GE FHSD720C User manual

FHSD700C Series
Installation and User Manual
June 2009
Document Number: 16097_01


GE Security FHSD700C Series Product Guide
Document Conventions
The following typographic conventions are used in this document:
Convention Description
Bold Used to denote: emphasis Used for names of menus, menu options, toolbar buttons
Italics Used to denote: references to other parts of this document or other documents. Used
for the result of an action.
The following icons are used in this document:
Convention Description
Caution: This icon is used to indicate that there is a danger to equipment. The danger
could be loss of data, physical damage, or permanent corruption of configuration
details.
Warning: This icon is used to indicate that there is a danger of electric shock. This may
lead to death or permanent injury.
Warning: This icon is used to indicate that there is a danger of inhaling dangerous
substances. This may lead to death or permanent injury.
Contact Us
Please contact your local GE representative, or visit www.gesecurity.net.
www.gesecurity.net i

FHSD700C Series Product Guide GE Security
Codes and Standards Information for Air Sampling Smoke
Detection
We strongly recommend that this document is read in conjunction with the appropriate local codes and standards for smoke
detection and electrical connections. This document contains generic product information and some sections may not comply
with all local codes and standards. In these cases, the local codes and standards must take precedence. The information
below was correct at time of printing but may now be out of date, check with your local codes, standards and listings for the
current restrictions.
FDA
This GE Security product incorporates a 658 nm laser device with an average power less than 10 mW, and is classified as a
Class 1 laser product that complies with FDA regulations 21 CFR 1040 with deviations pursuant to Laser Notice 50, and with
IEC / EN 60825-1. Access to the laser chamber is on the underside of equipment and is restricted by cover. The cover may
only be removed by qualified personnel. The laser emits visible light and can be hazardous if viewed with the naked eye.
CAUTION - Use of controls or adjustments of performance or procedures other than those specified herein may result in
hazardous radiation exposure.
Regional Regulatory Requirements and Notices
UL
For open area protection the Fire 1 alarm threshold (signal) must be set within the limits specified by the following conditions:
FHSD721C / FHSD721DC, FHSD724DC and FHSD726DC detectors must have a Fire 1 threshold set within 0.04 to
0.16% obs/ft
FHSD7215DC detectors must have a Fire 1 threshold set between 0.04 to 0.7% obs/ft
FHSD720C detectors must have a Fire 1 threshold set within 0.04 to 0.29% obs/ft
EN54-20
The product must use a power supply conforming to EN54-4.
The product is compliant with EN54-20 sensitivity requirements provided that the hole sensitivity is better and transport time is
less than the following values:
FHSD720C FHSD721C /
FHSD721DC FHSD724DC FHSD726DC FHSD7215DC
Class A 0.6% obs/m
60 secs 0.6% obs/m
60 secs 1.5% obs/m
60 secs 1.5% obs/m
60 secs 0.1% obs/m
30 secs
Class B 1.6% obs/m
60 secs 3.6% obs/m
60 secs 4.5% obs/m
60 secs 4.5% obs/m
75 secs 0.1% obs/m
30 secs
Class C 3.6% obs/m
60 secs 10% obs/m
60 secs 10% obs/m
60 secs 10% obs/m
90 secs 1% obs/m
30 secs
The product is compliant with EN54-20 flow monitoring requirements provided that the following conditions are met:
Flow Low and Flow High parameters should be set to 85% and 115% respectively for FHSD720C, FHSD721C /
FHSD721DC, FHSD724DC and FHSD726DC detectors
TRCPRESS parameter should be set to 25 for FHSD7215DC detectors
Additional Information
Class A, B and C detectors passed EN54-20 approvals testing with the following number of holes and detector sensitivities:
FHSD720C FHSD721C /
FHSD721DC FHSD724DC FHSD726DC FHSD7215DC
Class A 12 holes
0.04% obs/m 16 holes
0.04% obs/m 20 holes
0.05% obs/m 30 holes
0.05% obs/m 15 holes
0.1% obs/m
Class B 36 holes
0.04% obs/m 72 holes
0.04% obs/m 48 holes
0.06% obs/m 72 holes
0.06% obs/m 15 holes
0.1% obs/m
Class C 36 holes
0.1% obs/m 72 holes
0.1% obs/m 72 holes
0.1% obs/m 72 holes
0.1% obs/m 15 holes
1.0% obs/m
ii www.gesecurity.net

