclusion of incidental or
consequential damages, so above limitation or exclusion may not apply
to you.
Seller does not represent that the product may not be compromised or
circumvented;thattheproductwillpreventanypersonalinjuryorproperty
loss by burglary, robbery, fire or otherwise; or that the product will in all
cases provide adequate warning or protection. Buyer understands that a
properly installed and maintained alarm my only reduce the risk of a
burglary,robbery, or fire occurring without providing analarm,but it is not
insurance or a guarantee that such will not occur or that there will be no
personal injury or property loss as a result. CONSEQUENTLY, SELLER
SHALL HAVE NO LIABILITY FOR ANY PERSONAL INJURY, PROP-
ERTY DAMAGE, OR OTHER LOSS BASED ON A CLAIM THAT THE
PRODUCTFAILEDTOGIVEWARNING.However,ifsellerisheldliable,
whether directly or indirectly, for any loss or damage arising under this
Limited Warranty or otherwise, regardless of cause or origin, Seller’s
maximum liability shall not in any case exceed the purchase price of the
product, and shall be the complete and exclusive remedy against Seller.
Thiswarrantygivesyouspecificlegalrights, andyoumay alsohaveother
rights which vary from state to state. No increase or alteration, written or
verbal, to this warranty is authorized.
In general, detectors cannot be expected to provide warnings for fires
resulting from inadequate fire protection practices, violent explosions,
escaping gases that ignite, improper storage of flammable liquids like
cleaningsolventsthatignite,othersimilarsafetyhazards,arson,smoking
in bed, children playing with matches or lighters, etc. Smoke detectors
used in high air velocity conditions may have a delay in alarm due to
dilution of smoke densities created by frequent and rapid air exchanges.
Additionally, high air velocity environments may create increased dust
contamination, demanding more frequent detector maintenance.
To keep your equipment in excellent working order, ongoing mainte-
nanceis required per the manufacturer’srecommendations and UL and
NFPAstandards. Ata minimum,the requirementsof Chapter7 ofNFPA
72, the National Fire Alarm Code, shall be followed. A preventative
maintenance agreement should be arranged through the local
manufacturer’s representative. Though smoke detectors are designed
for long life, they may fail at any time. Any smoke detector, fire alarm
equipment,oranycomponentofthatsystemwhichfailsshallberepaired
or replaced as soon as possible.
NOTE: Before removing the detector, notify the proper authorities
that the smoke detector system is undergoing maintenance
and will be out of service. Disable the zone or system under-
going maintenance to prevent unwanted alarms.
1. Remove the detector cover by placing a small-bladed screwdriver in
the cover removal slot and twisting it slightly until the cover can be
turned counterclockwise for removal.
2. Removethescreenbypullingitstraightout(seeFigure8).Vacuumthe
screenthoroughly.
3. Clean the black vaned chamber piece by vacuuming or blowing out
dust and particles.
4. Toreinstall thescreen,rotate thescreen on thehousing until itdrops
into the alignment slots. Carefully push the screen onto the base,
making sure it fits tightly to the chamber. Replacement screens are
available (order part number RS23).
5. Replace the cover by rotating it clockwise until it locks in place.
6. Reinstallthedetectorintothesystem, enable system operation, and
notify the proper authorities that the system is back on line.
For use with QED control panel ONLY!
R
Previous Menu
HORIZONTAL
DISTANCE
FROM PEAK
3 FEET
(.9M)
Figure4. Recommendedsmoke detector locationin rooms
withsloped,gabledorpeakedceilings. A78-1171-05
WhereSmokeDetectorsShouldNOTBeInstalled
• Inor near areaswhere combustion particlesare normally present
suchaskitchens;ingarageswherethereareparticlesofcombustion
invehicle exhausts;near furnaces, hot water heaters, or gas space
heaters. Install detectors at least 20 feet (6 meters) away from
kitchens and other areas where combustion particles are nor-
mally present.
• On the ceiling in rooms next to kitchens where there is no transom
between the kitchen and these rooms. Instead, install the smoke
detectoronaninsidewall,furthest from the kitchen (See Figure 5). Be
surenot toinstall smokedetectors within4"oftheceiling orany corner
or more than 6" from the ceiling.
CORRECT
AIR RETURN
BEDROOM
BATH
BEDROOM
LIVING
ROOM
INCORRECT
KITCHEN
STOVE
AIR INLET
78-1171-06
Figure 5. Recommended smoke detector locations
to avoid air streams with combustion particles
• In damp or very humid areas, or next to bathrooms with showers.
The moisture in humid air can enter the sensing chamber as water
vapor, then cool and condense into droplets that cause a nuisance
alarm. Install detectors at least 5 feet (1.5 meters) away from
bathrooms.
• In very cold or very hot rooms or areas. Operating temperature of
the smoke detector is 40°F to 100°F (4°C to 38°C).
• In dusty, dirty, or insect-infested areas. Dust and dirt can build up
onthedetector’s sensingchamberandmakeit overlysensitive,orcan
block openings to the sensing chamber and keep the detector from
sensing smoke.
•Near fresh air inlets or returns or excessively drafty areas. Air
conditioners, heaters, fans, and fresh air intakes and returns can drive
smokeawayfromsmokedetectors,makingthe detectorslesseffective.
• In dead air spaces atthetop of a peakedceilingor wall/ceiling intersect.
Dead air may prevent smoke from reaching a detector.
• Near fluorescent light fixtures. Install detectors at least 10 feet
(3 meters) away from such light fixtures.
WHAT TO DO IN CASE OF FIRE
1. DON’T PANIC — escape may depend on clear thinking.
2. Getoutofthehousefollowingtheplannedescaperoutes,ifpossible.
Do not stop to dress or to collect anything.
3. Open doors carefully only after feeling them to see if they are hot. If
a door is hot, do not open it— follow an alternate escape route.
4. Keepclosetothefloor—smokeandhotgasesrise.Breathethrough
