Alpha Communications TekTone CM800 Manual

ALPHA COMMUNICATIONS® • 42 Central Drive • Farmingdale, NY 11735-1202
Toll-Free Technical Line: 1-800-666-4800 • Phone: (631) 777-5500 • Fax: (631) 777-5599
CM800/CM900
Emergency Call Signaling System
Installation & Operating Instructions
IL514
Section C
Rev.13 -5/2011
Contents
System Installation............................................................. 1
Installation Procedure......................................................1
Equipment Locations .......................................................1
Wiring Installation ...........................................................2
Housing Installation ........................................................2
Wire Checkout .................................................................2
Connections Checkout ....................................................2
System Operating Instructions ......................................... 7
CM800,CM900Annunciators .........................................7
SF117-,SF118-seriesEmergencyCallStations ................7
SF154EmergencyCallStation .........................................7
IR019,IR019BRemoteAnnunciatorToneSpeakers ........7
LI381CorridorLight.........................................................7
LI382,LI382LEDCorridorLights .....................................7
LI118B,LI123BCorridorLights .......................................7
BE005,BE007CorridorBells ............................................7
Illustrations
Figure 1—Master Panel Housing Chart and
Wall Cut-Out Details...............................................3
Figure2—RingandBackBoxforSF117series,SF118
series and SF154 Emergency Call Stations .............3
Figure3—RingandBack Box forIR019&IR019B
ToneSpeakers,andLI118B,LI123B,LI381,
LI382&LI382LEDCorridorLights .........................3
Figure 4—PK2019ATone Volume Shunt Settings.................3
Figure5—EmergencyCallHook-UpDiagram
withSF117/2series,SF118 series &
SF154 Emergency Switches, and
LI381&LI118B CorridorLights ..............................4
Figure6—EmergencyCallHook-UpDiagramwith
SF117/4 series Continuous Duty Door Release,
LI381CorridorLight, LI123BCorridorLight
withBuzzer,andBE005Corridor Bell ......................5
Figure7—EmergencyCallHook-UpDiagramwith
SF117/2 series Continuous Duty Door Release,
LI381CorridorLight,SmokeDetector,
andBE007CorridorBell ..........................................6
Figure8—ConnectionDiagramforParallel
CM800Panels .........................................................6
SystemInstallation
Installation Procedure
• Read the following instructions concerning system equip-
ment, and determine installation methods before proceed-
ing.
• Determineequipmentlocations.
• Installwiring.
• Install housings.
• Checkwires.
• Connect equipment.
• Check connections.
• Apply power.
• Check system operation.
Equipment Locations
CM800, CM900 Annunciator: Locate CM800 and CM900
Annunciators within easy reach of operating personnel.
Permittedoperatingtemperatureof10°C–30°Cmustnotbe
exceeded.
SF117series,SF118series,SF154EmergencyCallStations:
Locateemergencystationswhereconvenientforoperation.
Avoidareaswheredirectcontactwithwatermayoccur.The
SF117 series and SF118 series include a 6' long pull cord,
permitting installation high enough to provide easy opera-
tionbythestaffandby seatedorprone patients.TheSF154
isoperatedbymeansofapushbuttonlocatedonthestation.
IR019, IR019B Remote Annunciator Tone Speakers:Locate
annunciatortonespeakersasneededandwhereconvenient
for operation. Location must provide for unobstructed
visibilityofthetone-offindicator(IR019B).
LI118B,LI123B,LI381,LI382,LI382LEDCorridorLights:
Locate corridor lights in the corridor above or beside the
dooroftheassociatedrooms.Locationmustprovideunob-
structed visibility of the corridor light in both directions.
PK2019, PK2019A Control Unit: The PK2019 or PK2019A
maybesurfacemountedadjacenttotheSS106,ifnecessary.
If remotely located, cable run from PK2019/A to CM800/
CM900mustnotexceed100'.
PK601A Power Supply: Surface mount the PK601A adjacent
totheSS106andPK2019/A.
PK612ADCFlasher: Surface mount the PK612A adjacent to
theSS106andPK2019/A.