GE Security FHSD700C Series Product Guide
www.gesecurity.net iii
Approvals
CFE
EN54-20, VdS
CPD
CE EMC
LVD

FHSD700C Series Product Guide GE Security
Table of Contents
1Introduction................................................................................................................................1
1.1 Detector Models.................................................................................................................1
2Principle of Operation...............................................................................................................2
2.1 Flow Monitoring .................................................................................................................2
2.2 Alarms and Trace Mode ....................................................................................................3
2.3 Detector Display Panel......................................................................................................3
3Installation..................................................................................................................................6
3.1 Mounting the Detectors......................................................................................................6
3.2 Cable Connections ............................................................................................................8
3.3 Connection of Sampling Tubes........................................................................................14
3.4 Remote Display Panel.....................................................................................................15
4Starting Up...............................................................................................................................16
4.1 Flow Normalization..........................................................................................................16
5Setup and Button Functionality.............................................................................................18
5.1 Access Codes..................................................................................................................18
5.2 User Functions.................................................................................................................19
5.3 Main Menu Modes...........................................................................................................20
5.4 Input-Output Modules......................................................................................................31
6Maintenance.............................................................................................................................33
6.1 Servicing..........................................................................................................................34
Appendix A: Display Panel Navigation....................................................................................35
Appendix B: Communications Guide.......................................................................................36
B.1 Installation Guide for RS485 Equipment..........................................................................36
Appendix C: Laser Chamber Safety.........................................................................................38
iv www.gesecurity.net

GE Security FHSD700C Series Product Guide
1 Introduction
Welcome to the GE Security FHSD700C Series Product Guide. This document is written to provide you
with information on technical specifications, cabling, and how to install, configure and operate these
detectors.
FHSD700C Series detectors are aspirating smoke detectors that provide early warning of fire by
analyzing air drawn through an air sampling pipe network. A highly sensitive detector chamber is able to
detect smoke at very low concentrations. Embedded and PC software enable the configuration of a
wide range of user defined parameters and reporting capabilities and extended input and output
functionality is achieved through the addition of plug-in modules.
1.1 Detector Models
Detectors in the GE Security FHSD700C range differ in a variety of ways including the number of
sample tube inlets available, ability to provide individual pipe sampling, aspiration system and sample
tube type.
FHSD724DC to FHSD7215DC detectors incorporate a rotary valve as a method of sampling individual
pipes and providing addressability. This unique feature is described in Principle of Operation on page 2.
The two types of aspiration systems used include an internal fan (low pressure system), or an internal
vacuum pump (high pressure system). High pressure systems are capable of drawing air samples down
small bore tubes while low pressure systems use wide-bore rigid sample tubes. Small bore systems are
often preferred when installations need to be unobtrusive.
RS232, RS485 and TCP/IP interfaces enable flexible connectivity options for detector networking,
configuration and monitoring via GE Security Fire System Configuration and Management Software: GE
Security VSC and VSM4. When connected by TCP/IP, the Fire System Management software enables
the configuration and monitoring of a large number of systems by a single PC, which can be accessed
anywhere via any standard internet connection.
The differentiating attributes for the detector models are summarized in the following table.
Table 1-1: Detector Models and Differentiating Factors
Model FHSD720C FHSD721C /
FHSD721DC FHSD724DC FHSD726DC FHSD7215DC
Applicable EN54-20 Classes A / B / C A / B / C A / B / C A / B / C A / B / C
Number of Sample Tubes 2 4 4 6 15
Individual Sampling (rotary valve) No No Yes Yes Yes
Individual Flow Monitoring No Yes Yes Yes Yes
Flow Monitoring System Thermal Pressure
Sample tube inlet diameter 25mm OD 25mm OD 6mm OD / 4mm ID
Aspirator system Fan Pump
Area Coverage 2000m2(VdS)
850m2(UL) 2000m22000m22000m2N/A
Available with Beacon Option No Yes Yes Yes Yes
Ethernet FHSD720NETC
only FHSD721DC only Yes Yes Yes
Note: FHSD7215DC detectors are not designed for open-area coverage. However, for the purpose of
calculating sampling point spacing, the equivalent maximum area coverage is 1500 m2(16 000
ft2).
www.gesecurity.net 1

