Adleepower AP2G3-337 User manual

ADLEEPOWER
INSTRUCTION MANUAL
GENERAL-PURPOSE INVERTER
THANK YOU VERY MUCH FOR YOUR PURCHASE
OF ADLEE INVERTER APxG3 SERIES.
PLEASE READ THIS INSTRUCTION MANUAL
BEFORE INSTALLATION OF THE INVERTER.
R
AP2G3-337~AP2G3-3220
AP4G3-337~AP4G3-3220

CONTENTS
1. RECEIVING
2. SPECIFICATIONS
3. DIMENSION DRAWINGS
4. INSTALLATION
5. DESCRIPTION OF TERMINALS
6. DIGITAL OPERATION PANEL
7. FUNCTIONS DESCRIPTION
8. PROTECTIVE FUNCTIION
9. PRECAUTIONS
10. TROUBLESHOOTING
11.APPLICATION
12. INVERTER SELECTION
13. APPENDIX
A. Optional braking resistor
B. Terminal wiring diagram
1
2
4
6
8
17
18
79
83
84
85
91
93
93
94

1. RECEIVING
Befor installation and wiring, check to see :
(1) No damage is found on each product after shipping.
(2) The product is as ordered (check the nameplate, voltage and fre-
quency).
(3) A set of inverter unit and instruction manual is contained in the
package.
For any irregularity, contact the sales shop where you purchased
immediately.
(4) Description of name plate
MODEL : AP 4 G3 - 3 37
Max Applicable motor(4 pole)
37 : 3.7KW 55 : 5.5KW 75 : 7.5KW
110 : 11KW 150 : 15KW 185 : 18.5KW
220 : 22KW
3: 3
AP series
Voltage class :
2 : 200/240V
4 : 380/440V
IPM AC drive
1
∮

2. SPECIFICATIONS
2
ENTER
Model AP2G3
Voltage 3φ 200~240VAC ± 10%
Model No 337 355 375 3110 3150 3185 3220
Input Frequency 50HZ/60HZ ±5%
Output Voltage 3φ 220VAC
Output Frequency 0.5 ~ 400HZ
Output
Rated current (A) 17 24 33 46 61 76 90
Capacity (KVA) 6.5 9.2 12.6 17.6 23.3 29 34
Largest motor
KW ( 2.4.6 poles ) 3.7 5.5 7.5 11 15 18.5 22
Control Sine wave pulse width modulation
Braking Regenerative discharge braking
Over current
Capacity 150% of rated current ( 1 minute)
Acceleration time 0.1 ~ 6000 SEC
Deceleration time 0.1 ~ 6000 SEC
Frequency
setting
DigitalUse keyboard for setting and confirm by
Analog Analog signal input DC 0~5V, 0~10V, 4~20mA
Output signal Open collector output 50v 50mA Max
Cooling Method Air-cooled
Dimension drawing Fig 1 Fig 2
Weight ( KG ) 5.5 6.2 6.6 17 18 18.5 19

3
Model AP4G3
Voltage 3φ 380/440VAC ±10%
Model No 337 355 375 3110 3150 3185 3220
Input Frequency 50HZ/60HZ ±5%
Output Voltage 3φ 380/440VAC
Output Frequency 0.5 ~ 400HZ
Output
Rated current (A) 8.5 12 16.5 23 31 38 45
Capacity (KVA) 6.5 9.2 12.6 17.6 23.6 29 34
Largest motor
KW ( 2.4.6 poles ) 3.7 5.5 7.5 11 15 18.5 22
Control Sine wave pulse width modulation
Braking Regenerative discharge braking
Over current
Capacity 150% of rated current ( 1 minute)
Acceleration time 0.1 ~ 6000 SEC
Deceleration time 0.1 ~ 6000 SEC
Frequency
setting Digital Use keyboard for setting and confirm by
Analog Analog signal input DC 0~5V, 0~10V, 4~20mA
Output signal Open collector output 50v 50mA Max
Cooling Method Air-cooled
Dimension drawing Fig 1 Fig 2
Weight ( KG ) 5.5 6.2 6.6 6.8 18 18.5 19.5
ENTER