Page2• IL514 CM800/CM900Emergency Call SystemManual Copyright©TekToneSound& SignalMfg.,Inc.AllRightsReserved.
BE005/BE007CorridorBells:LocateBE005andBE007Cor-
ridorBellsincorridorabovedoorheight.Locationincorridor
willbedeterminedbythenumberofbellsrequiredoneach
floor.
SS106Transformer:LocateSS106inanaccessibleareaneara
source of 117 VAC. Observe local codes.
Wiring Installation
Run wiring conduit from corridor light to corridor light and
terminate at the CM800 or CM900 annunciator panel. Select
conduit size according to the application, as shown in wiring
diagrams in this booklet. Observe local codes.
PK2019, PK2019A Options:
• For30-second delay before tone, connect terminal A to
terminalN.
• Forsteadytone,connectterminalWtoterminalN.Ifthe
annunciatorlampisflashing,thetonewillbeintermittent
despite terminal W connection.
Housing Installation
CM800, CM900 Annunciators:
Flush Wall Mount—Provide a wall cutout as shown in
Figure 1. Fit the back box and frame assembly into the
prepared opening. Fasten the assembly in place. Note:The
back box must be TekTone®OH200 Series.
Surface Wall Mount—Fasten the back box and frame
assembly to the wall through the holes provided in back of
the box, using suitable fasteners. Note: Back box must be
TekTone®OH300 Series.
SF117series,SF118series,SF154EmergencyCallStations:
Installsinglegangring(orsinglegangringanddoublegang
box) as shown in Figure 2 for each emergency call station
insystem.Minimumdimensionsofbackboxmustnotbeless
than4"×4"×1.5".Minimumopeningonringmustnotbeless
than1.75"×2.75".Minimumclearancefromlivepartsofthe
station to dead metal parts must not be less than 0.5".
IR019, IR019B Remote Annunciator Tone Speakers: Install
doublegangring(ordoublegangringanddoublegangbox)
as shown in Figure 3for each tone speaker station. Mini-
mum dimensions of back box must not be less than
4"×4"×1.5".
LI118B,LI123BCorridorLights:Installdoublegangring(or
double gang ring and double gang box) as shown in Fig-
ure 3foreachtonespeakerstation.Minimumdimensionsof
back box must not be less than 4"×4"×1.75".
LI381, LI382 Corridor Lights: Install double gang ring (or
double gang ring and double gang box) as shown in Fig-
ure 3foreachcorridorlight.Minimumdimensionsofback
boxmustnotbelessthan4"×4"×1.5".Minimumopeningon
ringmustnotbelessthan2.75"×2.75".Minimumclearance
fromlivepartsofthestationtodeadmetalpartsmustnotbe
less than 0.5".
LI382LEDCorridorZoneLight:Installstandardone-ortwo-
gang box with one- or two-gang ring as shown in Figure 3
foreachtonespeakerstation.Minimumclearancefromlive
partsofthestation to deadmetalpartsmustnot be lessthan
0.5".
BE005,BE007CorridorBells:Install astandard4"BellBox.
Wire Checkout
Use an ohmmeter or other continuity checking device to test
wires for shorts or grounds. If shorts or grounds are
encountered, find and correct the problems before continuing.
Make sure the minimum number of conductors that are needed
for all of the equipment being used in the system are available.
Connections Checkout
Re-check all connections to equipment. If all wires and
connections are satisfactory, connect the primary coil of the
SS106Transformerto a sourceof117VAC60 Hz (30VAmax.).

IL514CM800/CM900Emergency Call SystemManual • Page3
Copyright©TekToneSound& Signal Mfg.,Inc.AllRights Reserved.
Figure 1—Master Panel Housing Chart and Wall Cut-Out Details
Housing Wall Opening
Flush Surface Width (B) Height
OH202 OH302 8.5" 16.25"
OH203 OH303 12.5" 16.25"
OH204 OH304 16.5" 16.25"
OH205 OH305 20.5" 16.25"
Figure 2—Ring and Back Box for
SF117 series, SF118 series and SF154
Emergency Call Stations
Install ring with panel mounting holes at top and bottom, as shown.
Figure 3—Ring and Back Box for
IR019 & IR019B Tone Speakers, and
LI118B,LI123B,LI381,LI382&LI382LED
CorridorLights
Install ring with panel mounting holes at top and bottom, as shown.
16"
B
3.75"
Finished Wall
4" min.
16.25"
B
In masonry walls, install 0.5"×4" wood
fillers at top and bottom of opening for
housing attachment.
B
Finished Floor
66"
16.25"
Figure 4—PK2019A Tone Volume Shunt Settings
Low Medium High

