
The device is intelligent sensors that utilize a state-of-the-art thermistor sensing circuit for fast response.
These sensors are designed to provide open area protection with 50 foot spacing capability.
The device is a rate-of-rise temperature sensor with 135°F fixed temperature alarm.
The device is a rate-of-rise with fixed temperature alarm thermal detector utilizing a state-of-the-art dual
thermistor sensing circuit.
These detectors are designed to provide open area protection with 50-foot spacing capability, and are to be
used with compatible control panels only.
Two LEDs on each detector light to provide 360° visibility of the detector indication.
The device include a tamper-resistant capability that prevents their removal from the bracket without the use of a tool
-Before testing, notify the proper authorities that the system is undergoing maintenance, and will tempo
rarely be out of service. Disable the system to prevent unwanted alarms.
-All sensors must be tested after installation and periodically thereafter.
- Testing methods must satisfy the Authority Having Jurisdiction (AHJ).
- Sensors offer maximum performance when tested and maintained in compliance with NFPA 72.
The sensor can be tested in the following ways:
-Direct Heat Method (Hair dryer of 1000 – 1500 watts)
From the side of the detector, direct the heat toward the sensor.
-Hold the heat source about 6 inches (15cm) away to prevent damage to the cover during testing.
-The LEDs on the detector should light when the temperature at the detector reaches the
alarm set point.
-If the LEDs fail to light, check the power to the detector and the wiring in the detector base.
-Reset the detector at the system control panel.
-Detectors that fail these tests should be cleaned as described under MAINTENANCE and retested.
If the detectors still fail these tests they should be returned for repair.
NOTE: Before cleaning notify the proper authorities that the system is undergoing maintenance, and therefore
the system will temporarily be out of service. Disable the loop or system undergoing maintenance to prevent
unwanted alarms.
It is recommended that the sensor be removed from its mounting base for easier cleaning and that sensors
be cleaned at least once a year. Use a vacuum cleaner to remove dust from the sensing chamber
-
-
-
-
-
-
-
intelligent solutions
intelligent solutions