a cloth (wet, if possible) and take short shallow breaths.
5. Keepdoorsandwindowsclosedunless it is necessary to open them
for escape.
6. Meet at your meeting place after leaving your home.
7. Call the local fire department as soon as possible from outside
the home.
8. Never re-enter a burning building.
For more information about fire safety, contact your local fire depart-
SMOKE DETECTOR LIMITATIONS
• Smoke detectors will not sense a fire if the smoke does not reach the
sensor or if the air temperature does not reach 135° F. In order for a
smoke detector to sense smoke, it must be installed in the immediate
vicinity of the fire. In addition, smoke from fires in chimneys, in walls, on
roofs, in remote parts of the building, or on another level from where the
smoke detector is located, may not reach the smoke detector quickly
enough for occupants to escape unharmed. For this reason, installer
shall install smoke detectors on every level, in every sleeping area,
and in every bedroom of the household.
• Smoke detectors may not be heard. The alarm horn in this smoke
detector meets or exceeds current Underwriter's Laboratories standards.
However, if the smoke detector is not located in the same room as the
occupant,orifitisblockedby a closeddoorornormalnoise,thealarmhorn
may not be heard. In addition, sound sleepers, or persons who are under
the influence of drugs or alcohol may not hear the alarm or be able to react
toit.Therefore,locatethissmokedetector,whichhas a sounder rated
at 85 dB at 10 feet, on every level, in every sleeping area, and in every
bedroom of the household.
• In general, detectors may not always warn you about fires caused by
carelessness and safety hazards like smoking in bed, violent explosions,
escaping gas, improper storage of flammable materials, overloaded elec-
trical circuits, children playing with matches, or arson.
• Smoke detectors are not fool-proof. Like all electronic devices, smoke
detectors have limitations. No type of smoke detector can sense every
kind of fire every time. In addition, smoke from slow, smoldering fires
rises slowly and may not reach the smoke detector until actual flame
breaksout.Thistypeofsmoke maynotreachthe smokedetectorintime
for occupants to escape unharmed.
• Smoke detectors are not a substitute for life or property insurance.
Thoughsmokedetectorshavebeenresponsibleforsavingmanylives,they
arenotwarrantedorimpliedtoprotectlivesorpropertyintheeventofafire.
•To keep your equipment in excellent working order, ongoing maintenance
is required per the manufacturer’s recommendations and UL and NFPA
standards. At a minimum, the requirements of Chapter 7 of NFPA 72, the
National Fire Alarm Code, shall be followed. A preventative maintenance
agreementshould be arrangedthrough thelocal manufacturer’s represen-
tative. Though smoke detectors are designed for long life, they may fail at
any time. Any smoke detector, fire alarm equipment, or any component of
that system which fails shall be repaired or replaced as soon as possible.
Where to Install Smoke Detectors
Warning: As a minimum requirement, smoke detectors must be in-
stalled in accordance with the National Fire Protection Agency (NFPA)
Standard 72, Chapter 5, which defines the standards for the National
Fire Alarm Code (National Fire Protection Association, Batterymarch
Park, MA 02269-9101). In addition, observe all local and national
building and electrical codes.
Recommended Smoke Detector Locations:
DINING ROOM KITCHEN BEDROOM BEDROOM
BEDROOMLIVING ROOM
SMOKE DETECTORS FOR MINIMUM PROTECTION
SMOKE DETECTORS FOR MORE PROTECTION AND
REQUIRED IN NEW CONSTRUCTION
A78-1171-01
Figure 2. Single-floor residence with only one sleeping area
BEDROOM
SMOKE DETECTORS FOR
MINIMUM PROTECTION
SMOKE DETECTORS FOR
MORE PROTECTION AND
REQUIRED IN NEW CONSTRUCTION
BEDROOM
BEDROOM
LIVING ROOM
DINING
ROOM
KITCHENFAMILY ROOM
A78-1171-02
Figure 3. Single-floor residence with more than one sleeping area
ment.Theycansupplymoredetailedinformationaboutmakingyourhome
asfreefromfirehazardsaspossibleandaboutplanningforescapeincase
of fire.
MOUNTING
First, determine the best location for the smoke detector; a location that
provides strong wireless transmission paths and proper smoke detec-
tion. A GOOD TRANSMISSION PATH MUST BE ESTABLISHED
FROM THE PROPOSED MOUNTING LOCATION BEFORE PERMA-
NENTLY INSTALLING THE DETECTOR. To check, perform the test
described in the TESTING TRANSMITTER SIGNAL section of this
manual.Tomountthedetector:
1. Once a suitable location has been determined, install the mounting
bracket on the ceiling or on the wall (if local ordinances permit). Use
the two screws and anchors provided.
2. Prior to mounting the detector to the mounting bracket, the system
must "enroll" the detector's ID. See the PROGRAMMING section for
the steps to follow.
3. Turn the detector in a clockwise direction in the mounting bracket
until it clicks into place.
4. Test the detector immediately after completing the installation (as
describedintheTESTINGsectionofthismanual)andrefertotheQED
controlsystem'sinstructionsforadditionalinformationconcerningthe
useof wireless smokedetectors.
TAMPER SLOT
(DEPRESS TAB
TO REMOVE
DETECTOR)
TAMPER RESISTANT TAB
(CUT OFF SMALL TAB TO
ACTIVATE TAMPER PROOF
FEATURE)
LED
LED
BRACKET INDICATES
POSITION OF LED WHEN
DETECTOR IS INSTALLED
Figure 6. Detector Mounting Bracket
Figure 7. Mount Detector Across Ceiling Panel Support
CAUTION
DO NOT attach the detector to removable ceiling panels. Attach the
detector across panel support as shown in Figure 7.
TAMPER PROTECTION
Thisdetectorhasabuilt-intamperswitchthatwillcauseaCHECKsignal
to be displayed at the console of the detector if it is removed from its
installationbracket.Themountingbracketcanalsobemadetamperproof
by breaking off the smaller tab at the scribed line (see Figure 6), thus
preventing removal of the detector without a tool. To remove the
detector, use a small screwdriver to depress the tamperproof tab and
turn the detector counterclockwise.
TESTING
