Alarmcom ADC-ACC1-17 User manual

DOOR
CONTROLLER
INSTALLATION GUIDE

DOOR
CONTROLLER
The ADC-ACC1-17 Door Controller provides local decision
making, event reporting, and database storage capabilities
for the Alarm.com Smarter Access Control platform.
Two reader interfaces provide control for one supervised
physical barrier or two unsupervised physical barriers.
For UL compliance, the Power Sourcing Equipment (PSE), such as
a PoE enabled network switch and/or PoE power injectors, must be
UL Listed under UL294B.
Reader port 1 can accommodate a Wiegand reader and
provides LED and buzzer control. This port can alternatively
utilize a two-wire RS-485 bus to connect up to eight
Alarm.com expansion modules. Reader port 2 can
accommodate a Wiegand reader and provides LED
and buzzer control.
Two Form-C contact relay outputs may be used to control
locking hardware. The relay contacts are rated at 2A @
provided may be used for monitoring door position switches
as unsupervised or supervised. The ADC-ACC1-17 requires
Power over Ethernet (PoE) or 12V DC for power.
The ADC-ACC1-17 may be mounted in a 3-gang switch box;
on the provided mounting plate, or in an enclosure. The
supplied mounting plate has mounting holes that match
the ADC-ACX1 mounting footprint.
The SRAM is backed up by a rechargeable battery when input
power is removed. This battery should retain the data for
a minimum of 3 days. If data in the SRAM is determined to
cardholder data must be re-downloaded.
The initial charge of the battery may take up to 48 hours
to be fully charged.

2| Door Controller
ADC-ACC1-17 Hardware
TB1 TB2 TB3
1 1 1 12V
PoE
J3
TB5
1
TB4
1
3
4
S1
21
ON
S2
7 6 5 4 3 2 1
J7
J1
J4
J5
BT1
K1
J6
K2
TB1
TB5
RESET SWITCH
2.55” [64.77 mm] 2.55” [64.77 mm]
.15” [3.81 mm]
.20” [5.08 mm]
5.40” [137.16 mm]
2.35” [59.69 mm]
.20” [5.08 mm]
2.75” [69.85 mm]
TAMPER
SWITCH
CONNECTION
(J7)
ETHERNET
CONNECTOR
(J6)
PoE/12V DC
POWER SELECTOR
JUMPER (J3)
DIP SWITCHES STATUS LEDs CHASSIS GND
Ø .125”
[Ø3.175 mm]
RELAY 1 LED
RELAY 2 LED

ADC-ACC1-17 Installation Guide | 3
Wiring and DIP Switch Setup
IN1 Input 1
IN2 Input 2
VO Reader 1 Power Output – 12V DC
LED Reader 1 LED Output
BZR Reader 1 Buzzer Output
CLK Reader 1 CLK/Data 1/TR+
DAT Reader 1 DAT/Data 0/TR-
GND Reader 1 Ground
LED Reader 2 LED Output
BZR Reader 2 Buzzer Output
CLK Reader 2 CLK/Data 1 Input
DAT Reader 2 DAT/Data 0 Input
VO Auxiliary Power Output – 12V DC
GND Auxiliary Power Output Ground
VIN Input Power – 12V DC (from local power supply)
GND Input Power Ground
NO Relay K1 – Normally Open Contact
1-C Relay K1 – Common Contact
NC Relay K1 – Normally Closed Contact
NO Relay K2 – Normally Open Contact
2-C Relay K2 – Common Contact
NC Relay K2 – Normally Closed Contact
Jumpers Set At Description
PoE ADC-ACC1-17 powered from the Ethernet connection
12V
ADC-ACC1-17 powered from a local 12V DC
power source connected to TB4-3 (VIN),
TB4-4 (GND)
Cabinet Tamper Switch Input: short = tamper secure
CONNECTIONS
JUMPERS

4| Door Controller
DIP SWITCHES
the ADC-ACC1-17 processor. DIP switches are read on
power-up except where noted. Pressing the reset button
(S2) causes the ADC-ACC1-17 to reboot.
All other switch settings are unassigned and reserved
for future use.
OFF OFF OFF OFF Normal operating mode.
ON X X X After initialization, enable default
User Name (admin) and Password
(password). The switch is read on the
section for additional information.
OFF ON XOFF Use installer network settings:
IP address: 192.168.0.251
Subnet Mask: 255.255.0.0
Default Gateway: 192.168.0.1
DNS Server: 192.168.0.1
Host port: IP server, port 3001,
communication address: 0
ON ON XOFF Use Alarm.com plug-and-play
network settings:
DHCP Enabled
Automatically obtain DNS server address
Connection Type: IP Client
Data Security: TLS Required
Host IP: mercury.g4c5j.com
Port Number: 7001
Connection Mode: Continuous
Retry Interval: 5 sec
X X ON XDisable TLS security.
The controller will not interact
with Alarm.com in this state.

