manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. AIC
  6. •
  7. Boiler
  8. •
  9. AIC COILMASTER 70 Manual

AIC COILMASTER 70 Manual

EN
Z-089875 • 02
COILMASTER 60-70-80-100-120 Gas Conversion Procedure
After gas conversion is performed,
control the gas pressure and consump-
tion at appliance start up, and perform
the adjustment procedures provided in
“Adjustment of Fan Speeds” on page
3and “Combustion Adjustment”
on page 4.
i
Summary
This procedure consists in replacing the facto-
ry-installed air-gas mixer for G20 natural gas at-
tached to the fan, by an air-gas mixer for either
G25 natural gas or G31 liqueed gas (Propane).
See Fig. 1 opposite for air-gas mixer location.
See table below for air-gas mixer top and bottom
injector sizes:
Air-gas mixer (Venturi)
Fig. 1. Component Location
Models
G25
Top - Bottom
G31
Top - Bottom
CM 60 - 70 - 80 6,0 - 6,0 4,7 - 4,5
CM 100 - 120 6,6 - 6,6 5,3 - 5,0
îMake sure that the gas type and pres-
sure of the distribution network are com-
patible with the appliance, as per the
information on the appliance data plate.
îIf the boiler was running before conversion,
allow it to cool down before performing any
task.
îConversion of the appliance from one
gas type to another can only be per-
formed by a qualied professional.
îGas conversion shall be performed
according to applicable local reg-
ulations. It is prohibited in some
countries. Perform conversion ac-
cording to the gas category spec-
ied for your country on the appli-
ance data plate.
îIf the boiler is intended to be used
with liqueed gas (propane), in-
stalling the boiler below ground
level can be hazardous and prohib-
ited in some countries. Please refer
to applicable local regulations for
installation requirements.
îIf the boiler is already installed before
conversion, the boiler must be turned
o, the power supply must be dis-
connected through the external fuse
or circuit breaker, and the gas supply
to the gas valve must be closed.
2Z-089875_EN • 02
CoilMaster 60-70-80-100-120 - Gas Conversion ProCedure
Air-Gas Mixer Replacement
Conditions:
îBoiler turned o using the appliance on/o switch
îPower supply deactivated through external electrical box
(fuse or circuit breaker)
îGas supply shut down
îBoiler cooled down
îFront and top panel removed. Please refer to the Installation
and Maintenance Manual for the correct procedure.
Tools and material:
îWrench, hex head
îScrewdriver, at
îTorque wrench
îProtective gloves
Air-Gas Mixer Removal Procedure (Fig. 2)
1. Disconnect all connectors and ground wires from the elec-
trodes, the fan and the gas valve.
2. Wearing protective gloves, remove rock wool insulation
from the upper plate. Retain for reinstallation.
3. Release the hose clamps and disconnect the compen-
sation hose (9) from the gas valve (3) and the ue box
(10). Retain hardware for reinstallation.
4. Check the hose (9) condition and that it is not obstructed.
Clean as required, or replace with a new one.
5. Disconnect the air inlet duct (1) from the air-gas mixer (6)
and the ue box (10).
6. Release gas pipe connection (2) from gas valve (3).
7. Release the screws and washers securing the fan as-
sembly to the burner door.
8. Remove the assembly formed by the fan (8), the air-gas
mixer (6) and gas valve (3). Check the fan gasket condi-
tion and replace as required.
9. Release union (4) securing the gas valve (3) and tube to
the air-gas mixer (6). Check the gasket (5) condition and
replace as required.
10. Release 3 screws and washers (7) securing the air-gas
mixer (6) to the fan (9).
11. Remove the air-gas mixer (6) and the hardware. Retain
hardware for reinstallation.
When removing the air-gas mixer, check the gen-
eral condition of the O-ring. Discard and replace
the O-ring if it is cracked or torn.
Air-Gas Mixer Installation Procedure (Fig. 2)
1. Install the new air-gas mixer (6) on fan using hardware
retained at removal (7) and O-ring.
2. Install gasket (5) and fasten the gas valve (3) with pipe to
the air-gas mixer (6) with union (4).
3. Install the assembly formed by the fan, the air-gas mixer
and gas valve with a new gasket (if required) on the burn-
er door, using retained screws and washers. Torque the
screws at 4 Nm.
4. Connect the gas pipe (2) to the gas valve (3)
5. Connect the air inlet duct (1) to the air-gas mixer (6) and
ue box (10).
6. Connect the compensation hose (9) to the gas valve (3)
and the ue box (10). Tighten both extremities using re-
tained clamps.
After installing the compensation hose,
make sure that the clamps are correct-
ly tightened at both ends. An accidental
disconnection during boiler operation can
cause injuries.
7. Wearing protective gloves, install insulation on the burner door.
8. Reconnect all connectors and grounding wires to the gas
valve and fan.
Follow-on Task(s)
îOpen gas supply to the boiler.
îCheck the absence of leaks.
îPerform the fan speed adjustment. See “Adjustment of Fan
Speeds” on page 3.
i
7
6
1
3
4
5
2
8
Fig. 2. Removal and Installation of the Air-Gas Mixer
9
10
3
Z-089875_EN • 02
CoilMaster 60-70-80-100-120 - Gas Conversion ProCedure
Adjustment of Fan Speeds
Conditions:
îBoiler full of water and under pressure
îGas supply open
îPower supply activated through external electrical
box (fuse or circuit breaker)
Adjustment Procedure (Fig. 3)
1. Restart the boiler according to the procedure pro-