FHSD700C Series Product Guide GE Security
2 Principle of Operation
Air samples are drawn through the pipe network from the protected area through wide or small bore
pipe systems. Wide bore tubes generally have sampling holes drilled at intervals within the protected
area while small bore tubes normally sample air at their end points.
The aspirator draws air from the pipe network into the detector inlets where the samples are combined,
filtered, and directed to the laser detection chamber. Systems incorporating a rotary valve have an
Overall position which draws air equally from all sectors. In contrast, the FHSD721C / FHSD721DC has
an inlet manifold which combines samples from up to four inlet pipes while the FHSD720C uses a T-
piece of pipe to combine air sampled from two inlet pipes.
All models, except the FHSD720C, have flow monitoring on each inlet. The FHSD720C has flow
monitoring of the combined air-flow. More information on flow monitoring can be found in Section 2.1.
The detection chamber consists of a laser beam directed across an optical chamber, through which the
air sample flows. A photodetector built into the optical chamber measures the amount of light scattering
from particles in the air. A clean air sample will cause very little scattering but as the smoke density of
the sample increases, the amount of light directed onto the photodetector will also increase. The light
signal is processed to become a direct measurement of the amount of obscuration caused by smoke.
Information about the laser chamber can be found in Appendix C.
If the smoke detected is higher than the preset alarm thresholds in the detector (Alert, Action, Fire 1 and
Fire 2), an alarm will be reported. One or more Alarm relays, preset to activate at an alarm threshold will
signal the host panel after a preset time delay. Alarm states are also shown on the display panel, and
an audible warning is given. An optional alarm beacon can also be fitted for all detectors except the
FHSD720C.
Systems with a rotary valve (FHSD724DC to FHSD7215DC) have an additional preset trigger level,
Trace, usually set below the Alert level. When Trace is activated, the rotary valve will sequentially scan
the sectors, in order to determine the source of the event. While in Trace mode, the default levels for
Alert, Action, Fire 1 and Fire 2 are the same as used for Overall monitoring. If required, different levels
for Alert, Action, Fire 1 and Fire 2 may be set for each sector in the Sector Alarms menu. The Overall
alarm levels may also be changed as can all delay times (FHSD720C and FHSD721C / FHSD721DC
only).
2.1 Flow Monitoring
The control system monitors for blockages or disconnection of tubes for each sector by detecting when
the air flow is above or below acceptable flow thresholds. Flow thresholds are dependant on air flows
measured during normalization.
The normalization process enables the detector to learn typical air flow characteristics of the system
and sets these expected flow readings to 100% for each sector. A normalization sequence must be
performed at installation. The detector has default high and low limits and associated delay times, which
may be changed in the Configure menu.
Air flow characteristics of the system are highly dependent on the detector's pipe network. The design of
the pipe network should be considered carefully prior to installing the system.
2 www.gesecurity.net