ADC-ACC1-17 Installation Guide | 5
RUNNING
Status LEDS
All LEDs OFF
LEDs 1, 2, 3, 4, 5, 6, and 7 are sequenced
during initialization. LEDs 1, 3, and 4 are turned ON for
approximately 1.5 seconds after the hardware initialization
has completed, then the application code is initialized. The
amount of time the application takes to initialize depends
on the size of the database, about 3 seconds without a
card database. Each set of 10,000 cards will add about 3
seconds to the application initialization. When LEDs 1, 2,
this state.
If the sequence stops or repeats, perform the Bulk Erase
If clearing the memory does not correct the initialization
problem, contact technical support.
LED Description
Connecting to Alarm.com =
Connected to Alarm.com =
Alarm.com Communication Activity
Readers (combined):
Clock/Data or D1/D0 Mode = Flashes when Data is
Received, Either Input.
RS-485 Mode = Flashes when Transmitting Data
Input IN1 Status:
OFF = Inactive,
ON = Active, Flash = Trouble See Note 1
Input IN2 Status:
OFF = Inactive,
ON = Active, Flash = Trouble See Note 1
Cabinet Tamper
Reserved

6| Door Controller
Bulk Erase Configuration Memory
The bulk erase function can be used for the
following purposes:
•
database information
• Recover from database corruption causing
ADC-ACC1-17 board to continuously reboot
If clearing the memory does not correct the initialization
problem, contact technical support.
BULK ERASE STEPS
Do not remove power during steps 1-8.
1 Set S1 dip switches to: 1 & 2 “ON”, 3 & 4 “OFF”.
2 Press the reset button (S2) next to the DIP switches.
3
a 0.5 second rate.
4 Within 10 seconds of powering up, change switches
1 and 2 to “OFF”.
5
memory is being erased.
6 Full memory erase takes up to 60 seconds.
7
8 The ADC-ACC1-17 board will reboot 8 seconds after
this time).

ADC-ACC1-17 Installation Guide | 7
Input Power
The ADC-ACC1-17 may be powered by one of two ways.
Use jumper J3 to select the input power source:
• Power over Ethernet (PoE) connection, fully compliant
to IEEE 802.3af, or
• Local 12V DC power supply wired to TB4-3 (VIN),
TB4-4 (GND)
Reader & Expansion Module Wiring
Reader port 1 can be used to wire either one Wiegand
reader or up to eight Alarm.com expansion modules.
Reader port 2 can be used to wire one Wiegand reader.
Power is supplied to reader port 1 at 12V DC at 180 mA
maximum. The reader connected to reader port 2 may be
powered from the 12V DC auxiliary power output; TB4-1
high current requirements should be powered separately.
cabling requirements.
Reader port 1 can support up to eight Alarm.com expansion
modules using a 2-wire RS-485 bus. The maximum cable
length is 2,000 ft. (610 m).
For readers with two LED wires, only connect the wire
controlling the green LED to the ADC-ACC1-17.
When powering expansion modules and peripherals from
the ADC-ACC1-17, be cautious not to exceed 650 mA @
12V DC. 22 AWG minimum recommended for readers.