3. DIMENSION DRAWINGS
( AP2G3-337 AP2G3-355 AP2G3-375 )
( AP4G3-337 AP4G3-355 AP4G3-375 AP4G3-3110 )
Fig 1
Unit : mm
4

Fig 2
Unit : mm
5
( AP2G3-3110 AP2G3-3150 AP2G3-3185 AP2G3-3220 )
( AP4G3-3150 AP4G3-3185 AP4G3-3220 )

4. INSTALLATION
Inadequate environment around installation site and installation
surface can result in damage to the inverter.
Before operating the APxG3 series inverter, please check the following
points :
(1) Avoid high temperature, high humidity, easy-to-dew ambient envi-
ronment. Don’t expose to dust or dirt, corrosive gas, and coolant
mist, and direct sunlight. Place the unit in a well-ventilated room.
(2) Avoid a place subjected to substantial vibration.
(3) When installing the unit within the cabinet. Please pay attention to
ventilation and limit the ambient temperature in between -10℃~
45℃. (14℉~ 113℉).
(4) Use a nonflammable material, such a steel sheet on the wall for
installation. (The rear side will generate heat)
(5) Install the unit always vertically with a marginal spacing around.
6
AIR FLOW
15 cm
15 cm
5 cm
10 cm
10 cm

7
AIR FLOW

5. DESCRIPTION OF TERMINALS
(1) Main circuit connection diagram
8
RSTP2 P1 U V W
IM
Ground Power source Braking resistor
(★Note)
Ground
AP2G3-337~375
AP4G3-337~3110
AP2G3-3110~3220
AP4G3-3150~3220
Note : Release the internal braking resistor when connect external brak-
ing resistor.
L1 L2 L3 U V WPPR
IM
Ground Power source Brakingresistor
(★Note)
Ground
Main circuit terminal
Symbol Terminal name Description
R / L1
Inverter power source Terminal connecting with
power source
Single phase input : R, S
S / L2
T / L3
U
Inverter output terminal Terminal connecting with
motor
V
W
P / P2 DC voltage terminal Regenerative braking resistor
connecting terminal
PR / P1

(2) Description of hardware setting
AP2G3-337~375 AP4G3-337~3110
AP2G3-3110~3220 AP4G3-3150~3220
(3) RS485 connector
9
NO 8 7 6 5 4 3 2 1
Color Black Red Orange Yellow Green Blue Purple Brown
Symbol GND VCC GND ARFA0 BVCC
Connect to F306 or RS485
This connector is for RS485. Set CD13 for selection.
※
8765 4321
GND 10V FA1 FA2 MET MA MB MC ABC24V FWD REV CF1 FT2CF2 FT1 ARRRST COMCOM
RS485
SW1
431 2
S1
65
GND 10V FA1 FA2 MET MA MB MC A B C24V FWD REV CF1 FT2CF2 FT1 ARRRST COM COM
RS485
S1
SW1
431 2 65

ON
1 2 3 4 5 6
ON
ON
ON
(4) Analog signal switch setting
10
Note 1 : Input 4-20mA at FA1 or FA2, refer to function CD10/CD12/
CD44/CD45/CD54.
SIGNAL FA1 FA2
0 - 10V
0 - 5V
4 - 20mA
(Note1)★
Error setting
ON ON
ONON
ON ON
ON ON
SIGNAL Keypad VR
Keypad VR
Error setting
Error setting
Error setting
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6

(5) Jumper setting
S1 terminal control structure
(6) Control circuit terminal
AP2G3-337~3220 AP4G3-337~3220
11
1 and 2 short circuit :
External terminal NPN(SINK) structure.
(Factory setting)
2 and 3 short circuit :
External terminal PNP(SOURCE) structure.
1
2
3
GND 10V FA1 FA2 MET MA MB MC AB C 24V FWDREV CF1 CF2 FT1 FT2 RST ARR
VR5KB RUN Relay
Contact rating:1A 240VAC
21 43 5 76 98 10 1211 1413 15 191716 18 20
COMCOM
2221
METER
Fault Relay
1A 30VDC
NPN(SINK) structure (Factory setting)