GE Security FHSD700C Series Product Guide
2.2 Alarms and Trace Mode
The default settings of the four alarm states (Alert, Action, Fire1 and Fire2) and Trace are shown in the
following table. The Trace threshold is only applicable to detectors FHSD724DC to FHSD7215DC,
which have a rotary valve.
Table 2-1: Default Behavior of Alarm States and Trace Mode
Level Latched / Unlatched Threshold Delay Beacon Pulse (On:Off) Sounder
Trace Latched 0.03% obs/m 3 secs - Continuous
Alert Latched 0.04% obs/m 3 secs 0.5 secs : 2 secs Continuous
Action Latched 0.06% obs/m 3 secs 0.5 secs : 1 sec Continuous
Fire1 Latched 0.08% obs/m 3 secs 0.5 secs : 0.5 secs Continuous
Fire2 Latched 0.1% obs/m 3 secs Continuous Continuous
Trace parameters apply when the rotary valve is in the Overall position and all sectors are being
monitored. If latched, the Trace indicator will remain illuminated after the initiating event has ceased. It
does NOT mean that the unit will continue indefinitely in Trace (scan) mode. The system will only
continue in Trace mode if the detected smoke level is above the Trace threshold after scanning. The
Alert relay may be programmed to be activated by the Trace threshold. Its action will then follow that of
the Trace indicator.
If any alarms are unlatched, all resultant actions (relay contacts, display panel indicators, sounder and
beacon) will clear if and when the triggering event ceases. If it is latched, all the warning mechanisms
are maintained until action is taken by the user (please see Detector Display Panel on page 3). These
alarm states are global and will be set depending on the smoke density being measured, regardless of
which sector is being sampled. Once in Trace mode, each sector has an alarm indicator associated with
it. These individual sector alarms pulse progressively, depending on the degree of alarm status, in the
same way as the Beacon (please see Default Behavior of Alarm States and Trace Mode on page 3).
2.3 Detector Display Panel
All FHSD700C detectors (except for the FHSD720C and FHSD721C) can have a full display panel or a
blank panel fitted to the main system. The FHSD720C and FHSD721C have no display but can be
connected to a remote display unit via RS485 communications from the Main I/O module. The display
panel is used for annunciating the detector status and smoke levels, and can also be used to configure
the detector.
The display consists of a range of configuration and control buttons (Item 1 in Figure 2-1) and LEDs to
indicate Alarms, Faults, Power, Reset and other operational status (Items 5 and 6 in Figure 2-1). When
configuring the detector via the display panel, some of these configuration and control buttons will have
a dual function to allow the user to enter parameter values, scroll through configuration items, or enter
an Access Code. Alternate functions are indicated by LEDs located above the buttons (Item 3 in Figure
2-1) and are activated when the associated button can be used for the alternative function.
More information about button functionality, Access Codes and how to setup the detector with the Main
Menu can be found in Setup and Button Functionality on page 18. A flowchart illustrating how to
navigate through the display panel can be found in Appendix A Display Panel Navigation on page 35.
www.gesecurity.net 3

FHSD700C Series Product Guide GE Security
1. Control and Configuration Buttons
2. Status Display
3. Alternate Button Function Indicators
4. Sector, Alarm and Fault Indicators
5. Display LEDs
6. Alert, Action, Fire1 and Fire2 Indicators
7. Logarithmic smoke density bargraph
Figure 2-1: FHSD700C Series Display Panel
The following describe the display panel for the FHSD700C detector.
1. Control and Configuration Buttons
All local user-interface options are done using these buttons.
1. Not used for FHSD700C detectors
2. Menu key
3. Test key
4. Scan / parameter scroll down key
5. Isolate / parameter scroll up key
6. Sounder silence / enter key
7. Reset / value scroll down key
8. Accept / value scroll up key
Figure 2-2: Control and configuration keys
2. Status display
Will normally show the smoke density value. Also used for all Setup and Configure procedures.
3. Alternate button function indicators
When the unit is in a mode accessed by the Main Menu, the five right-most buttons can change to Scroll
and Enter functions.
4. Sector, Alarm and Fault Indicators
Individual Sample, Alarm, and Fault indicators for each sector. The All alarm is the Trace indicator.
4 www.gesecurity.net