vided in the installation manual of the appliance.
2. Rotating the selector (1) and depressing it to con-
rm each selection:
îselect the icon,
îselect “Expert”,
îin “Select user level”; select “Engineer”, then
“Continue”
îselect the icon,
îselect “complete parameter list”,
îselect “Time of day and date” to access the list
of menus.
3. Rotating the selector (1), scroll to the bottom of the
list, “Burner Control”,
4. On page “(4/12)”, select “9524 Required speed LF”.
Press the selector (1) to modify the value. The value is
displayed in white on a black background (2).
5. Rotating the selector (1), adjust the minimum fan
speed according to the table shown at the bottom
of the page.
6. Press the selector (1) to conrm and save the value.
7. Rotating the selector, go up the screen, back to the
Burner Control page number. Select page number
“(4/12)” by pressing the selector (1), then go to the
following page.
8. On page “(5/12)”, select “9529 Required speed
HF”. Press the selector (1) to modify the value. The
value is displayed in white on a black background.
9. Rotating the selector (1), adjust the nominal fan
speed according to the table shown at the bottom
of the page.
10. Press the selector (1) to conrm and save the value.
11. Press the selector (1) for more than 3 sec. to exit
the setting menu.
Follow-on Task(s)
îPerform the combustion adjustment. See “Com-
bustion Adjustment” on page 4.
Fig. 3. Fan Speed Adjustment - Typical Screen
27.01.2020 16:42
2
Burner control 4/12
9518 Safety me
9519 Safety me with ignion
9524 Required speed LF
3.0s
1400rpm
3.6s
Back
1
2
CM 60 CM 70 CM 80 CM 100 CM 120
Fan speeds for G25 (Natural Gas) Minimum rpm 1 400 1 400 1 400 1 400 1 400
Nominal rpm 5 150 6 300 7 050 7 320 8 300
Fan speeds for G31 (Propane Gas) Minimum rpm 1 400 1 400 1 400 1 400 1 400
Nominal rpm 4 800 5 900 6 630 6 600 7 550
4
CoilMaster 60-70-80-100-120 - Gas Conversion ProCedure
www.myaic.eu
AIC Europe B.V.
Graafschap Hornelaan 163A
NL-6001 AC Weert
Combustion Adjustment
Conditions:
îBoiler full of water and under pressure
îGas supply activated
îPower supply activated through external electrical
box (fuse or circuit breaker)
îBoiler turned on using the On/O switch
Tools and material:
îFlue gas analyser
îScrewdriver, at head, size 3
îWrench, hex head, sizes 2 and 2.5
Adjustment Procedure (Figs. 4 & 5):
1. Activate the required heating mode.
2. Allow the boiler to operate for a few minutes.
3. Connect the ue gas analyser probe to the meas-
uring port of the ue gas pipe.
4. Check CO2 contents in the ue gas at max output
as follows:
îUsing the rotary selector (1), select and acti-
vate the icon,
îSelect “Special operations (1/3)”,
îSet “Chimney sweep function” to “On”,
îSet “Burner output” to “Full load”.
6. If the value is outside the range, adjust the com-
bustion value by turning the gas valve throttle (2) in
small steps, to allow the value to stabilise before
performing additional adjustments.
- Rotate throttle screw clockwise (to the right)
to decrease the CO2 contents.
- Rotate throttle screw counter-clockwise (to
the left) to increase the CO2 contents.
7. Check CO2 contents in the ue gas at min. output
as follows:
îSet “Burner output” to “Partial load”.
îCheck the CO2 contents, and compare the values
with those in the table at the bottom of the page.
îIf the value is outside the range, adjust the
combustion value by turning the oset screw
(3) in small steps to allow the value to stabilise
before performing additional adjustments.
The oset screw (3) is factory-sealed.
After adjustment, make sure to reseal it.
8. In “Special operations (1/3)”, set “Chimney
sweep function” to “off”.
9. Press the selector (1) for more than 3 sec. to exit
the setting menu.
10. Restart the boiler to check the ignition behaviour.
Control the correct operation of the boiler by re-
peating steps 1 to 7.
11. Reseal the oset screw (3) using some paint or tape.
Follow-on Task(s):
îOn the gas valve (Fig. 5), place the yellow sticker in-
dicating that a gas conversion has been carried out.
îOn the data plate (below the boiler), place the white stick-
er indicating that a gas conversion has been carried out.
îReinstall front and top panels, Please refer to the ap-
pliance Installation and Maintenance manual for the
correct procedure.
îRecord the combustion values in the log sheet available
in the installation manual of the appliance.
i
Fig. 4. Combustion Adjustment - Control Panel
2
3
Fig. 5. Combustion Adjustment on Gas Valve
G31
G25/
G25.3
Or
Sticker
27.01.2020 14:42
Special operaons (1/3)
Chimney sweep funcon
On
Back
1
5. Check the CO2 (or O2) contents displayed on the
gas analyser, and compare the values with those in
the table below.
CM 60 - 70 - 80
CO2 contents (G20/G25) %8,4 (± 0,1) - 8,8 (+0,2)
CO2 contents (G31) %10,0 (± 0,2) - 10,5 (± 0,2)
O2 contents (G20) %5,9 (± 0,18) - 5,2 (-0,36)
O2 contents (G25) %5,7 (± 0,18) - 4,9 (-0,36)
O2 contents (G31 %5,7 (± 0,30) - 4,9 (± 0,30)
CM 100 - 120
CO2 contents (G20/G25) %8,4 (± 0,1) - 8,8 (± 0,1)
CO2 contents (G31) %10,0 (± 0,2) - 10,5 (± 0,2)
O2 contents (G20) %5,9 (± 0,15) - 5,2 (± 0,15)
O2 contents (G25) %5,7 (± 0,15) - 5,0 (± 0,15)
O2 contents (G31) %5,7 (± 0,15) - 4,9 (± 0,15)
CO2 contents (G20/G25) (± 0.1) %8.4 - 8.8
CO2 contents (G31) (± 0.2) %10.0 - 10.5
O2 contents (G20) (± 0.15) %5.9- 5.2
O2 contents (G25) (± 0.15) %5.7- 5.0
O2 contents (G31) (± 0.15) %5.7- 4.9

