AirCycler g1 Operation manual

AirCycler® g1
Installation & User’s Guide
VENTILATION MADE BREEZY!™
a breeze to install • a breeze to use
Ventilation Products

2AC DOC
REV 9/14/2016
INTRODUCTION
If the AirCycler® g1 was installed in your home as a ventilation controller, turning o or otherwise disabling the
controller could result in under ventilating your home and could adversely impact indoor air quality.
In the past, homes depended on natural leaks for ventilation. Today, energy ecient homes are built to reduce natural
ventilation and leaks. Inadequate ventilation can cause indoor air pollutants to rise to harmful levels. Indoor air quality
is typically 5 to 10 times more polluted than outside air. Controlled ventilation systems like the AirCycler® g1 provide
adequate air ow to the home without compromising its eciency.
The AirCycler® g1 is integrated with the home’s HVAC system. When the home’s furnace fan is turned on by the
thermostat to provide heating or cooling, the AirCycler® g1 controller opens a motorized damper to let in a measured
amount of fresh air. The fresh air is ltered by the return plenum lter and is then distributed uniformly throughout
the home through the existing ductwork. Once the ventilation requirements are met, the damper is closed to prevent
over-ventilation. If there are not enough heating or cooling calls to meet ventilation requirements for the hour the
AirCycler® g1 will turn on the furnace fan and open the motorized damper until requirements have been met.
SAFETY CONSIDERATIONS
Read and follow manufacturer’s instructions carefully. Follow all local electrical codes during installation. All wiring
must conform to local and national electrical codes. Improper wiring or installation may result in personal injury or
product and property damage.
INSTALLATION CONSIDERATIONS
The AirCycler® g1 requires 24VAC (R and C terminals) to be connected for proper operation. The controller will not
operate without these two connections.
The wires (R, C, & W ) from the air handler to the thermostat can run parallel with the wiring from the AirCycler®
g1 to the air handler. The fan wire (G) must be interrupted by the AirCycler® g1. Some thermostats do not require a
common (C) connection. The AirCycler® g1 requires this for power, which must be wired to the furnace.
BATTERY (MODEL CR1220)
The AirCycler® g1 is equipped with a real time battery backed-up clock for use with the Operation Hours setting ONLY.
If not setting the hours of operation, the included battery is not required. All other settings are saved in nonvolatile
memory.
RECORD ALL SETTINGS ON THE INSTALL STICKER PROVIDED. LIMITED
WARRANTY WILL BE VOID IF THE STICKER IS NOT PRESENT.

3AC DOC
REV 9/14/2016
SELECTING YOUR COMPONENT EQUIPMENT
AIR HANDLER
The 2012 IECC requires the central blower used with the AirCycler® g1 to use an electronically commutated motor.
WIRING DIAGRAM
Y R W G
Y R C W G
White
OPTIONAL
DAMPER
Red
Blue
THERMOSTAT
AirCycler® g1AIR HANDLER
KEY
R - 24VAC Power
C - Common
Gt - Fan From Thermostat
Gf - Fan To Furnace
V - Vent
Vnc - Normal Closed Vent

4AC DOC
REV 9/14/2016
Filter
AirCycler®
g1
Thermostat
Main Return
Duct
Motorized
Damper
Outside
Air Duct
DAMPER LOCATION
The fresh air damper can be located anywhere in the inlet duct. Minimize the length of the inlet duct to improve air
ow and improve system eciency. It is recommended that the damper be as close to the return air plenum and the
AirCycler® g1 controller as possible, and the inlet duct connect to the return plenum upstream of the system lter, and
down- stream of any duct mounted sensors.
DAMPER INSTALLATION
The damper may be installed in any position. It is recommended to install it with the motor at the 12 o’clock position if
mounted horizontally. Air may ow through in either direction, although it is recommended to install with the crimped
end as the outlet. Use care to avoid distorting the damper housing and provide adequate support. Upon system start
up be sure to set damper power switch to UP or AUTOMATIC position.
CHOOSE A FRESH AIR LOCATION
ASHRAE recommends that the fresh air intake be located at least 10 ft. from any source of pollutants, such as auto
exhaust, dryer exhaust, exhaust from any fuel-burning appliances, etc. Avoid installation near odor sources such as
garbage bins or barbecue grills. A minimum of 3 ft. above ground is recommended to avoiding ingress of leaf litter,
grass clippings, etc. Do not use a crawl space, basement, or attic as a source of intake air. Always be sure to comply with
local building codes and requirements regarding fresh air inlets.