GE Security FHSD700C Series Product Guide
5. Display LEDs
Table 2-2: LED Descriptions
LED Description
Power Indicates that the power supply is ON.
If the system processor is faulty, the General Fault, Power and Comms LEDs will be
activated simultaneously.
General Fault The detector has one or more faults, which will also be shown by other specific fault
indicators. The Fault relay contacts always follow the state of this indicator.
Isolated will also show as General Fault.
If the system processor is faulty, the General Fault, Power and Comms LEDs will be
activated simultaneously.
Processor
Reset The processor has been reset
Mains Fault This indicator may activate due to an incorrect device configuration.
To prevent this from occurring, please ensure that Pin 2 and Pin 5 on CN2 are linked. For
more information, please see External Power Supply Connection on page 9.
Flow Fault The flow rate for any sector is outside the bounds set by the High and Low flow limits. All
sectors are normalized by a run-time sequence; on high pressure systems, the pipe lengths
should be balanced.
Battery Fault This indicator may activate due to an incorrect device configuration.
To prevent this from occurring, please ensure that the STANDBY parameter in the
Configuration menu is set to 0. For more information, please see Table 5-4 on page 22.
Aspiration
Fault The rotary valve has a fault.
Detector Fault The laser smoke detector has developed a fault.
Isolated This has been put into Isolated mode when the unit functions normally, but alarm reporting
via the relays is disabled.
Note: General Fault will also be shown.
Comms Fault An element of the internal RS485 communication link or remote display is faulty.
If the system processor is faulty, the General Fault, Power and Comms LEDs will be
activated simultaneously.
Hold Flashes when a manual scan is being performed.
Unlock The Panel is unlocked - meaning that an access code has been entered. It will clear when
normal operation is resumed.
6. Alert, Action, Fire1, and Fire2 Indicators
These operate in tandem with corresponding relays on the I/O board to indicate progressive levels of
smoke and are programmable for obscuration level. The FHSD721C / FHSD721DC and FHSD720C
also enable these indicators to be configured for time delays.
7. Logarithmic smoke density bar graph
Displays 0 to 20 %obs/m with a resolution of 0.01 %obs/m at the lower end (0 - 6.09 %obs/ft).
www.gesecurity.net 5

FHSD700C Series Product Guide GE Security
3 Installation
The units should be installed in accordance with the following installation instructions and in a manner
acceptable to the local Authority Having Jurisdiction (AHJ). The units are also intended to be installed in
accordance with NFPA 72 National Fire Alarm Code.
Warning: Use of controls or adjustments of performance or procedures other than those specified
herein may result in hazardous radiation exposure.
The following steps should be carried out in order to correctly install the system:
1. Securely mount the back box to a suitable wall or support using the three points shown in the
fixing diagrams in Section 3.1. M6 or M8 screws are suitable.
2. Connect the cables for the power supply and any I/O modules. Ferrite cores should be fitted to
the power cable, whether DC or AC.
3. Fit the pipe network to the system. For details on how to design and install a pipe network, refer
to www.gesecurity.net.
3.1 Mounting the Detectors
Careful consideration should be given to the mounting location of the detector unit to ensure that it is:
Positioned at an accessible height to facilitate commissioning, routine testing and maintenance.
Positioned in an area where the exhaust air pipe will remain clear of obstacles at all times.
Not installed above a heat source such as a radiator or in direct air flow source such as Air
Conditioners.
Secure and free from operation by unauthorized personnel.
Figure 3-1: FHSD720C Mounting Diagram and Dimensions
6 www.gesecurity.net

GE Security FHSD700C Series Product Guide
Figure 3-2: FHSD721C / FHSD721DC Mounting Diagram and Dimensions
Figure 3-3: FHSD724DC and FHSD726DC Mounting Diagram and Dimensions
Figure 3-4: FHSD7215DC Mounting Diagram and Dimensions
www.gesecurity.net 7