This manual suits for next models

4

Other AIC Boiler manuals

AIC SILOX S Manual

AIC

AIC SILOX S Manual

AIC COILMASTER 35 User manual

AIC

AIC COILMASTER 35 User manual

AIC NESTA 300 Manual

AIC

AIC NESTA 300 Manual

AIC COILMASTER 60 User guide

AIC

AIC COILMASTER 60 User guide

AIC NESTA CHROME 150 Manual

AIC

AIC NESTA CHROME 150 Manual

AIC SILOX 140L User guide

AIC

AIC SILOX 140L User guide

AIC NESTA CHROME User manual

AIC

AIC NESTA CHROME User manual

AIC NESTA CHROME Series Manual

AIC

AIC NESTA CHROME Series Manual

AIC Nesta Series Manual

AIC

AIC Nesta Series Manual

AIC NESTA CHROME 150 Manual

AIC

AIC NESTA CHROME 150 Manual

AIC NESTA PLUS Series Manual

AIC

AIC NESTA PLUS Series Manual

AIC NESTA CHROME 24 Manual

AIC

AIC NESTA CHROME 24 Manual

AIC COILMASTER 100 Manual

AIC

AIC COILMASTER 100 Manual

AIC COILMASTER 100 User manual

AIC

AIC COILMASTER 100 User manual

AIC NESTA 120 Manual

AIC

AIC NESTA 120 Manual

Popular Boiler manuals by other brands

ACV E-Tech S 160 Installation & servicing instructions

ACV

ACV E-Tech S 160 Installation & servicing instructions

ROC Crown Gold Series user guide

ROC

ROC Crown Gold Series user guide

IDEAL Concord CXA 40 user manual

IDEAL

IDEAL Concord CXA 40 user manual

Burnham Alpine ALP105 Installation, operating and service instructions

Burnham

Burnham Alpine ALP105 Installation, operating and service instructions

Smith GSX SERIES User's information manual

Smith

Smith GSX SERIES User's information manual

Zip 11052 Zip Autoboil 15 Litre White Installation & operating instructions

Zip

Zip 11052 Zip Autoboil 15 Litre White Installation & operating instructions

Dunkirk Empire II Installation & operation manual

Dunkirk

Dunkirk Empire II Installation & operation manual

American Standard GRWF130A94A0A installation guide

American Standard

American Standard GRWF130A94A0A installation guide

Fondital ITACA CH KR 45 Installation, use and maintenance

Fondital

Fondital ITACA CH KR 45 Installation, use and maintenance

Beretta EXCLUSIVE GREEN 25 CSI Installation and user manual

Beretta

Beretta EXCLUSIVE GREEN 25 CSI Installation and user manual

MHS Boilers NHREV18 installation instructions

MHS Boilers

MHS Boilers NHREV18 installation instructions

Riello INSIEME CONDENS 26 B Installation and maintenance manual

Riello

Riello INSIEME CONDENS 26 B Installation and maintenance manual

Sime afaq PIROEMME manual

Sime

Sime afaq PIROEMME manual

Astra G-50E Installation and operation manual

Astra

Astra G-50E Installation and operation manual

iQe SIMPLICITY Series User instructions

iQe

iQe SIMPLICITY Series User instructions

Gemco GE-IM016En-0312 owner's manual

Gemco

Gemco GE-IM016En-0312 owner's manual

Arca Caldaie ASPIRO A 29 R/SA Installation operation & maintenance

Arca Caldaie

Arca Caldaie ASPIRO A 29 R/SA Installation operation & maintenance

Copa eomix User and installation manual

Copa

Copa eomix User and installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.