NOTE: Before testing, notify the proper authorities that the smoke
detector system is undergoing maintenance and will tempo-
rarilybeoutofservice.Disablethezoneorsystemundergoing
maintenance to prevent unwanted alarms.
Detectors must be tested after installation and following periodic main-
tenance.The 5808 maybe tested asfollows:
A. TEST SWITCH
1. A recessed test switch is located on the detector housing.
2. Push and hold the recessed test switch with a 0.1" maximum
AD300-00-00 3 I56-918-06AD300-00-00 2 I56-918-06
A78-2333-03
A78-2620-00
diametertool(anallenwrenchorsmallscrewdriver.)
3. TheLEDonthedetectorshouldblinkoncepersecondandthehorn
shouldsoundwithin3seconds.
B. TEST MODULE (Model No. MOD400R)
The MOD400R test module can be used with a DMM or analog
voltmeter to check the detector sensitivity as described in the test
module’s manual.
C. SMOKE ENTRY TEST
Holdasmolderingpunkstickorcottonwickatthesideofthedetector
and gently blow smoke through the detector until the unit alarms.
D. DIRECT HEAT METHOD (Hair dryer of 1000-1500 watts)
Directtheheattowardeithersidethermistor. Besureto holdtheheat
source about 12 inches from the detector to avoid damage to the
plastic. The detector will reset only after it has time to cool.
Smokedetectiontestingisrecommendedforverifyingsystemprotection
capability.
A detector that fails to activate with any of these tests should first be
cleaned as outlined in this manual's MAINTENANCE section. If the
detector still fails to activate, return for repair.
Notify the proper authorities that the system is back on line.
TESTING TRANSMITTER SIGNAL
NOTE: Remove battery tab before installation.
This test should be performed before installation to determine a strong
communication path with the QED control panel and after installation is
complete. Also, the owner/user should test the unit at least weekly.
1. Activate the wireless system's TEST mode from the console.
2. Depressandholdthesmokedetector'sTESTswitchandthedetector
shouldimmediatelytransmitanalarmsignaltotheQEDcontrolpanel.
Thebuilt-inhornwillstarttosoundabout2.5secondsafterdepressing
thebutton.
3. Thewireless system's consoleshouldemit at least3audible sounds
whenthealarmtransmissionisreceivedandwilldisplaythetransmit-
ting detector's ID number.
4. When the console has received the test signal, release the TEST
switch. The horn will immediately stop and a few seconds later the
detector's ID number will clear from the console display.
5. If the console does not respond as noted, check the polarity of the
batteriesand be sure they are fresh. Ifthisis an initial installation, try
moving the detector to another location that provides proper recep-
tion. Alsobesurethatthedetector'sIDhasbeen"enrolled"bytheQED
controlpanel(seePROGRAMMING).Then,repeatthetest.
6. Turn off the system's TEST mode from the console (security code +
OFF).
MAINTENANCE
REPLACEMENT SCREEN,
ORDER PART NO. RS23
ARROW IS ALIGNED
WITH COVER REMOVAL
SLOT WHEN COVER
IS IN POSITION.
COVER
REMOVAL SLOT
A78-2335-01
Figure 8. Removal of Cover and Screen for Cleaning
HORIZONTAL
DISTANCE
FROM PEAK
3 FEET
(.9M)
Figure4. Recommendedsmoke detector locationin rooms
withsloped,gabledorpeakedceilings. A78-1171-05
WhereSmokeDetectorsShouldNOTBeInstalled
• Inor near areaswhere combustion particlesare normally present
suchaskitchens;ingarageswherethereareparticlesofcombustion
invehicle exhausts;near furnaces, hot water heaters, or gas space
heaters. Install detectors at least 20 feet (6 meters) away from
kitchens and other areas where combustion particles are nor-
mally present.
• On the ceiling in rooms next to kitchens where there is no transom
between the kitchen and these rooms. Instead, install the smoke
detectoronaninsidewall,furthest from the kitchen (See Figure 5). Be
surenot toinstall smokedetectors within4"oftheceiling orany corner
or more than 6" from the ceiling.
CORRECT
AIR RETURN
BEDROOM
BATH
BEDROOM
LIVING
ROOM
INCORRECT
KITCHEN
STOVE
AIR INLET
78-1171-06
Figure 5. Recommended smoke detector locations
to avoid air streams with combustion particles
• In damp or very humid areas, or next to bathrooms with showers.
The moisture in humid air can enter the sensing chamber as water
vapor, then cool and condense into droplets that cause a nuisance
alarm. Install detectors at least 5 feet (1.5 meters) away from
bathrooms.
• In very cold or very hot rooms or areas. Operating temperature of
the smoke detector is 40°F to 100°F (4°C to 38°C).
• In dusty, dirty, or insect-infested areas. Dust and dirt can build up
onthedetector’s sensingchamberandmakeit overlysensitive,orcan
block openings to the sensing chamber and keep the detector from
sensing smoke.
•Near fresh air inlets or returns or excessively drafty areas. Air
conditioners, heaters, fans, and fresh air intakes and returns can drive
smokeawayfromsmokedetectors,makingthe detectorslesseffective.
• In dead air spaces atthetop of a peakedceilingor wall/ceiling intersect.
Dead air may prevent smoke from reaching a detector.
• Near fluorescent light fixtures. Install detectors at least 10 feet
(3 meters) away from such light fixtures.
WHAT TO DO IN CASE OF FIRE
1. DON’T PANIC — escape may depend on clear thinking.
2. Getoutofthehousefollowingtheplannedescaperoutes,ifpossible.
Do not stop to dress or to collect anything.
3. Open doors carefully only after feeling them to see if they are hot. If
a door is hot, do not open it— follow an alternate escape route.
4. Keepclosetothefloor—smokeandhotgasesrise.Breathethrough
a cloth (wet, if possible) and take short shallow breaths.
5. Keepdoorsandwindowsclosedunless it is necessary to open them
for escape.
6. Meet at your meeting place after leaving your home.
7. Call the local fire department as soon as possible from outside
the home.
8. Never re-enter a burning building.
For more information about fire safety, contact your local fire depart-
SMOKE DETECTOR LIMITATIONS
• Smoke detectors will not sense a fire if the smoke does not reach the
sensor or if the air temperature does not reach 135° F. In order for a