CF1 CF2 SPEED
OFF OFF SPEED - 1
ON OFF SPEED - 2
OFF ON SPEED - 3
ON ON SPEED - 4
12
Symbol Control circuit terminal
Terminal Description
GND Analog common terminal Common terminal of free analog terminals
10V Analog source Power source +10V of analog terminals
FA1 Free analog terminal 1 See functions description (CD44)
FA2 Free analog terminal 2 See functions description (CD45)
MET Frequency meter terminal 0~100% duty open collector output or
0~10VDC / 2mAoutput (0~CD14)
MA
Relay output RUN
Relay output contact (normal open)
MB Relay output contact (normal close)
MC Relay output contact (common)
AAlarm output A Fault alarm contact (normal open)
BAlarm output B Fault alarm contact (normal close)
CAlarm output C Fault alarm contact (common)
24V Source terminal Source terminal of control board
FWD Forward operation Forward operation / stop terminal
REV Reverse operation Reverse operation / stop terminal
CF1
Multistage speed terminal
CF2
FT1 Multi function terminal 1 See functions description (CD42)
FT2 Multi function terminal 2 See functions description (CD43)
RST Reset Reset
ARR Operation output terminal
Frequency arrival signal Photocoupler output 48VDC/50mA(MAX)
COM Common terminal Common terminal of control board

13
∮
∮
(7) WIRING
7-1 Wiring of main circuit
AP2G3 3 and AP4G3 3
power source terminal
connect R/L1, S/L2, T/L3.
7-2 Wiring equipments
Select the wiring equipment and wiring size, refer to the table
below.
1. On the input power side, a molded case circuit breaker (MCCB)
to protect inverter primary wiring should be installed.
2. A leakage current breaker threshold of 200mA and above, or of
inverter use is recommended.
3. Use of input side magnetic contactor. An input MC can be used to
prevent an automatic restart after recovery from an external power
loss during remote control operation. However, do not use the MC
frequently for start/stop operation, or will lead to a reduced reliabil-
ity.
4. In general, magnetic contactors on the output of the inverter,
Should not be used for motor control. Starting a motor with the
inverter running will cause large surge currents and the inverter
overcurrent protector to trigger.
R/L1
S/L2
U
V
W
APxG3-Series
IM
E
POWER
T/L3
THRY
SOURCE
Model AP2G3 AP4G3
Model No 337 355 375 3110 3150 3185 3220 337 355 375 3110 3150 3185 3220
Capacity (KVA) 6.5 9.2 12.6 17.6 23.3 29 34 6.5 9.2 12.6 17.6 23.6 29 34
Current (A) 17 24 33 46 61 76 90 8.5 12 16.5 23 31 38 45
Circuit Breaker
(MCCB) (A) 20 30 50 75 100 125 150 15 20 30 50 50 75 75
Electro-Magnetic
Contactor (A) 18 35 50 65 80 93 93 12 18 18 35 48 50 50
Thermal relay
RC value (A) 15 20 28 40 55 67 80 6.8 9 15 20 28 40 40

7-3 Surge absorber
In order to prevent malfunction, provide the surge absorber on the
coils of the electromagnetic contactors, relays and other devices
which are to be used adjacent of the inverter.
7-4 Cable size and length
If the inverter is connected to a distant motor (especially when low
frequency is output), motor torque decreases because of voltage
drop in the cable. Use sufficiently heavy wire.
Changing the carrier frequency reduce RF1 noise and leakage
current. (Refere to the table below)
14
Distance
INVERTER →MOTOR under
25M under
50M under
100M above
100M
APxG3 SERIES under
16KHZ under
10KHZ under
5KHZ under
2.5KHZ