8| Door Controller
VO (12 Vdc)
GND
DAT
CLK
1
OSDP PROTOCOL DEVICE
9600 BAUD
ADDRESS 0
1
TB2
VO (12V DC)
GND
LED
BZR
CLK/D1
DAT/D0
TB3
1
BZR
DAT/D0
CLK/D1
LED
SECOND READER PORT
1
TB4
GND
VIN
GND
VO
BZR
1
GND
GND
VIN
VO
DAT/D0
CLK/D1
1
LED
LED
BZR
FIRST READER PORT
1
BZR
VO
DAT/D0
CLK/D1
LED
GND
VIN
GND
TB4
TB3
1
VO (12 Vdc)
CLK
LED
BZR
GND
DAT
TB2
1
REMOTE SERIAL I/O MODULEREMOTE SERIAL I/O MODULE
MR16in
MR16out
FOR EXAMPLE:
MRDT
MR50
MR52
GND
GND
12 Vdc
TR+
TR-
MRDT
FOR EXAMPLE:
MR50
MR16out
MR16in
MR52
GND
TR+
12 Vdc
GND
TR-
OSDP PROTOCOL DEVICE
ADDRESS 1
9600 BAUD
TR+
TR-
FIRST READER PORT
REFER TO THE APPROPRIATE REMOTE SERIAL I/O DEVICE INSTALLATION MANUAL FOR
ADDRESS AND BAUD RATE SETTINGS. DO NOT TERMINATE ANY OF THE DEVICES ON
THE RS-485 MULTI-DROP COMMUNICATION BUS. EACH REMOTE SERIAL I/O DEVICE
MUST BE CONFIGURED WITH AN UNIQUE COMMUNICATION ADDRESS. A MAXIMUM OF
EIGHT REMOTE SERIAL I/O DEVICES MAY BE CONNECTED TO READER PORT 1.
REFER TO THE APPROPRIATE REMOTE SERIAL I/O DEVICE INSTALLATION MANUAL FOR
ADDRESS AND BAUD RATE SETTINGS. DO NOT TERMINATE ANY OF THE DEVICES ON
THE RS-485 MULTI-DROP COMMUNICATION BUS. EACH OSDP DEVICE MUST BE
CONFIGURED WITH AN UNIQUE COMMUNICATION ADDRESS. A MAXIMUM OF TWO OSDP
DEVICES MAY BE CONNECTED TO READER PORT 1.
(12V DC)
+12 Vdc
D1
GROUND
DO (GREEN LED)
F/2F Reader
1
TB2
VO (12 Vdc)
GND
LED
BZR
CLK/D1
DAT/D0
+12 Vdc
D1
GROUND
DO (GREEN LED)
F/2F Reader
NORMALLY CLOSED CONTACT *
DOOR MONITOR SWITCH
REQUEST TO EXIT SWITCH
NORMALLY OPEN CONTACT *
1K,1%
1K,1%
1K,1%
1K,1%
1
VO (12 Vdc)
GND
LED
BZR
CLK/D1
DAT/D0
TB2
1
BZR
DAT/D0
CLK/D1
LED
1
GND
VIN
GND
VO
+12 Vdc
D1
GROUND
DO (GREEN LED)
F/2F Reader
1K,1%
1K,1%
1K,1%
1K,1%
TB3
1
BZR
DAT/D0
CLK/D1
LED
1
TB4
GND
VIN
GND
VO +12 Vdc
D1
GROUND
DO (GREEN LED)
F/2F Reader
SECOND READER PORT
FIRST READER PORT
FIRST READER PORT
SECOND READER PORT
TB3
TB4
DOOR MONITOR SWITCH
NORMALLY CLOSED CONTACT *
REQUEST TO EXIT SWITCH
NORMALLY OPEN CONTACT *
(DEFAULT) (DEFAULT)
FIRST READER PORT
TB4
TB3
TB2
FIRST READER PORT
GND
GND
12 Vdc
TR+
TR-
GND
TR+
12 Vdc
GND
TR-
TR+
TR-
FIRST READER PORT
1K,1%
1K,1%
1K,1%
1K,1%
Standard Supervised Circuit,
Normally Closed Contact
Standard Supervised Circuit,
Normally Open Contact
Unsupervised Circuit,
Normally Open Contact
Unsupervised Circuit,
Normally Closed Contact
IN2
IN1
TB1
1
}
+
-
DC STRIKE
DIODE
or MOV
TB5
2-C
NC
NC
NO
1
NO
1-C
TO DC POWER
SOURCE
-
+
AC STRIKE
MOV
FUSE
TB5
1
NO
1-C
NC
NC
NO
2-C
AC
TRANSFORMER
TB1 TB2 TB3
1 1 1 12V
PoE
J3
TB5
1
TB4
1
3
4
S1
21
ON
S2
7 6 5 4 3 2 1
J7
J1
J4
J5
BT1
K1
J6
K2
TB1
TB5
RESET SWITCH
.15” [3.81 mm] 2.55” [64.77 mm] 2.55” [64.77 mm] .15” [3.81 mm]
.20” [5.08 mm]
5.40” [137.16 mm]
2.35” [59.69 mm]
.20” [5.08 mm]
2.75” [69.85 mm]
TAMPER
SWITCH
CONNECTION
(J7)
ETHERNET
CONNECTOR
(J6)
PoE/12V DC
POWER SELECTOR
JUMPER (J3)
DIP SWITCHES STATUS LEDs CHASSIS GND
Ø .125” [Ø3.175 mm]
6 PL
SOLDER SIDE
RELAY K1 LED
RELAY K2 LED
FIELD WIRING
EP1501 WITH INCLUDED
MOUNTING PLATE
TO ETHERNET
NETWORK
OPTIONAL 3-GANG
JUNCTION BOX
OPTIONAL BLANK
COVER W/SCREWS
OPTIONAL MAGNETIC
TAMPER SWITCH
3.85 [97.8]
2.35 [59.7]
5.50 [139.7]
3.63 [92.1]
3.30 [83.8]
3.63 [92.1]
Ø0.16 [Ø4.0]
MR50 MGT HOLES
4PL
Ø0.16 [Ø4.0]
3-GANG MGT HOLES
4PL
VO (12 Vdc)
GND
DAT
CLK
1
OSDP PROTOCOL DEVICE