smoke detector to sense smoke, it must be installed in the immediate
vicinity of the fire. In addition, smoke from fires in chimneys, in walls, on
roofs, in remote parts of the building, or on another level from where the
smoke detector is located, may not reach the smoke detector quickly
enough for occupants to escape unharmed. For this reason, installer
shall install smoke detectors on every level, in every sleeping area,
and in every bedroom of the household.
• Smoke detectors may not be heard. The alarm horn in this smoke
detector meets or exceeds current Underwriter's Laboratories standards.
However, if the smoke detector is not located in the same room as the
occupant,orifitisblockedby a closeddoorornormalnoise,thealarmhorn
may not be heard. In addition, sound sleepers, or persons who are under
the influence of drugs or alcohol may not hear the alarm or be able to react
toit.Therefore,locatethissmokedetector,whichhas a sounder rated
at 85 dB at 10 feet, on every level, in every sleeping area, and in every
bedroom of the household.
• In general, detectors may not always warn you about fires caused by
carelessness and safety hazards like smoking in bed, violent explosions,
escaping gas, improper storage of flammable materials, overloaded elec-
trical circuits, children playing with matches, or arson.
• Smoke detectors are not fool-proof. Like all electronic devices, smoke
detectors have limitations. No type of smoke detector can sense every
kind of fire every time. In addition, smoke from slow, smoldering fires
rises slowly and may not reach the smoke detector until actual flame
breaksout.Thistypeofsmoke maynotreachthe smokedetectorintime
for occupants to escape unharmed.
• Smoke detectors are not a substitute for life or property insurance.
Thoughsmokedetectorshavebeenresponsibleforsavingmanylives,they
arenotwarrantedorimpliedtoprotectlivesorpropertyintheeventofafire.
•To keep your equipment in excellent working order, ongoing maintenance
is required per the manufacturer’s recommendations and UL and NFPA
standards. At a minimum, the requirements of Chapter 7 of NFPA 72, the
National Fire Alarm Code, shall be followed. A preventative maintenance
agreementshould be arrangedthrough thelocal manufacturer’s represen-
tative. Though smoke detectors are designed for long life, they may fail at
any time. Any smoke detector, fire alarm equipment, or any component of
that system which fails shall be repaired or replaced as soon as possible.
Where to Install Smoke Detectors
Warning: As a minimum requirement, smoke detectors must be in-
stalled in accordance with the National Fire Protection Agency (NFPA)
Standard 72, Chapter 5, which defines the standards for the National
Fire Alarm Code (National Fire Protection Association, Batterymarch
Park, MA 02269-9101). In addition, observe all local and national
building and electrical codes.
Recommended Smoke Detector Locations:
DINING ROOM KITCHEN BEDROOM BEDROOM
BEDROOMLIVING ROOM
SMOKE DETECTORS FOR MINIMUM PROTECTION
SMOKE DETECTORS FOR MORE PROTECTION AND
REQUIRED IN NEW CONSTRUCTION
A78-1171-01
Figure 2. Single-floor residence with only one sleeping area
BEDROOM
SMOKE DETECTORS FOR
MINIMUM PROTECTION
SMOKE DETECTORS FOR
MORE PROTECTION AND
REQUIRED IN NEW CONSTRUCTION
BEDROOM
BEDROOM
LIVING ROOM
DINING
ROOM
KITCHENFAMILY ROOM
A78-1171-02
Figure 3. Single-floor residence with more than one sleeping area
ment.Theycansupplymoredetailedinformationaboutmakingyourhome
asfreefromfirehazardsaspossibleandaboutplanningforescapeincase
of fire.
MOUNTING
First, determine the best location for the smoke detector; a location that
provides strong wireless transmission paths and proper smoke detec-
tion. A GOOD TRANSMISSION PATH MUST BE ESTABLISHED
FROM THE PROPOSED MOUNTING LOCATION BEFORE PERMA-
NENTLY INSTALLING THE DETECTOR. To check, perform the test
described in the TESTING TRANSMITTER SIGNAL section of this
manual.Tomountthedetector:
1. Once a suitable location has been determined, install the mounting
bracket on the ceiling or on the wall (if local ordinances permit). Use
the two screws and anchors provided.
2. Prior to mounting the detector to the mounting bracket, the system
must "enroll" the detector's ID. See the PROGRAMMING section for
the steps to follow.
3. Turn the detector in a clockwise direction in the mounting bracket
until it clicks into place.
4. Test the detector immediately after completing the installation (as
describedintheTESTINGsectionofthismanual)andrefertotheQED
controlsystem'sinstructionsforadditionalinformationconcerningthe
useof wireless smokedetectors.
TAMPER SLOT
(DEPRESS TAB
TO REMOVE
DETECTOR)
TAMPER RESISTANT TAB
(CUT OFF SMALL TAB TO
ACTIVATE TAMPER PROOF
FEATURE)
LED
LED
BRACKET INDICATES
POSITION OF LED WHEN
DETECTOR IS INSTALLED
Figure 6. Detector Mounting Bracket
Figure 7. Mount Detector Across Ceiling Panel Support
CAUTION
DO NOT attach the detector to removable ceiling panels. Attach the
detector across panel support as shown in Figure 7.
TAMPER PROTECTION
Thisdetectorhasabuilt-intamperswitchthatwillcauseaCHECKsignal
to be displayed at the console of the detector if it is removed from its
installationbracket.Themountingbracketcanalsobemadetamperproof
by breaking off the smaller tab at the scribed line (see Figure 6), thus
preventing removal of the detector without a tool. To remove the
detector, use a small screwdriver to depress the tamperproof tab and
turn the detector counterclockwise.
TESTING
NOTE: Before testing, notify the proper authorities that the smoke
detector system is undergoing maintenance and will tempo-
rarilybeoutofservice.Disablethezoneorsystemundergoing
maintenance to prevent unwanted alarms.
Detectors must be tested after installation and following periodic main-
tenance.The 5808 maybe tested asfollows:
A. TEST SWITCH
1. A recessed test switch is located on the detector housing.
2. Push and hold the recessed test switch with a 0.1" maximum
AD300-00-00 3 I56-918-06AD300-00-00 2 I56-918-06
A78-2333-03
A78-2620-00
diametertool(anallenwrenchorsmallscrewdriver.)
