
For most applications, these controls do not need to be
adjusted. The Model 4082 will display any range from
00.0 to 34.6 feet of depth, and is factory set for this
range (i.e., 4ma equals 00.0 feet, and 20ma equals 34.6
feet). For levels less than 34.6 feet, the display will still
show the correct level.
Advanced Adjustments
If your Model 4082 Controller application does not require
any adjustments to the factory setting described above, skip
this section and go on to the 4-20ma Output Zero & Span
Adjustments section.
If it is necessary to make adjustments, for other
transducers, or for liquids other than water, the Model
4082 Controller has a wide display range (-600 to 1999).
If you are monitoring a 20 foot level, the Model 4082 will
show 20.0 feet, with an input of approximately 12ma.
With a different transducer, however, it will be
necessary to re-calibrate the display to accurately show
the correct depth. If care is taken, accuracy of 1% or
better is possible. An accurate 4-20ma source is
required.
Before going on with the adjustment procedures,
several critical areas must be thoroughly understood.
At this point in the instructions, decimal points will be
ignored (until you know the possible resolution, you
won’t know where to set the decimal selector).
First, the largest number possible on the LCD display is
1999 (the left most digit will only show a “1” or a blank).
Second, the difference between the minimum and
maximum values to be displayed is the span. The
Model 4082 Controller has a span range of 250 to 2600
counts. The difference between your minimum and
maximum values must fall within this range; i.e. your
application’s span must be at least 250 count, but not
over 2600 counts. Once you have this information, you
can determine how many decimal places to select. The
following are some examples:
1. You use a transducer with a 20ma output equaling
15 feet of liquid. The difference between 0 and 15,
is 15 counts, well below the minimum of 250 counts.
Add a zero to each number; now the span is 150
counts, still below the minimum. Add another zero,
and you now have a span of 1500 counts, well with-
in the span range. Now, you can see that the
decimal must be set for two places,for a resolution
of 1/100th of a foot, or 15.00.
2. You use a transducer with a 20ma output equaling
25 feet. The span is only 25, so a zero is added to
the count. The span is now 250, which meets the
minimum span. Select one decimal place (25.0).
Notice that adding another zero gives you a count
of 2500, which also falls within the span range;
however, you cannot place the decimal at two
places (25.00) because the LCD display can only
show up to 1999 (19.99).
3. You use a transducer with a 20ma output equaling
20 feet. The span is 20, so you must add a zero. A
span of 200 still does not meet the minimum of
250, so add another zero for a span of 2000. This
falls within the acceptable span range; however, as
stated above, the maximum LCD display is 1999.
Therefore, the decimal selector must be set to two
places, or 19.99. This means that your display will
be short of 20 feet by 1/100th of a foot, which
should be sufficient in most any application.
Now let’s look at the actual adjustment procedure.
The DISPLAY ZERO control sets the lowest number
you want the LCD display to read. This number will be
displayed when the transducer input is at 4ma. While
usually zero (the factory default), this number can be as
low as -600, or as high as 1749.
The DISPLAY SPAN control sets the highest number
you want the display to read. This number will be
displayed when the transducer input is 20ma. This
number is factory set to 34.6, but can be set as high as
1999, or as low as -350 (assuming a one decimal place
display setting).
Application example: Display level in a 5 foot tank,
when 4ma equal 0 feet, and 20ma equals 5 feet.
1. Using methods previously described in this section,
the span is determined to be 500. Set the decimal
selector to two places, for a resolution of 5.00.
2. Set the DISPLAY SELECT knob to LIQUID LEVEL
(either position).
3. Apply a 4ma signal to the input. Adjust the DISPLAY
ZERO control for a 0.00 reading.
4. Apply a 20ma signal to the input. Adjust the
DISPLAY SPAN control for a 5.00 reading.
5. Repeat steps 3 and 4 as needed to fine-adjust the
display reading. It may be necessary to repeat the
steps several times to achieve maximum accuracy.
MODEL 4082 Liquid Level Controller
TIME MARK is a division of
Telephone: Main -(918) 438-1220
Sales -(800) 862-2875
Fax: (918) 437-7584
E-mail: sales@time-mark.com
Internet:http://www.time-mark.com
Doc No. 87A403 04/03 page 5 of 6
© 2003 TIME MARK CORPORATION
11440 East Pine Street
Tulsa, Oklahoma 74116