FHSD700C Series Product Guide GE Security
3.2 Cable Connections
Note: All work carried out on these units should be performed by fully qualified personnel. There are no
user serviceable parts inside.
CAUTION: Before installing or removing batteries or carrying out any work that requires
the removal of any board ensure that the power supply is disconnected.
A fused junction box may be used as an external disconnect device.
3.2.1 FHSD721C / FHSD721DC to FHSD7215DC Main Board Connections
This section describes the power, input / output and communications connections for the FHSD721C /
FHSD721DC to FHSD7215DC detectors and how to access the interfaces for the connections. A
summary of these interfaces is shown in the following table.
Table 3-1: Standard FHSD721C / FHSD721DC to FHSD7215DC Connections
Category Name Description
24 VDC Input 24 VDC power input from external power supply.
For more information, please refer to External Power Supply Connection on
page 9.
Power
Auxiliary 24 VDC
Output 24 VDC power output rated to 1A for powering an external sounder,
addressable I/O devices etc.
Fault Relay Output Activates when a Fault is detected.
Alarm Relay
Outputs Alarm relays for each Alarm level (Alert, Action, Fire 1, Fire 2) that are
activated when the corresponding alarm level is detected.
Input / Output
Remote
Reset/Isolate Input Dual action input for remote reset and isolate.
Remote Reset: Activated by applying 24 VDC.
Remote Isolate: Activated by applying 24 VDC for 8 seconds or more.
Once 24 VDC is removed, the system reverts to normal operation.
The function of this input is programmed in the Setup Menu. More
information can be found in Section 5.3.8 SETUP: Setup Menu on page 29.
RS 485 Enables the following connections:
Connection to a remote Display Panel
Connecting up to 30 detectors on an RS 485 multi-drop network
Connection to a PC with GE Security VSC or VSM4 via a RS232-
RS485 converter.
Ethernet Enables TCP/IP connections to a PC with GE Security VSC or VSM4 via
LAN/WAN.
Note: Not available for the FHSD720C and FHSD721C.
Communications
RS 232 Enables a direct serial connection to a PC with GE Security VSC or VSM4
for configuration and monitoring.
8 www.gesecurity.net

GE Security FHSD700C Series Product Guide
Detector Access
To gain access to the interior of the detector, first isolate the power supply then remove the front cover.
It is secured by two screws underneath and hinged at the top, allowing complete removal. If the beacon
option is fitted, a cable-loom is attached; this may be unplugged at either end, but it may be easier to
detach/reattach the plug connecting to the main unit.
To access the Fault Relay and other I/O Module connections, the front panel must be dropped down by
loosening the two knurled screw fixings at either side.
As shown in the diagrams in Section Mounting the Detectors on page 6, knock-out cable entry points
are provided at the top and left-hand side of the metal back box. Where the field wiring to the unit is not
via conduit tubing, strain-relief type cable glands of a suitable size to fit the 25 mm diameter holes must
be fitted to all used cable entry holes. These cable glands shall be fitted so as to provide strain relief
and ensure that the protective earth connection (where used) is the last conductor to take any strain.
External Power Supply Connection
FHSD700C detectors are powered by an external 24 VDC power supply.
The power supply cable cores should be fitted individually with ferrite cores, close to the cable gland
inside the equipment case. To fit the cables with the ferrite cores, insert the 24V and 0V conductors
through the ferrite cores and wrap around once to provide maximum effectiveness.
Connect the 24 VDC power supply to the 5-way connector (CN2) on the I/O board under the control
panel as shown in Figure 3-5.
1. External Power Supply
2. No Connection
3. Link
Figure 3-5: 24 VDC connection for FHSD700C Detectors
The MAINS/BAT terminal must be linked to 0 V. Failure to do so may result in a Mains Fault. The VBAT
and BATT TEST terminals should be left unconnected.
Ensure that in the Configuration menu, the STANDBY parameter is set to 0. For more information about
Configuration mode, please see CONFIGURE: Configuration Mode on page 21.
Grounding and Fuse Protection
An M5 chassis earthing stud is provided for the grounding of the unit using a suitable gauge of wire or
earth braiding (0.75 mm2minimum) to a primary earth point (i.e. copper water pipe or an earth-stake
etc.). This chassis earth should be connected on all DC powered installations.
www.gesecurity.net 9

FHSD700C Series Product Guide GE Security
1. Knock-out cable entry holes
2. M5 Chassis grounding stud
3. RS232 connector
4. Ethernet connector
5. Fuse (1 A)
6. Main I/O board
7. Beacon connector
8. Display & valve connector
9. Programming connector
10. Optional I/O modules
11. Drop-down display panel
Figure 3-6: FHSD721C / FHSD721DC to FHSD7215DC input and output interfaces
10 www.gesecurity.net