3. TheLEDonthedetectorshouldblinkoncepersecondandthehorn
shouldsoundwithin3seconds.
B. TEST MODULE (Model No. MOD400R)
The MOD400R test module can be used with a DMM or analog
voltmeter to check the detector sensitivity as described in the test
module’s manual.
C. SMOKE ENTRY TEST
Holdasmolderingpunkstickorcottonwickatthesideofthedetector
and gently blow smoke through the detector until the unit alarms.
D. DIRECT HEAT METHOD (Hair dryer of 1000-1500 watts)
Directtheheattowardeithersidethermistor. Besureto holdtheheat
source about 12 inches from the detector to avoid damage to the
plastic. The detector will reset only after it has time to cool.
Smokedetectiontestingisrecommendedforverifyingsystemprotection
capability.
A detector that fails to activate with any of these tests should first be
cleaned as outlined in this manual's MAINTENANCE section. If the
detector still fails to activate, return for repair.
Notify the proper authorities that the system is back on line.
TESTING TRANSMITTER SIGNAL
NOTE: Remove battery tab before installation.
This test should be performed before installation to determine a strong
communication path with the QED control panel and after installation is
complete. Also, the owner/user should test the unit at least weekly.
1. Activate the wireless system's TEST mode from the console.
2. Depressandholdthesmokedetector'sTESTswitchandthedetector
shouldimmediatelytransmitanalarmsignaltotheQEDcontrolpanel.
Thebuilt-inhornwillstarttosoundabout2.5secondsafterdepressing
thebutton.
3. Thewireless system's consoleshouldemit at least3audible sounds
whenthealarmtransmissionisreceivedandwilldisplaythetransmit-
ting detector's ID number.
4. When the console has received the test signal, release the TEST
switch. The horn will immediately stop and a few seconds later the
detector's ID number will clear from the console display.
5. If the console does not respond as noted, check the polarity of the
batteriesand be sure they are fresh. Ifthisis an initial installation, try
moving the detector to another location that provides proper recep-
tion. Alsobesurethatthedetector'sIDhasbeen"enrolled"bytheQED
controlpanel(seePROGRAMMING).Then,repeatthetest.
6. Turn off the system's TEST mode from the console (security code +
OFF).
MAINTENANCE
REPLACEMENT SCREEN,
ORDER PART NO. RS23
ARROW IS ALIGNED
WITH COVER REMOVAL
SLOT WHEN COVER
IS IN POSITION.
COVER
REMOVAL SLOT
A78-2335-01
Figure 8. Removal of Cover and Screen for Cleaning
fi
Toreplacebatteries:
1. Removethedetectorfromitsmountingplatebytwistingthedetectorcounter-
clockwise.Removebatteries,ifreplacing,anddispose properly.
2. Installtwonew3-voltCR123ALithiumbatteriesinthebatterycompart-
ment. Followthepolaritydiagraminsidethecompartment.
3. Reinstall the smoke detector onto the mounting plate by turning the
detector clockwise.
4. Test the detector as described in the TESTING TRANSMITTER SIG-
NAL section of this manual. The LED should flash about once every 40
seconds to indicate normal operation. If the batteries are not installed
correctly, the smoke detector will not operate and the batteries may be
damaged.Ifthedetectordoesnotappeartobesendingasignalduring
anyofthetests,checkforcorrectbatteryinstallation.
Test Module
Port
Indicator Light
Pulsing: Normal/Thermal Alarm
Fast Blink: Smoke Alarm
None: Call for Service
Test Switch
Figure1. 5808Wireless Smoke/ Heat Detector
PROGRAMMING
Thesmokedetector’sIDmustbeenrolledintheQEDcontrolpanelduring
installationofthesystem.TheQEDcontrolpanelshouldbeprogrammed
toenrollthe 5808asan“RF”unit(mustbeprogrammedas“supervisedRF”
for UL installations). Put the QED control panel in the program
mingmodeand performthefollowing:
With the QED control panel, program the detector as loop 1 and either
manuallyentertheserialnumberthatisonthelabelofthe 5808,orpress
thetestswitchtocauseatransmission. Additionaltransmissionswillcause
the“Confirm”display toappearonthekeypad display.
SeetheQEDcontrolunit’sinstallationinstructionsforfurtherdetails.
Beforeinstallingdetectors,pleasethoroughlyreadtheseinstallationinstruc-
tionsandManualI56-407,
GuideforProperUseofSystemSmokeDetectors,
whichprovidesdetailedinformationondetectorspacing,placement,zoning,
wiring, and special applications. Copies of this manual are available from
ADEMCO.
NOTICE:Thismanualshouldbeleftwiththeowner/userofthisequipment.
IMPORTANT:Thisdetectormustbetestedandmaintainedregularlyfollowing
NFPA72requirements.Thedetectorshouldbecleanedatleastonceayear.
WARNING: Do not use the maintenance signal as an indication that the
detectorhasreachedthelimitsofitsnominalsensitivityrange.Maintenance
onlyindicatesthatthedetectormayneedcleaningorcannolongerrespond
to smoke and shall not be used as a sensitivity indicating means.
GENERAL DESCRIPTION
The5808photoelectronicsmoke/heatdetectorwithbuilt-inwirelesstransmit-
ter is intended for use with wireless alarm systems that support QED 5800
seriesdevices.RefertoQEDcontrolcommunicatorinstallationinstructions
forcompatibility.The 5808smoke/heatdetectorcanbeusedwith5881series
(L,M,H)and5881EHreceiversforresidentialinstallations.The 5808smoke/
heatdetectorcanbeusedwiththe5881EHreceiverforcommercialinstalla-
tions. The transmitter can send alarm, tamper, maintenance (when QED
control panels are equipped to process maintenance signals), and battery
conditionmessagestotheQEDsystem'sreceiver. Themaintenancesignal
willeitherindicatethatthephotochamberrequirescleaningorthatthedetector
can no longer respond to smoke and may need replacement. Refer to the
wirelesssystem'sinstructionsforthemaximumnumberoftransmittersthatcan
besupported.
The 5808soundsitsbuilt-in hornwhensmokereachesthedetector(the
LEDalsoflashesrapidly)orwhentheairtemperaturereaches135°F(the
LEDflashesnormally,aboutonceevery40seconds).Amessageisalso
senttothewirelessQEDcontrolpanelandthesmokedetector'sIDnumber
is displayed at the console. The alarm message is transmitted every 4
secondsuntilthesmokeconditionhasclearedandthedetectorhasreset.
About1secondafterthehornstops,aRESTOREmessageistransmitted