9600 BAUD
ADDRESS 0
1
TB2
VO (12V DC)
GND
LED
BZR
CLK/D1
DAT/D0
TB3
1
BZR
DAT/D0
CLK/D1
LED
SECOND READER PORT
1
TB4
GND
VIN
GND
VO
BZR
1
GND
GND
VIN
VO
DAT/D0
CLK/D1
1
LED
LED
BZR
FIRST READER PORT
1
BZR
VO
DAT/D0
CLK/D1
LED
GND
VIN
GND
TB4
TB3
1
VO (12 Vdc)
CLK
LED
BZR
GND
DAT
TB2
1
REMOTE SERIAL I/O MODULEREMOTE SERIAL I/O MODULE
MR16in
MR16out
FOR EXAMPLE:
MRDT
MR50
MR52
GND
GND
12 Vdc
TR+
TR-
MRDT
FOR EXAMPLE:
MR50
MR16out
MR16in
MR52
GND
TR+
12 Vdc
GND
TR-
OSDP PROTOCOL DEVICE
ADDRESS 1
9600 BAUD
TR+
TR-
FIRST READER PORT
REFER TO THE APPROPRIATE REMOTE SERIAL I/O DEVICE INSTALLATION MANUAL FOR
ADDRESS AND BAUD RATE SETTINGS. DO NOT TERMINATE ANY OF THE DEVICES ON
THE RS-485 MULTI-DROP COMMUNICATION BUS. EACH REMOTE SERIAL I/O DEVICE
MUST BE CONFIGURED WITH AN UNIQUE COMMUNICATION ADDRESS. A MAXIMUM OF
EIGHT REMOTE SERIAL I/O DEVICES MAY BE CONNECTED TO READER PORT 1.
REFER TO THE APPROPRIATE REMOTE SERIAL I/O DEVICE INSTALLATION MANUAL FOR
ADDRESS AND BAUD RATE SETTINGS. DO NOT TERMINATE ANY OF THE DEVICES ON
THE RS-485 MULTI-DROP COMMUNICATION BUS. EACH OSDP DEVICE MUST BE
CONFIGURED WITH AN UNIQUE COMMUNICATION ADDRESS. A MAXIMUM OF TWO OSDP
DEVICES MAY BE CONNECTED TO READER PORT 1.
(12V DC)
+12 Vdc
D1
GROUND
DO (GREEN LED)
F/2F Reader
1
TB2
VO (12 Vdc)
GND
LED
BZR
CLK/D1
DAT/D0
+12 Vdc
D1
GROUND
DO (GREEN LED)
F/2F Reader
NORMALLY CLOSED CONTACT *
DOOR MONITOR SWITCH
REQUEST TO EXIT SWITCH
NORMALLY OPEN CONTACT *
1K,1%
1K,1%
1K,1%
1K,1%
1
VO (12 Vdc)
GND
LED
BZR
CLK/D1
DAT/D0
TB2
1
BZR
DAT/D0
CLK/D1
LED
1
GND
VIN
GND
VO
+12 Vdc
D1
GROUND
DO (GREEN LED)
F/2F Reader
1K,1%
1K,1%
1K,1%
1K,1%
TB3
1
BZR
DAT/D0
CLK/D1
LED
1
TB4
GND
VIN
GND
VO +12 Vdc
D1
GROUND
DO (GREEN LED)
F/2F Reader
SECOND READER PORT
FIRST READER PORT
FIRST READER PORT
SECOND READER PORT
TB3
TB4
DOOR MONITOR SWITCH
NORMALLY CLOSED CONTACT *
REQUEST TO EXIT SWITCH
NORMALLY OPEN CONTACT *
(DEFAULT) (DEFAULT)
FIRST READER PORT
TB4
TB3
TB2
FIRST READER PORT
GND
GND
12 Vdc
TR+
TR-
GND
TR+
12 Vdc
GND
TR-
TR+
TR-
FIRST READER PORT
1K,1%
1K,1%
1K,1%
1K,1%
Standard Supervised Circuit,
Normally Closed Contact
Standard Supervised Circuit,
Normally Open Contact
Unsupervised Circuit,
Normally Open Contact
Unsupervised Circuit,
Normally Closed Contact
IN2
IN1
TB1
1
}
+
-
DC STRIKE
DIODE
or MOV
TB5
2-C
NC
NC
NO
1
NO
1-C
TO DC POWER
SOURCE
-
+
AC STRIKE
MOV
FUSE
TB5
1
NO
1-C
NC
NC
NO
2-C
AC
TRANSFORMER
TB1 TB2 TB3
1 1 1 12V
PoE
J3
TB5
1
TB4
1
3
4
S1
21
ON
S2
7 6 5 4 3 2 1
J7
J1
J4
J5
BT1
K1
J6
K2
TB1
TB5
RESET SWITCH
.15” [3.81 mm] 2.55” [64.77 mm] 2.55” [64.77 mm] .15” [3.81 mm]
.20” [5.08 mm]
5.40” [137.16 mm]
2.35” [59.69 mm]
.20” [5.08 mm]
2.75” [69.85 mm]
TAMPER
SWITCH
CONNECTION
(J7)
ETHERNET
CONNECTOR
(J6)
PoE/12V DC
POWER SELECTOR
JUMPER (J3)
DIP SWITCHES STATUS LEDs CHASSIS GND
Ø .125” [Ø3.175 mm]
6 PL
SOLDER SIDE
RELAY K1 LED
RELAY K2 LED
FIELD WIRING
EP1501 WITH INCLUDED
MOUNTING PLATE
TO ETHERNET
NETWORK
OPTIONAL 3-GANG
JUNCTION BOX
OPTIONAL BLANK
COVER W/SCREWS
OPTIONAL MAGNETIC
TAMPER SWITCH
3.85 [97.8]
2.35 [59.7]
5.50 [139.7]
3.63 [92.1]
3.30 [83.8]
3.63 [92.1]
Ø0.16 [Ø4.0]
MR50 MGT HOLES
4PL
Ø0.16 [Ø4.0]
3-GANG MGT HOLES
4PL
Reader Port 1: Typical Wiegand Reader
Reader Port 2: Typical Wiegand Reader
READER WIRING DIAGRAMS