GE Security FHSD700C Series Product Guide
3.2.2 FHSD720C Connections
The FHSD720C detector provides interfaces as shown in Figure 3-7. Tables in Connection Interfaces
on page 12 provide detailed connection information for:
24 VDC power supply.
Fault Relay contact connections.
Auxiliary 24 VDC output supply - fused to 1 A Fast-blow and can be used for powering an
external sounder, addressable I/O units etc.
Remote Reset input line - activated by applying 24 VDC.
RS485 Communications - used for operating the unit via a remote panel, or for connecting up to
30 detectors.
Ethernet connection - used for connecting to a host computer. The unit can be monitored and
driven remotely via GE Security VSC or VSM4 software.
RS232 connection - used for conducting Test/Configuration functions and interrogation of the
Fault Log Data when connected to a PC running configuration software.
1. RS232
2. Ethernet
3. Fuse 1A
4. I/O Board
5. Output Relay Contacts
6. Optional I/O Modules
7. Programming Connector
Figure 3-7: Diagram of the I/O board for the FHSD720C detector
FHSD720C units are powered by an external 24 VDC power supply.
Access to the interior of the unit is gained by removal of the front cover. This is secured by four screw
lock fixings (one at each of the four corners), releasing these fixings allows the removal of the cover
complete with the ‘self-retained’ fixings.
The Fault Relay and other I/O Module connections are all located on the (i602) printed circuit board
immediately on the front face of the internal metal sub-chassis.
The DC Supply fuse (FS1), TR5 style fuse 250V 2A Time Delay, is located on the (i602) printed circuit
board.
A cable entry gland is provided on the rear of the bottom casing for entry of the DC Supply Cabling and
the field wiring cables. This cable gland is fitted so as to provide strain relief. The power supply cable
cores should be fitted individually with ferrite cores, provided for the purpose, close to the cable gland
inside the detector case. The 24 V and 0 V conductors are fed through the ferrite core and wrapped
round once to provide maximum effectiveness.
A second cable entry hole is provided, fitted with 0.2 to 2 mm grommet, to facilitate the Ethernet cable
(if used).
www.gesecurity.net 11

FHSD700C Series Product Guide GE Security
3.2.3 Connection Interfaces
The following tables define input and output connections for the FHSD700C Series.
Table 3-2: Connections for i602 I/O Board
CN1: RS232 Interface
2 Receive Data
3 Transmit Data
5 0 V
1, 4, 6, 7,
8, 9 N/C
Shell Earth (Screen)
Requires suitable twisted screened cable up to a maximum distance of 15 m.
CN2: DC Supply
1 24 VDC in
2 0 VDC in
3 N/C
4 N/C
5 Mains/Battery
Requires 16 x 0.25-15 A (18 AWG) cable (0.75mm2minimum IEC60227 H05 W-F/H05 WH2-F2
for EC).
Note: Link Pin 2 (0 V) and Pin 5 (MAINS/BAT). See External Power Supply Connection on page
9for further details.
CN3: Auxiliary Supply Output Interface
1 0 VDC
2 24 VDC
Requires 7 x 0.2 - 6 A (24 AWG) cable (1 A maximum load).
CN4: Remote Reset Interface
1 - input
2 + input Opto isolated input. 24 VDC low current signal.
CN6: RS485 Interface
1 Shield
2 RS485 -
3 RS485+
Belden 9842 cable (or suitable equivalent)
Note: Ensure that the Mid/End Jumper Link is fitted correctly on pins 7/8/9 of CN 5. Please see
Appendix B.1 on page 36 for further details.
CN7: Output Relay Interface
1 C
2 NC
3
FIRE 2
NO
4 C
5 NC
6
FIRE 1
NO
7 C
8 NC
9
ACTION
NO
10 C
11 NC
12
ALERT
NO
13 C
14 NC
15
FAULT
NO
Requires 7 x 0.2 - 6 A (24 AWG) cable
Note: Maximum relay contact rating is 2 A @ 30 VDC.
Note: Please see 4-Channel Relay Module on page 31 for further details.
Note: Connection CN14 is only used for special applications.
12 www.gesecurity.net