totheQEDcontrolpanelandtheIDnumbercanbeclearedfromthepanel.
Duringnormal,maintenance,andlowbatteryconditions,theLEDflashes
approximatelyonceevery40seconds.
BATTERY INSTALLATION AND REPLACEMENT
The5808ispoweredbytwo3-voltCR123AorDL123ALithiumbatteries
(included).ThedetectorchecksforlowbatteriesateverynormalLEDflash.
Ifalowbatteryisdetected,thetransmittersendsalowbatterymessageto
theQED control panel,whichbeeps and displaysthedetector's ID. This
conditionwillexistfor a minimum of seven days, and then the detector's
hornwill"chirp"aboutevery40seconds.Thebatteriesshouldbereplaced
BEFOREthechirpsbegin.BESURETOREPLACEBOTHBATTERIES
WITH FRESH ONES.
AD300-00-00 I56-918-06
ADEMCO, 165 Eileen Way, Syosset, New York 11791
AD300-00-00 4 I56-918-06
© ADEMCO 1998
WARNING
LIMITATIONS OF SMOKE DETECTORS/TRANSMITTERS
This smoke detector is designed to activate and initiateactivate and initiate
activate and initiateactivate and initiate
activate and initiate emergency
action, but will do so only when used in conjunction with an authorized
fire alarm system. This detector must be installed in accordance with
NFPA standard 72..
..
.
Smoke detectors will not work without power.Smoke detectors will not work without power.
Smoke detectors will not work without power.Smoke detectors will not work without power.
Smoke detectors will not work without power. AC or DC powered
smokedetectorswillnotworkifthepowersupplyiscutoffforanyreason.
Alarm signal sent by the wireless transmitter in this detector may be
blocked or reflected by metal before reaching the alarm receiver. Even
if the signal path has been recently checked, blockage can occur if a
metal object is moved into the path.
Smokedetectorswillnotsensefires whichstartwheresmokedoesSmokedetectorswillnotsensefires whichstartwheresmokedoes
Smokedetectorswillnotsensefires whichstartwheresmokedoesSmokedetectorswillnotsensefires whichstartwheresmokedoes
Smokedetectorswillnotsensefires whichstartwheresmokedoes
notreachthedetectors.notreachthedetectors.
notreachthedetectors.notreachthedetectors.
notreachthedetectors. Smolderingfirestypicallydonotgeneratealot
ofheatwhichisneededtodrivesmokeuptotheceilingwherethesmoke
detectoris usually located.Forthis reason, theremay be largedelaysin
detecting a smoldering fire with either an ionization-type detector or a
photoelectric-type detector. Either one of them may alarm only after
flaming has initiated, which will generate the heat needed to drive the
smoke to the ceiling.
Smoke from fires in chimneys, in walls, on roofs, or on the other side of
aclosed doormaynot reachthe smoke detectorand alarm it.A detector
cannot quickly detect, or sense at all, a fire developing on another level
ofabuilding.Alarmwarningdevices,such asbellor horns,maynotalert
peopleorwakeupsleepersiftheyarelocatedontheothersideofclosed
or partly open doors, or on another level. Persons may not hear a
warning device over the noise levels of a radio, air conditioner or other
appliances, or traffic. For this reason, detectors shall be located ondetectors shall be located on
detectors shall be located ondetectors shall be located on
detectors shall be located on
every level and in every bedroom within a building.every level and in every bedroom within a building.
every level and in every bedroom within a building.every level and in every bedroom within a building.
every level and in every bedroom within a building. Alarm warning
devices,howeverloud,maynotwarnhearing-impairedpeopleorwaken
deep sleepers.
Smoke detectors shall be located in any room where an alarmSmoke detectors shall be located in any room where an alarm
Smoke detectors shall be located in any room where an alarmSmoke detectors shall be located in any room where an alarm
Smoke detectors shall be located in any room where an alarm
control is located, or in any room where alarm control connectionscontrol is located, or in any room where alarm control connections
control is located, or in any room where alarm control connectionscontrol is located, or in any room where alarm control connections
control is located, or in any room where alarm control connections
to an AC source or phone lines are made.to an AC source or phone lines are made.
to an AC source or phone lines are made.to an AC source or phone lines are made.
to an AC source or phone lines are made. If detectors are not so
located, a fire within any of these rooms could prevent the QED control
from reporting a fire.
Smoke detectors have sensing limitations, too.Smoke detectors have sensing limitations, too.
Smoke detectors have sensing limitations, too.Smoke detectors have sensing limitations, too.
Smoke detectors have sensing limitations, too. Ionization detectors
and photoelectronic detectors are required to pass fire tests of the
flaming and smoldering types. This is to ensure that both can detect a
wide range of fires. Ionization detectors offer a broad range of fire-
sensing capability, but they are somewhat better at detecting fast-
flamingfiresthanslow-smolderingfires.Photoelectronicdetectorssense
smolderingfires better than flaming fires,which have little, if any,visible
smoke.Becausefiresdevelopindifferentways,andareoftenunpredict-
able in their growth, neither type of detector is always best, and a given
detector may not always provide early warning of a specific type of fire.
A78-2332-01
5808 Photoelectronic Smoke/Heat Detector with5808 Photoelectronic Smoke/Heat Detector with
5808 Photoelectronic Smoke/Heat Detector with5808 Photoelectronic Smoke/Heat Detector with
5808 Photoelectronic Smoke/Heat Detector with
Built-inBuilt-in
Built-inBuilt-in
Built-inWirelessWireless
WirelessWireless
WirelessTT
TT
Transmitter Installation Instructionsransmitter Installation Instructions
ransmitter Installation Instructionsransmitter Installation Instructions
ransmitter Installation Instructions
SPECIFICATIONSSPECIFICATIONS
SPECIFICATIONSSPECIFICATIONS
SPECIFICATIONS
Power Source: Two 3-volt CR123A Lithium Batteries (included). (Replace with Duracell DL123A, Sanyo