5AC DOC
REV 9/14/2016
1.0 INSTALLATION & CONFIGURATION INSTRUCTIONS
1.1 AIRCYCLER® G1 CONTROLLER LOCATION
The AirCycler® g1 controller can be installed near the thermostat or out of view on/near the air handler unit.
Warning: Before installing the AirCycler®, turn o all power to the furnace. There may be more than one power to disconnect.
Electrical shock can cause injury or death.
1.2 CONFIGURING THE AIRCYCLER G1®
On power up, all icons will be illuminated for 3 seconds.
There are two set up methods: Calculated Flow and Calculated Time. If you know the amount of fresh air coming into the
air handler as well as ow required by code you can use Calculated Flow to meet requirements. If you prefer to congure
the amount of time you want fresh air to enter the home per hour, use Calculated Time.
To set up the AirCycler® g1 based on Calculated Flow press and hold the UP arrow for 10 seconds.
To set up the AirCycler® g1 based on Calculated Time press and hold the DOWN arrow for 10 seconds.
OPERATING MODE DISPLAY
When the AirCycler® is in Normal Operation, the display will show
the percentage of ventilation complete for the current hour.
If the outside fresh air damper is open the OA icon will show.
If the thermostat is calling for heat or cool, the FAN icon will be
illuminated without the ON icon.
If the central fan is on, the FAN and ON icons will show. The
ON icon is only illuminated when the AirCycler® g1 has
forced the central fan on.
Pressing the MODE button at any time during normal
operation will go to setting the current time of day.
THE THERMOSTAT
HAS TURNED ON
THE CENTRAL FAN
THE AIRCYCLER® G1
HAS FORCED THE FAN
THE DAMPER
IS OPEN
PERCENTAGE OF
VENTILATION COMPLETE
G1 OPERATION & DISPLAY UP ARROW
Use as directed during set up.
During Normal Operation, use to view
current status
MODE BUTTOM
Use as directed during set up.
During Normal Operation, use to cycle
through current time of day
DOWN ARROW
Use as directed during set up.
During Normal Operation, use to view
current settings

6AC DOC
REV 9/14/2016
2.2 SETTING CODE REQUIRED CONSTANT AIR FLOW
Set the required continuous air ow in CFM based on relevant codes. For ASHRAE 62.2
see Appendix A. Factory default is 30 CFM. The AirCycler® g1 will calculate run times
based on settings 2.1 and 2.2.
Press MODE to advance to the next setting
2.3 SETTING OPTIONAL MIXING TIME
If the user needs more central fan time for whole house mixing than the amount that
is provided by ventilation time, the central fan can be congured to run an additional
time period to complete the mixing period. Factory default is 0 or OFF. To use/change
this setting press UP arrow. The fresh air damper will not be open during this extra time.
Press MODE to advance to next setting.
2.4 SETTING OPERATION HOURS
If the user does not want the ventilation system to run throughout the day you can set
ON time and OFF time. Factory default is NO. If you are not setting an ON and OFF time,
press MODE and continue to section 2.5.
If you want to set hours of operation press the UP arrow for yes [YS]. Press MODE to select
yes. The AirCycler® g1 will prompt you to enter the hour you would like the ventilation
to begin and the hour you want it to end followed by the current time.
Set the hour you want ventilation to START. Press MODE to advance to the next setting.
Set the hour you want the ventilation to STOP. Press MODE to advance to next setting.
2.4.1 SETTING CURRENT TIME
Enter the current time. Press MODE to save all settings. Setup is complete.
2.5 CALCULATED FLOW SETUP IS COMPLETE
Set up is complete. The AirCycler® g1 will now return to normal operation.
2.0 CALCULATED FLOW SET UP
2.1 SETTING MEASURED SUPPLY AIR FLOW
The measured ow is the amount of air that enters the
return side of the air handler from the outside air vent.
Enter the measured ow. To accommodate variable speed
air handlers, you can enter dierent values for heat, cool
and fan. Factory default is 90 CFM.
Press MODE to advance to the next setting.
Flow measured
during heat call
Flow measured during
cooling call
Flow measured during
fan only call
*Only if FanConnect™ switch is not
connected
Alternating
Display
Press: MODE
Alternating
Display
Press: MODE
Alternating
Display
Press: MODE
N

7AC DOC
REV 9/14/2016
3.0 CALCULATED TIME SETUP
3.1 SETTING NUMBER OF MINUTES PER HOUR OF SUPPLIED AIR FLOW REQUIRED
Enter the minutes per hour that you require fresh air to be brought into the home. Factory
default is 20 minutes. Press MODE to advance to the next setting
3.2 SETTING OPTIONAL MIXING TIME
If the user needs more central fan time for whole house mixing than the amount that is
provided by ventilation time, the central fan can be congured to run an additional time
period to complete the mixing period. Factory default is 0 or OFF. The fresh air damper
will not be open during this extra time. Press MODE to advance to the next setting.
3.3 SETTING OPERATION HOURS
If the user does not want the ventilation system to run throughout the day you can set
ON time and OFF time. Factory default is NO. If you are not setting an ON and OFF time,
press MODE and continue to section 3.4.
If you want to set hours of operation press the UP arrow for yes [YS]. Press MODE to select
yes. The AirCycler® g1 will prompt you to enter the hour you would like the ventilation
to begin and the hour you want it to end followed by the current time.
Set the hour you want ventilation to START.
Press MODE to advance to the next setting.
Set the hour you want the ventilation to STOP.
Press MODE to advance to the next setting.
3.3.1 SETTING CURRENT TIME
Enter the current time.
Press MODE to save all settings. Setup is complete.
3.4 CALCULATED TIME SETUP IS COMPLETE
Setup is complete. The AirCycler® g1 will now return to normal operation.
N