GE Security FHSD700C Series Product Guide
Table 3-3: Connections to RABBIT Processor Board
Connector Pin Description Description
8-pin RJ45 Standard Ethernet connections Standard Ethernet cable.
Note: See Installation Guide for RS485 Equipment on page 36 for further details.
Table 3-4: Connections From 4 Channel Relay Board (Optional Module)
Output Relay Interface (i606)
1 C
2 NC
3
RELAY 1
NO
4 C
5 NC
6
RELAY 2
NO
7 C
8 NC
9
RELAY 3
NO
10 C
11 NC
12
RELAY 4
NO
Requires 7 x 0.2 - 6 A (24 AWG) cable.
Note: Maximum relay contact rating is 2 A @ 30 VDC.
Note: Please see 4-Channel Relay Module on page 31 for full operational details .
The following tables do not apply to the FHSD720C detector.
Table 3-5: Connections To Remote Panel (Optional) - from I620 Control Board
RS485 Remote Control Data
1 +24 VDC (Supply Out) Belden 9842 (24 AWG) cable (or equivalent)
2 0 V (Supply Common)
3 RS485 +
4 RS485 -
Note: Ensure that the Mid/End Jumper Link is fitted to the End position (pins 1 and 2 of CN 6).
Note: Please see Sections Remote Display Panel on page 15 and Installation Guide for
RS485 Equipment on page 36 for further details.
Note: Please refer to Section Remote Display Panel on page 15 for details.
www.gesecurity.net 13

FHSD700C Series Product Guide GE Security
3.3 Connection of Sampling Tubes
There are several common guidelines that should be followed when attaching the pipe network to the
FHSD700C detector:
Pipes must NEVER be glued to the inlets of the detector
Pipe network itself MUST be glued together
Use removable unions where necessary
Unused inputs on FHSD7215DC detectors should be looped to one another using short lengths of
microbore. For example, if an FHSD7215DC has unused inputs 9 to 15, one way of connecting the
unused inputs would be to use short pieces of microbore to connect inputs 9 to 12, 10 to 13, 11 to 14
and have input 15 capped off. Ensure that these short lengths of microbore do not kink.
Do not insert ANY object into the inlet ports other than the correct size of piping. This is
to avoid damage to delicate electronic flow sensor components mounted just inside
each port opening.
Other pipe and inlet specifications are addressed in the following table.
Table 3-6: Detector Inlet to Pipe Network Termination Specifications
Detector Inlet Port Acceptable Pipe
or Adapter Maximum Pipe
Length Other Considerations
FHSD720C 25mm outer-
diameter UPVC
tubes 25mm; or
26.7mm (0.75in.)
with 25 to 26.7mm
(0.75in.) adaptors
2 x 100m -
FHSD721C /
FHSD721DC Tapered push-fit 26.7mm (0.75 in.)
to 25mm 4 x 100m -
FHSD724DC &
FHSD726DC Tapered push-fit 25mm; or
26.7mm (0.75in.)
with 25mm to
26.7mm (0.75in.)
adaptors
4 x 100m
or 6 x 100m
-
FHSD7215DC - 6mm outer-
diameter, 4mm
inner-diameter
flexible nylon tube
50m
Note: Tube lengths
should be equal
Other materials may be used
e.g. FEP/ Stainless Steel with
suitable adaptors for harsh
environments
14 www.gesecurity.net
This manual suits for next models
4
Table of contents
Other GE Smoke Alarm manuals

GE
GE ADTGC-HDVM Assembly instructions

GE
GE ESL 560N Series User manual

GE
GE 60-992-900 User manual

GE
GE TX-6212-03-1 Assembly instructions

GE
GE TX-6010-01-1 User manual

GE
GE 782136710441 User manual

GE
GE 429CT User manual

GE
GE ESL 700 Series User manual

GE
GE ESL 570N User manual

GE
GE Z630-3 Assembly instructions