CR123A, Panasonic CR123A, ADEMCO 466, or Varta CR123A.)
Maintenance Limits (Maintenance signal
is activated at either smoke level): Hot Sensitivity: 0.65% ± 0.15% per foot
Cold Sensitivity: less than 6% per foot
Height: 2.5 inches (14 cm)
Diameter: 5.5 inches (64 mm)
Weight: 0.7 lb. (310 g)
Operating Ambient Temperature Range: 4.4° to 37.8° C (40° to 100° F)
Operating Humidity Range: 5% to 95% Relative Humidity
Heat Sensor: 135° F Fixed Temperature Electronic Thermistors
Agency Listings: UL 217; UL 268 – Residential, Commercial Installations
ADEMCO ONE-YEAR LIMITED WARRANTYADEMCO ONE-YEAR LIMITED WARRANTY
ADEMCO ONE-YEAR LIMITED WARRANTYADEMCO ONE-YEAR LIMITED WARRANTY
ADEMCO ONE-YEAR LIMITED WARRANTY
AlarmDevice Manufacturing Company,aDivision of PittwayCorporation
(“Seller”), 165 Eileen Way, Syosset, NY 11791, warrants its security
equipment (the “product”) to be free from defects in materials and
workmanship for one year from date of original purchase, under normal
use and service. Seller’s obligation is limited to repairing or replacing, at
itsoption,freeofchargeforparts,labor,ortransportation,anypartproven
tobedefectiveinmaterialsorworkmanshipundernormaluseandservice.
Sellershallhavenoobligationunderthiswarrantyotherwiseiftheproduct
is altered or improperly repaired or serviced by anyone other than the
seller. In case of defect, contact the security professional who installed
and maintains your security system or the Seller for product repair.
This one year Limited Warranty is in lieu of all other express warranties,
obligations, or liabilities. THERE ARE NO EXPRESS WARRANTIES
WHICH EXTEND BEYOND THE FACE HEREOF. ALL IMPLIED WAR-
RANTIES, OBLIGATIONS, OR LIABILITIES MADE BY SELLER IN
CONNECTION WITH THIS PRODUCT, INCLUDING ANY IMPLIED
WARRANTYOFMERCHANTABILITY,ORFITNESSFORAPARTICU-
LAR PURPOSE OR OTHERWISE, ARE LIMITED IN DURATION TO A
PERIODOF ONEYEAR FROMTHEDATE OFORIGINAL PURCHASE.
ANY ACTION OR BREACH OF ANY WARRANTY, INCLUDING BUT
NOTLIMITEDTOANYIMPLIEDWARRANTYOFMERCHANTABILITY,
MUST BE BROUGHT WITHIN 18 MONTHS OF DATE OF ORIGINAL
PURCHASE. IN NO CASE SHALL SELLER BE LIABLE TO ANYONE
FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR
BREACH OF THIS OR ANY OTHER WARRANTY, EXPRESS OR
IMPLIED, OR UPON ANY OTHER BASIS OF LIABILITY WHATSO-
EVER,EVENIFTHELOSSORDAMAGEISCAUSEDBYTHESELLER’S
OWNNEGLIGENCE ORFAULT. Somestates donotallowlimitationson
how long an implied warranty lasts or the exclusion of incidental or
consequential damages, so above limitation or exclusion may not apply
to you.
Seller does not represent that the product may not be compromised or
circumvented;thattheproductwillpreventanypersonalinjuryorproperty
loss by burglary, robbery, fire or otherwise; or that the product will in all
cases provide adequate warning or protection. Buyer understands that a
properly installed and maintained alarm my only reduce the risk of a
burglary,robbery, or fire occurring without providing analarm,but it is not
insurance or a guarantee that such will not occur or that there will be no
personal injury or property loss as a result. CONSEQUENTLY, SELLER
SHALL HAVE NO LIABILITY FOR ANY PERSONAL INJURY, PROP-
ERTY DAMAGE, OR OTHER LOSS BASED ON A CLAIM THAT THE
PRODUCTFAILEDTOGIVEWARNING.However,ifsellerisheldliable,
whether directly or indirectly, for any loss or damage arising under this
Limited Warranty or otherwise, regardless of cause or origin, Seller’s
maximum liability shall not in any case exceed the purchase price of the
product, and shall be the complete and exclusive remedy against Seller.
Thiswarrantygivesyouspecificlegalrights, andyoumay alsohaveother
rights which vary from state to state. No increase or alteration, written or
verbal, to this warranty is authorized.
In general, detectors cannot be expected to provide warnings for fires
resulting from inadequate fire protection practices, violent explosions,
escaping gases that ignite, improper storage of flammable liquids like
cleaningsolventsthatignite,othersimilarsafetyhazards,arson,smoking
in bed, children playing with matches or lighters, etc. Smoke detectors
used in high air velocity conditions may have a delay in alarm due to
dilution of smoke densities created by frequent and rapid air exchanges.
Additionally, high air velocity environments may create increased dust
contamination, demanding more frequent detector maintenance.
To keep your equipment in excellent working order, ongoing mainte-
nanceis required per the manufacturer’srecommendations and UL and
NFPAstandards. Ata minimum,the requirementsof Chapter7 ofNFPA
72, the National Fire Alarm Code, shall be followed. A preventative
maintenance agreement should be arranged through the local
manufacturer’s representative. Though smoke detectors are designed
for long life, they may fail at any time. Any smoke detector, fire alarm
equipment,oranycomponentofthatsystemwhichfailsshallberepaired
or replaced as soon as possible.
NOTE: Before removing the detector, notify the proper authorities
that the smoke detector system is undergoing maintenance
and will be out of service. Disable the zone or system under-
going maintenance to prevent unwanted alarms.
1. Remove the detector cover by placing a small-bladed screwdriver in
the cover removal slot and twisting it slightly until the cover can be
turned counterclockwise for removal.
2. Removethescreenbypullingitstraightout(seeFigure8).Vacuumthe
screenthoroughly.
3. Clean the black vaned chamber piece by vacuuming or blowing out
dust and particles.
4. Toreinstall thescreen,rotate thescreen on thehousing until itdrops
into the alignment slots. Carefully push the screen onto the base,
making sure it fits tightly to the chamber. Replacement screens are
available (order part number RS23).
5. Replace the cover by rotating it clockwise until it locks in place.
6. Reinstallthedetectorintothesystem, enable system operation, and
notify the proper authorities that the system is back on line.
For use with QED control panel ONLY!
R
Previous Menu