8AC DOC
REV 9/14/2016
4.0 NORMAL OPERATION DISPLAY
DISPLAY STATUS & SETTINGS
4.1 CURRENT STATUS
To get detailed status information, press the UP arrow during normal operation. The status screens are the same for
both Calculated Flow and Calculated Time modes.
4.1.1 MINUTES LEFT
The rst screen is the number of minutes left in the period (hour). Pressing the UP arrow
again gets you to the next status screen
4.1.2 OUTSIDE AIR TIME ELAPSED
This display shows the number of minutes this period that the outside air damper has
been open with the central fan running.
4.2 CURRENT SETTINGS
By pressing the DOWN arrow during normal operation, the user can scroll through the current settings entered by the
installer.
For Calculated Flow mode the screens will show:
• Required CFM set
• Measured outside air CFM
• If operating time is enabled:
Operating Time ON
Operating Time OFF
For Calculated Time mode the screens will show:
• Outside air time in minutes
• If operating time is enabled:
Operating Time ON
Operating Time OFF
5.0 SET CURRENT TIME
By pressing the MODE key you will cycle through current time of day and will be able to change it if needed. See section
2.4 or 3.3 for details.
6.0 RESET TO DEFAULT VALUES
From normal operation hold the UP arrow for 15 seconds to be prompted to reset all settings to default. Press the UP
arrow for yes [YS]. Press MODE to select yes.
7.0 POWERING OFF
Warning: It is not recommended to turn o the AirCycler® if the unit is used as a ventilation controller.
From normal operation hold the MODE button for 10 seconds. You will have the option to turn the unit o. Press the UP
arrow for yes [YS]. Press MODE to select yes. The controller will shut o within a few seconds.

9AC DOC
REV 9/14/2016
APPENDIX A
ASHRAE 62.2 REFERENCE CHART
CFM Required:
7.5 CFM * (N+1) + A * 0.01
N = No. of Bedrooms A = Square Footage
Square Footage
No. of Bedrooms
SOFTWARE VERSION
To determine the software version used in your controller press and hold the DOWN arrow for 15 seconds
(from normal operation). The software revision number will be displayed on the screen.

10 AC DOC
REV 9/14/2016
APPENDIX B
TROUBLESHOOTING
Problem: No power to AirCycler® g1
Check common wire connection. “C” must be connected to “C” on the furnace.
Problem: Furnace fan is running constantly
Make sure the thermostat FAN switch is set to AUTO and not ON.
Problem: Central fan does not shut o when AirCycler® g1 is removed from base (when thermostat fan switch is on)
Check wiring - “G” wire from thermostat should be wired to “Gt” on AirCycler® g1. “Gf” on AirCycler® g1 should be
connected to “G” on furnace.
Problem: Blank Display on the AirCycler® g1
Conrm:
1. The furnace has power
2. The thermostat is operational
3. The furnace will call for heat from the thermostat
4. The fan operates with a fan only signal from the thermostat
5. The furnace is providing 24 VAC to the AirCycler® g1
6. Verify wiring conforms to wiring diagram
7. Make sure cover is rmly seated on the base
Problem: AirCycler® g1 turns furnace fan on and o, but the motorized damper does not cycle.
Conrm:
1. The AirCycler® g1 is providing a 24 VAC signal to the motorized damper
2. The 24 VAC motorized damper is operational by powering directly with a 24 VAC signal
3. There is continuity in the wiring between the damper and the AirCycler® g1
4. Conrm damper power switch is in up or automatic position
Problem: A/C turns on during fan cycling calls
Conrm:
1. Wiring conforms to wiring diagram
2. The G wire is properly connected
3. The G wire needs to be interrupted by the AirCycler® g1
4. Do not run the G wire in parallel
Technical Support:
1.877.FAN.CONTrol
(1.877.326.2668)
Other manuals for g1
1
Table of contents
Other AirCycler Controllers manuals
Popular Controllers manuals by other brands

Samson
Samson 4765 Mounting and operating instructions

Festo
Festo DNCKE operating instructions

Helo
Helo OK 33 PS-3 product manual

Precision Flight Controls
Precision Flight Controls Cirrus Desktop Yoke user guide

Carlisle
Carlisle DeVILBISS HGB Series Service manual

National Instruments
National Instruments cDAQ-9133 quick start

Lenze
Lenze AC Tech M3103S Installation & operation manual

STEINEL
STEINEL NightmatIQ manual

YOKOGAWA
YOKOGAWA UTAdvanced UT32A user manual

Trane
Trane Tracer MP581 installation instructions

Sony
Sony BKM-36H instruction manual

Asahi/America
Asahi/America 94 Series Installation, operation and maintenance manual