ADC-ACC1-17 Installation Guide | 9
Reader Port 1: Wiring expansion modules using 2-wire RS-485
GND
DAT
CLK
ADC-ACC1-17
TR+
TR-
GND
ADC-ACX1
OR
ADC-ACX2
GND
TR-
TR+
GND
TR-
TR+
ADC-ACX1
OR
ADC-ACX2
USE TWISTED PAIR
24 AWG, 120 OHM
IMPEDANCE
CABLE WITH DRAIN AND
SHIELD WIRES. 2,000 FT.
(609 M) MAXIMUM
TOTAL LENGTH.
UP TO EIGHT TOTAL EXPANSION MODULES MAY
BE WIRED. THE LAST EXPANSION MODULE ON THE
BUS MUST HAVE JUMPER J5 INSTALLED FOR
ADCACX2 MODULES AND J4 INSTALLED FOR
ADCACX1 MODULES.
For ease of install, daisy chain expansion modules together. Wire each
expansion module to the next module instead of wiring directly back to
the controller.

10 | Door Controller
Relay Wiring
Two Form-C contact relays are provided for controlling door
lock mechanisms. The relay contacts are rated at 2A @ 30V
pole (C), a Normally Open pole (NO), and a Normally
Closed pole (NC).
When momentarily delivering power to unlock the locking
hardware (fail secure), the Normally Open and Common
poles are used. When momentarily removing power to
unlock the locking hardware (fail safe), the Normally Closed
and Common poles are used. Check with local building
codes for proper egress door installation.
Door lock mechanisms can generate EMF feedback to the
relay circuit that can cause damage and premature failure
of the relay. For this reason, it is recommended that either
a diode or MOV (metal oxide varistor) be used to protect
the relay.
From the Auxiliary output, the ADC-ACC1-17 can provide
12V DC power for external devices, provided 650 mA is not
power supply is used, it must be UL Listed Class 2 rated. 18
AWG minimum recommended for electric locking hardware.
VO (12 Vdc)
GND
DAT
CLK
1
OSDP PROTOCOL DEVICE
9600 BAUD
ADDRESS 0
1
TB2
VO (12V DC)
GND
LED
BZR
CLK/D1
DAT/D0
TB3
1
BZR
DAT/D0
CLK/D1
LED
SECOND READER PORT
1
TB4
GND
VIN
GND
VO
BZR
1
GND
GND
VIN
VO
DAT/D0
CLK/D1
1
LED
LED
BZR
FIRST READER PORT
1
BZR
VO
DAT/D0
CLK/D1
LED
GND
VIN
GND
TB4
TB3
1
VO (12 Vdc)
CLK
LED
BZR
GND
DAT
TB2
1
REMOTE SERIAL I/O MODULEREMOTE SERIAL I/O MODULE
MR16in
MR16out
FOR EXAMPLE:
MRDT
MR50
MR52
GND
GND
12 Vdc
TR+
TR-
MRDT
FOR EXAMPLE:
MR50
MR16out
MR16in
MR52
GND
TR+
12 Vdc
GND
TR-
OSDP PROTOCOL DEVICE
ADDRESS 1
9600 BAUD
TR+
TR-
FIRST READER PORT
REFER TO THE APPROPRIATE REMOTE SERIAL I/O DEVICE INSTALLATION MANUAL FOR
ADDRESS AND BAUD RATE SETTINGS. DO NOT TERMINATE ANY OF THE DEVICES ON
THE RS-485 MULTI-DROP COMMUNICATION BUS. EACH REMOTE SERIAL I/O DEVICE
MUST BE CONFIGURED WITH AN UNIQUE COMMUNICATION ADDRESS. A MAXIMUM OF
EIGHT REMOTE SERIAL I/O DEVICES MAY BE CONNECTED TO READER PORT 1.
