5
QM CONTROLLER INSTRUCTIONS
MAIN CONTROLS
OFF
Switches the unit off.
When the air conditioning system is switched off, the
water tank is emptied and a fresh tank of water is taken
in. The fresh water is used to perform a 15 minute
FLUSH cycle. Fresh water rinses and cleans the pads of
any impurities or minerals left from the evaporative
cooling process. To by-pass the FLUSH Mode, press FAN
then OFF.
FAN
In FAN mode, the water pump is not activated and the
OFF
COOL UP
FAN
EXHAUST DOWN
unit will deliver ambient temperature air from outside
throughout the property. Airflow is adjusted using the UP
and DOWN buttons.
EXHAUST
The EXHAUST function allows the hot air which has built
up to be expelled before the cooling process starts, this
can reduce the time needed to cool the property.
COOL
In COOL mode, both the fan and water pump operate to
provide cool airflow throughout the property. Air flow
can be adjusted from 1 % to 100% using the UP and
DOWN buttons
If the unit is operating in COOL or FAN mode when
QM CONTROLLER
switched to EXHAUST, there will be a 30 second delay to allow the motor to stop prior to reversing direction.
The system has been pre-set to provide a 5 minute pre-wash cycle before the fan starts. Water is circulated over
the pads to wash off any dust. To bypass this wash cycle, press FAN and then COOL. After each 5 hours of
operation a periodic drain cycle empties the tank of water. This 5 hour cycle may be altered if required. See “Water
Management System Settings”.
When the air conditioning system is switched off, the water tank is emptied and a fresh tank of water is taken in.
This fresh water is used to perform a 15 minute FLUSH cycle. Fresh water rinses and cleans the pads of any
impurities or minerals left from the evaporative cooling process. To by-pass this FLUSH cycle, press FAN then OFF.
FAN
The FAN Mode is useful when the outside ambient temperature is cool and no direct cooling from the air conditioner
is required.
EXHAUST
Exhaust mode is useful for eliminating heat or odours from the property without the in-rush of air experienced
with the COOL and FAN modes. It is particularly useful in winter when a cold draft of air is not desirable.
A delay occurs when switching to EXHAUST Mode. This is to protect the motor and allow it time to stop, before the
rotation is reversed.