(a) (b) (c)
15
7-5 Wiring and cautionary points
A. Main circuit
1. Don’t connect the cables of the power supply side (R/L1,S/L2,T/
L3) to the U, V and W output terminals for the motor.
2. Don’t connect any electromagnetic contactor between the
inverter and motor. If it is inevitable, turn on the contactor when
both the inverter and motor are both at stand still.
3. Don’t put the advance phase capacitor between the inverter and
motor.
4. Put MCCB in the input power supply.
B. Control signal circuit
1. Separate the power cables of main circuit etc. from the control
cables of the sequence and analog signals by passing the cables
through the different ducts.
2. Use twisted pair shielded wire for control signal and connect the
shield to earth terminal at on end, COMMON terminal of
control board. Leave the other end of shielding open.
3. Avoid common Ground leads between high and low level
voltage equipment.
C. Grounding
1. Be sure ground both the inverter and motor.
2. Keep grounded leads as short as possible.
3. Shield cables used to protect low-level signal leads should
grounded at one end point.
4. Provide class 3 grounding (0.1Ωor less) for a terminal.
5. When grounding several inverters, make connections as shown
below, no loop is produced as shown in FIG “a “, FIG “b“.

7-6 Main circuit terminals
Wire Wire type Torque
AP2G3-337~375
AP4G3-337~3110
Input (R/L1,S/L2,T/L3)
Output(U,V,W,P,PR)
10AWG
(5.5mm2)Stranded copper only
(600V/80 )℃18Kg-cm
(15.6lb-in)
AP2G3-3110~3220
AP4G3-3150~3220
Input (R/L1,S/L2,T/L3)
Output(U,V,W,P,PR)
2AWG
(38mm2)Stranded copper only
(600V/80 )℃61.1Kg-cm
(53.03lb-in)
External control signal
terminals 24AWG~14AWG
(0.5mm2~2.0mm2)Stranded copper only
(300V/80 )℃5.1Kg-cm
(4.42lb-in)
16

6. DIGITAL OPERATION PANEL
17
FUNC
STOP
LED Operating
FUNC
FWD REV
Key
Model
VR
FREQ. SET
STOP
DSPAP G3
SMART INVERTER Indication
Indication
ENTER
FWD REV
AP-G3 DSP
SMART INVERTER
STOP
Model
LED Operating
Digital
Key
Indication
Indication
Indication
ENTER
FUNC
Operation key Key function Description
FWD RUN Forward run Commands forward run
REV RUN Reverse run Commands reverse run
SHIFT Cursor
movement Select the digit
DOWN Down Decrease the parameter value
UP Up Increase the parameter value
ENTER Memory
storage Saves the setting vaule
FUNC Function Press once to select function CDxx and
press again to change its content
STOP Stop Stop operation / Escape to standby mode
ENTER

7. FUNCTIONS DESCRIPTION
18
DISPLAY
CODE FUNCTION DEFAULT VALUE
☆CD00 First speed setting 60.00HZ
50.00HZ
CD01 Parameter lock 0
CD02 Acceleration time 1 10.0Sec
CD03 Deceleration time 1 10.0Sec
CD04 Jogging frequency 5.00HZ
CD05 Start frequency 0.50HZ
CD06 Jog mode 0
CD07 Reserved
CD08 CW or CCW or CW / CCW 0
CD09 Search speed function 1
CD10 Analog / digital frequency 1
CD11 Dynamic brake / Free running 0
☆CD12 Terminal / Keypad command 0
1
CD13 Source operation command 2
☆CD14 Maximum frequency limit 120.00HZ
50.00HZ
CD15 Minimum frequency limit 0.00
☆CD16 Frequency display Scale 1.00
30.00
☆CD17 1st Maximum voltage frequency 60.00HZ
50.00HZ
CD18 V/F pattern setting 0
CD19 DC braking time 1.0Sec
This manual suits for next models
14
Table of contents
Other Adleepower Inverter manuals
Popular Inverter manuals by other brands

Mounting Systems
Mounting Systems Infix ProLine installation manual

Mastervolt
Mastervolt WHISPER16 ULTRA user manual

SMA
SMA SUNNY ISLAND 4.4M operating manual

MULTIQUIP
MULTIQUIP Whisperwatt DCA150USJ2 Operation and parts manual

YMGI
YMGI 86 Series Installation instructions & user manual

Trumpf
Trumpf TruConvert AC 3025 Operator's manual