REFER TO THE APPROPRIATE REMOTE SERIAL I/O DEVICE INSTALLATION MANUAL FOR
ADDRESS AND BAUD RATE SETTINGS. DO NOT TERMINATE ANY OF THE DEVICES ON
THE RS-485 MULTI-DROP COMMUNICATION BUS. EACH OSDP DEVICE MUST BE
CONFIGURED WITH AN UNIQUE COMMUNICATION ADDRESS. A MAXIMUM OF TWO OSDP
DEVICES MAY BE CONNECTED TO READER PORT 1.
(12V DC)
+12 Vdc
D1
GROUND
DO (GREEN LED)
F/2F Reader
1
TB2
VO (12 Vdc)
GND
LED
BZR
CLK/D1
DAT/D0
+12 Vdc
D1
GROUND
DO (GREEN LED)
F/2F Reader
NORMALLY CLOSED CONTACT *
DOOR MONITOR SWITCH
REQUEST TO EXIT SWITCH
NORMALLY OPEN CONTACT *
1K,1%
1K,1%
1K,1%
1K,1%
1
VO (12 Vdc)
GND
LED
BZR
CLK/D1
DAT/D0
TB2
1
BZR
DAT/D0
CLK/D1
LED
1
GND
VIN
GND
VO
+12 Vdc
D1
GROUND
DO (GREEN LED)
F/2F Reader
1K,1%
1K,1%
1K,1%
1K,1%
TB3
1
BZR
DAT/D0
CLK/D1
LED
1
TB4
GND
VIN
GND
VO +12 Vdc
D1
GROUND
DO (GREEN LED)
F/2F Reader
SECOND READER PORT
FIRST READER PORT
FIRST READER PORT
SECOND READER PORT
TB3
TB4
DOOR MONITOR SWITCH
NORMALLY CLOSED CONTACT *
REQUEST TO EXIT SWITCH
NORMALLY OPEN CONTACT *
(DEFAULT) (DEFAULT)
FIRST READER PORT
TB4
TB3
TB2
FIRST READER PORT
GND
GND
12 Vdc
TR+
TR-
GND
TR+
12 Vdc
GND
TR-
TR+
TR-
FIRST READER PORT
1K,1%
1K,1%
1K,1%
1K,1%
Standard Supervised Circuit,
Normally Closed Contact
Standard Supervised Circuit,
Normally Open Contact
Unsupervised Circuit,
Normally Open Contact
Unsupervised Circuit,
Normally Closed Contact
IN2
IN1
TB1
1
}
+
-
DC STRIKE
DIODE
or MOV
TB5
2-C
NC
NC
NO
1
NO
1-C
TO DC POWER
SOURCE
-
+
AC STRIKE
MOV
FUSE
TB5
1
NO
1-C
NC
NC
NO
2-C
AC
TRANSFORMER
TB1 TB2 TB3
1 1 1 12V
PoE
J3
TB5
1
TB4
1
3
4
S1
21
ON
S2
7 6 5 4 3 2 1
J7
J1
J4
J5
BT1
K1
J6
K2
TB1
TB5
RESET SWITCH
.15” [3.81 mm] 2.55” [64.77 mm] 2.55” [64.77 mm] .15” [3.81 mm]
.20” [5.08 mm]
5.40” [137.16 mm]
2.35” [59.69 mm]
.20” [5.08 mm]
2.75” [69.85 mm]
TAMPER
SWITCH
CONNECTION
(J7)
ETHERNET
CONNECTOR
(J6)
PoE/12V DC
POWER SELECTOR
JUMPER (J3)
DIP SWITCHES STATUS LEDs CHASSIS GND
Ø .125” [Ø3.175 mm]
6 PL
SOLDER SIDE
RELAY K1 LED
RELAY K2 LED
FIELD WIRING
EP1501 WITH INCLUDED
MOUNTING PLATE
TO ETHERNET
NETWORK
OPTIONAL 3-GANG
JUNCTION BOX
OPTIONAL BLANK
COVER W/SCREWS
OPTIONAL MAGNETIC
TAMPER SWITCH
3.85 [97.8]
2.35 [59.7]
5.50 [139.7]
3.63 [92.1]
3.30 [83.8]
3.63 [92.1]
Ø0.16 [Ø4.0]
MR50 MGT HOLES
4PL
Ø0.16 [Ø4.0]
3-GANG MGT HOLES
4PL
Diode Selection:
• Diode current rating: 1x strike current
• Diode breakdown voltage: 4x strike voltage
• For 12V DC or 24V DC strike,
diode 1N4002 (100V/1A) typical
RELAY CIRCUIT WIRING DIAGRAMS
MOV Selection:
• Clamp voltage: 1.5x V AC RMS
• Use UL recognized MOV with appropriate ratings