Other ADEMCO Smoke Alarm manuals

ADEMCO 4192CPM User manual

ADEMCO

ADEMCO 4192CPM User manual

ADEMCO PY2700TEM User manual

ADEMCO

ADEMCO PY2700TEM User manual

ADEMCO 5707 User manual

ADEMCO

ADEMCO 5707 User manual

ADEMCO 4192CP Instruction Manual

ADEMCO

ADEMCO 4192CP Instruction Manual

ADEMCO 5806 User manual

ADEMCO

ADEMCO 5806 User manual

ADEMCO 5192CP User manual

ADEMCO

ADEMCO 5192CP User manual

ADEMCO 5808LSTA User manual

ADEMCO

ADEMCO 5808LSTA User manual

ADEMCO 5808LST User manual

ADEMCO

ADEMCO 5808LST User manual

ADEMCO 4192 User manual

ADEMCO

ADEMCO 4192 User manual

ADEMCO 5806 User manual

ADEMCO

ADEMCO 5806 User manual

ADEMCO ALERT III User manual

ADEMCO

ADEMCO ALERT III User manual

ADEMCO 5807 User manual

ADEMCO

ADEMCO 5807 User manual

ADEMCO 5808 Series User manual

ADEMCO

ADEMCO 5808 Series User manual

Popular Smoke Alarm manuals by other brands

Simplex 2098-9207 installation instructions

Simplex

Simplex 2098-9207 installation instructions

C-LOGIC 720-SD instruction manual

C-LOGIC

C-LOGIC 720-SD instruction manual

First Alert SA511 user manual

First Alert

First Alert SA511 user manual

Kidde P4010ACSCO-WF-CA user guide

Kidde

Kidde P4010ACSCO-WF-CA user guide

GE FHSD720C Installation and user manual

GE

GE FHSD720C Installation and user manual

Bentel Security FireClass FC400P manual

Bentel Security

Bentel Security FireClass FC400P manual

Potter PAD300-PD quick start guide

Potter

Potter PAD300-PD quick start guide

Mircom RTI-265 installation instructions

Mircom

Mircom RTI-265 installation instructions

Zerio-Plus EDA-R6000 installation instructions

Zerio-Plus

Zerio-Plus EDA-R6000 installation instructions

Kidde HD135F Specification sheet

Kidde

Kidde HD135F Specification sheet

Homewatch PR1211 owner's manual

Homewatch

Homewatch PR1211 owner's manual

NOZE GS529 user manual

NOZE

NOZE GS529 user manual

Lexing LX-SO-215HT instructions

Lexing

Lexing LX-SO-215HT instructions

System Sensor AGILE Application and installation guidelines

System Sensor

System Sensor AGILE Application and installation guidelines

Firex 4480 Specification sheet

Firex

Firex 4480 Specification sheet

UniPOS YKB-02? instruction manual

UniPOS

UniPOS YKB-02? instruction manual

Honeywell TC842B1007 Installation and maintenance instructions

Honeywell

Honeywell TC842B1007 Installation and maintenance instructions

Smartwares ELRO RM142F quick start guide

Smartwares

Smartwares ELRO RM142F quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.