ADC-ACC1-17 Installation Guide | 11
VO (12 Vdc)
GND
DAT
CLK
1
OSDP PROTOCOL DEVICE
9600 BAUD
ADDRESS 0
1
TB2
VO (12V DC)
GND
LED
BZR
CLK/D1
DAT/D0
TB3
1
BZR
DAT/D0
CLK/D1
LED
SECOND READER PORT
1
TB4
GND
VIN
GND
VO
BZR
1
GND
GND
VIN
VO
DAT/D0
CLK/D1
1
LED
LED
BZR
FIRST READER PORT
1
BZR
VO
DAT/D0
CLK/D1
LED
GND
VIN
GND
TB4
TB3
1
VO (12 Vdc)
CLK
LED
BZR
GND
DAT
TB2
1
REMOTE SERIAL I/O MODULEREMOTE SERIAL I/O MODULE
MR16in
MR16out
FOR EXAMPLE:
MRDT
MR50
MR52
GND
GND
12 Vdc
TR+
TR-
MRDT
FOR EXAMPLE:
MR50
MR16out
MR16in
MR52
GND
TR+
12 Vdc
GND
TR-
OSDP PROTOCOL DEVICE
ADDRESS 1
9600 BAUD
TR+
TR-
FIRST READER PORT
REFER TO THE APPROPRIATE REMOTE SERIAL I/O DEVICE INSTALLATION MANUAL FOR
ADDRESS AND BAUD RATE SETTINGS. DO NOT TERMINATE ANY OF THE DEVICES ON
THE RS-485 MULTI-DROP COMMUNICATION BUS. EACH REMOTE SERIAL I/O DEVICE
MUST BE CONFIGURED WITH AN UNIQUE COMMUNICATION ADDRESS. A MAXIMUM OF
EIGHT REMOTE SERIAL I/O DEVICES MAY BE CONNECTED TO READER PORT 1.
REFER TO THE APPROPRIATE REMOTE SERIAL I/O DEVICE INSTALLATION MANUAL FOR
ADDRESS AND BAUD RATE SETTINGS. DO NOT TERMINATE ANY OF THE DEVICES ON
THE RS-485 MULTI-DROP COMMUNICATION BUS. EACH OSDP DEVICE MUST BE
CONFIGURED WITH AN UNIQUE COMMUNICATION ADDRESS. A MAXIMUM OF TWO OSDP
DEVICES MAY BE CONNECTED TO READER PORT 1.
(12V DC)
+12 Vdc
D1
GROUND
DO (GREEN LED)
F/2F Reader
1
TB2
VO (12 Vdc)
GND
LED
BZR
CLK/D1
DAT/D0
+12 Vdc
D1
GROUND
DO (GREEN LED)
F/2F Reader
NORMALLY CLOSED CONTACT *
DOOR MONITOR SWITCH
REQUEST TO EXIT SWITCH
NORMALLY OPEN CONTACT *
1K,1%
1K,1%
1K,1%
1K,1%
1
VO (12 Vdc)
GND
LED
BZR
CLK/D1
DAT/D0
TB2
1
BZR
DAT/D0
CLK/D1
LED
1
GND
VIN
GND
VO
+12 Vdc
D1
GROUND
DO (GREEN LED)
F/2F Reader
1K,1%
1K,1%
1K,1%
1K,1%
TB3
1
BZR
DAT/D0
CLK/D1
LED
1
TB4
GND
VIN
GND
VO +12 Vdc
D1
GROUND
DO (GREEN LED)
F/2F Reader
SECOND READER PORT
FIRST READER PORT
FIRST READER PORT
SECOND READER PORT
TB3
TB4
DOOR MONITOR SWITCH
NORMALLY CLOSED CONTACT *
REQUEST TO EXIT SWITCH
NORMALLY OPEN CONTACT *
(DEFAULT) (DEFAULT)
FIRST READER PORT
TB4
TB3
TB2
FIRST READER PORT
GND
GND
12 Vdc
TR+
TR-
GND
TR+
12 Vdc
GND
TR-
TR+
TR-
FIRST READER PORT
1K,1%
1K,1%
1K,1%
1K,1%
Standard Supervised Circuit,
Normally Closed Contact
Standard Supervised Circuit,
Normally Open Contact
Unsupervised Circuit,
Normally Open Contact
Unsupervised Circuit,
Normally Closed Contact
IN2
IN1
TB1
1
}
+
-
DC STRIKE
DIODE
or MOV
TB5
2-C
NC
NC
NO
1
NO
1-C
TO DC POWER
SOURCE
-
+
AC STRIKE
MOV
FUSE
TB5
1
NO
1-C
NC
NC
NO
2-C
AC
TRANSFORMER
TB1 TB2 TB3
1 1 1 12V
PoE
J3
TB5
1
TB4
1
3
4
S1
21
ON
S2
7 6 5 4 3 2 1
J7
J1
J4
J5
BT1
K1
J6
K2
TB1
TB5
RESET SWITCH
.15” [3.81 mm] 2.55” [64.77 mm] 2.55” [64.77 mm] .15” [3.81 mm]
.20” [5.08 mm]
5.40” [137.16 mm]
2.35” [59.69 mm]
.20” [5.08 mm]
2.75” [69.85 mm]
TAMPER
SWITCH
CONNECTION
(J7)
ETHERNET
CONNECTOR
(J6)
PoE/12V DC
POWER SELECTOR
JUMPER (J3)
DIP SWITCHES STATUS LEDs CHASSIS GND
Ø .125” [Ø3.175 mm]
6 PL
SOLDER SIDE
RELAY K1 LED
RELAY K2 LED
FIELD WIRING
EP1501 WITH INCLUDED
MOUNTING PLATE
TO ETHERNET
NETWORK
OPTIONAL 3-GANG
JUNCTION BOX
OPTIONAL BLANK
COVER W/SCREWS
OPTIONAL MAGNETIC
TAMPER SWITCH
3.85 [97.8]
2.35 [59.7]
5.50 [139.7]
3.63 [92.1]
3.30 [83.8]
3.63 [92.1]
Ø0.16 [Ø4.0]
MR50 MGT HOLES
4PL
Ø0.16 [Ø4.0]
3-GANG MGT HOLES
4PL
Input Wiring
Inputs are used to monitor door position switches or
unsupervised or supervised. When unsupervised, reporting
consists of only the open or closed states.
not only open and closed but also open circuit, shorted,
grounded*, and foreign voltage*. A supervised input circuit
requires two resistors be added to the circuit to facilitate
proper reporting. The standard supervised circuit requires
1k ohm, 1% resistors, and should be located as close to the
sensor as possible.
*Grounded and foreign voltage states are not a requirement of UL 294
22 AWG minimum required for input wiring. 18 AWG
recommended if wiring request-to-exit devices in series with
locking hardware.
but may not be typical:
TB5
2-C
NC
NC
NO
1
NO
1-C
TO DC POWER
SOURCE
DC MAG LOCK

12 | Door Controller
Specifications
The interface is for use in low voltage, Class 2 circuits only.
The installation of this device must comply with all local
INPUT POWER
PoE or 12V DC, 900 mA max.
OUTPUT POWER
650 mA @ 12V DC
INPUTS
One dedicated reader input
One switchable reader/two-wire RS-485 input
Two programmable inputs
One dedicated tamper input
OUTPUTS
Two relay outputs (2A @ 30V DC)
Single-wire LED control
Single-wire buzzer output
CERTIFICATIONS
HSPD-12/FIPS201 compliant
UL 294 and UL 294B recognized
ROHS
FCC Part 15 Class A
Without Bracket: 5.5 x 2.75 x 0.96” (140 x 70 x 24 mm)
With Bracket: 5.5 x 3.63 x 1.33” (140 x 92 x 34 mm)
TEMPERATURE
32°F – 158°F (0 – 70°C) operational
-67°F – 185°F (-55 – 85°C) storage
OPERATING HUMIDITY
10-95% (non-condensing) RH

ADC-ACC1-17 Installation Guide | 13
WARRANTY
Mercury Security warrants the product is free from defects in material and workmanship under
normal use and service with proper maintenance for one year from the date of factory shipment.
Mercury Security assumes no responsibility for products damaged by improper handling or
installation. This warranty is limited to the repair or replacement of the defective unit.
There are no expressed warranties other than set forth herein. Mercury Security does
not make, nor intends, nor does it authorize any agent or representative to make any other
warranties, or implied warranties, and expressly excludes and disclaims all implied warranties
Returns must be accompanied by a Return Material Authorization (RMA) number obtained
from customer service, and prepaid postage and insurance.
LIABILITY
The Interface should only be used to control exits from areas where an alternative method for
exit is available. This product is not intended for, nor is rated for operation in life-critical control
applications. Mercury Security is not liable under any circumstances for loss or damage caused
by or partially caused by the misapplication or malfunction of the product. Mercury Security’s
liability does not extend beyond the purchase price of the product.
This device complies with part 15 of the FCC Rules. Operation is subject to the following
two conditions: (1) This device may not cause harmful interference, and (2) this device must
accept any interference received, including interference that may cause undesired operation.

© 2018 Alarm.com. All rights reserved.
8281 Greensboro Drive, Suite 100
Tysons, VA 22102 180207
Table of contents
Popular Controllers manuals by other brands

PlugTech
PlugTech MBC-NULL operating instructions

Smartgen
Smartgen HAT552 user manual

Piedmont
Piedmont LT-3600RF manual

BERMAD
BERMAD Omega Installation and operation guide

TIANJIN BAILI ERTONG MACHINERY
TIANJIN BAILI ERTONG MACHINERY QBR3 Operation manual

Zennio
Zennio MAXinBOX FANCOIL 4CH2P Technical documentation

National Instruments Corporation
National Instruments Corporation FieldPoint cFP-20 Series quick start guide

Unitronics
Unitronics Vision V120 user guide

Eaton
Eaton CDAE-01/04 Installation

Emerson
Emerson Dixell Wing XW570L Installing and operating instructions

Rain Bird
Rain Bird E-6C user manual

Datakom
Datakom DKG-379 manual