Page4• IL514 CM800/CM900Emergency Call SystemManual Copyright©TekToneSound& SignalMfg.,Inc.AllRightsReserved.
Figure 5—Emergency Call Hook-Up Diagram with SF117/2 series, SF118 series &
SF154 Emergency Switches, and LI381 & LI118B Corridor Lights
IL514 General Wiring Figure 4 Rev4 110210 1
TONE
SPEAKER
R1
R2
R3
B
A
W
S
P
D
N
T1
T2
PK2019/A
Speaker
45 Ohm
Tone-Off
Lamp
Tone-Off
Button
IR019B
P
COMMON
COMMON
N
E
COMMON
LI381
DOME
LAMP
LI381
DOME
LAMP
SF118/2B
Call Placed
SF118/2(B/C)
Emergency Switch
LI118B
DOME
LAMP
w/ BUZZER
ANNUNCIATOR
LAMPS
TEST
BUTTON
#18 (optional, see Note 5)
FACTORY CONNECTED
NOTE: PM110/4N
Modules only!
PK2019/A
COMMON
R1
NORMALLY OPEN RELAY
OUTPUTS
R2 NORMALLY CLOSEDR3
B
A
WTONE-
OFF
LAMP
TONE-
OFF
BUTTON
#18
S
P
D
N
T1
T2
16 VAC SS106
TRANSFORMER
(See Note 1)
117 VAC
PK612A
(optional, see Note 5)
C
G
W
E
SF117/2(B,C)
or SF154
Emergency Switch
LI381
DOME
LAMP
SF117/2(B,C)
or SF154
Emergency Switch
SF117/2(B,C)
or SF154
Emergency Switch
SF117/2(B,C)
or SF154
Emergency Switch
Light
LI381
DOME
LAMP
SF118/4(B/C)
Call Placed
SF118/4(B/C)
Emergency Switch
Light
Door
Release
PK601A
T1
T2
D
F
SS106
TRANSFORMER
24VAC 117VAC
#18
#18
Wiring Diagram for IR019, IR019B and PK2019/A
(Disregard wiring for tone-off lamp if wiring IR019.)
1. Use 16 VAC connections on SS106 Transformer.
Notes:
2. Wiring may be #22 except where shown otherwise.
3. PK2019/A Annunciator Control Unit may be mounted
outside of annunciator enclosure.
4. Switches are shown in the OFF position.
5. PK612A and associated wiring is optional and needs
only to be installed if a flash common is needed.

IL514CM800/CM900Emergency Call SystemManual • Page5
Copyright©TekToneSound& Signal Mfg.,Inc.AllRights Reserved.
R1
R2
R3
B
A
W
S
P
D
N
T1
T2
#22
TO ADDITIONAL
EMERGENCY
SWITCHES
LI123B
LAMP
w/ BUZZER
DOOR RELEASE DOOR RELEASE
SF117/4(B,C)
EMERGENCY
SWITCH EMERGENCY
SWITCH
LI381
DOME
LAMP
+-+-
RECTIFIER
(See NOTE 9) RECTIFIER
(See NOTE 9)
BE005
CORRIDOR
BELL
24 VAC SS106
TRANSFORMER
(See NOTE 1)
TONE
SPEAKER
16 VAC
117 VAC
SS106
TRANSFORMER
ANNUNCIATOR LAMPS
TONE
OFF
BUTTON
TONE
OFF
LAMP
TEST BUTTON
FACTORY CONNECTED NOTE: PM110/4N MODULES ONLY
117 VAC
PK2019/A
SF117/4(B,C)
IL514 General Wiring Figure 5 Rev2 110210 1
1. Use 24 VAC connections on SS106 transformer. To calculate
Notes:
current requirements, add currents of all devices on at the
same time. Current requirements are as follows:
Corridor Lamp with buzzer– .16 amps
Corridor Bell– .2 amps
Door release– .3 amps
Annunciator lamp– .04 amps
2. Wiring must be #18 gauge except where shown otherwise.
8. Switches shown in the OFF position.
3. BE005 connects to emergency switch on the same floor only.
4. Door release (if used) must be 24 VDC continuous duty type.
5. Switch current capacity is 3 amps.
6. Power supply maximum current is 1 amp.
7. See Figure 4 for additional wiring details.
9. Rectifier RUFO® Model 1005 is not available from TekTone®.
Figure 6—Emergency Call Hook-Up Diagram with SF117/4 series Continuous Duty Door Release,
LI381 Corridor Light, LI123B Corridor Light with Buzzer, and BE005 Corridor Bell

Page6• IL514 CM800/CM900Emergency Call SystemManual Copyright©TekToneSound& SignalMfg.,Inc.AllRightsReserved.
Notes:
1. Use 24 VAC connections on SS106
transformer. To calculate current re-
quirements, add currents of all de-
vices on at the same time. Current
requirements are as follows:
CorridorLampwithbuzzer– .16 amps
Corridor Bell– .2 amps
Door release– .3 amps
Annunciator lamp– .04 amps
2. Wiring must be #18 gauge except
where shown otherwise.
3. BE007 connectstoemergency switch
on the same floor only.
4. Door release (if used) must be 24
VDC continuous duty type.
5. Switch current capacity is 3 amps.
6. Power supply maximum current is
1 amp.
7. See Figure 4 for more wiring details.
8. Switches shown in the OFF position.
9. Do not use same transformer for
PK2019/A and PK601A.
Figure 7—Emergency Call Hook-Up Diagram with SF117/2 series
Continuous Duty Door Release, LI381 Corridor Light,
Smoke Detector, and BE007 Corridor Bell
Figure 8—Connection Diagram for
Parallel CM800 Panels
Notes:
1. Use 16 VAC connections on SS106
Transformer.
2. Wiring may be #22 except where
shown otherwise.
3. PK2019/A Annunciator Control Unit
may be mounted outside of annun-
ciator enclosure.
C
G
W
E
#22
BE007
CORRIDOR
BELL
DOOR RELEASE
SF117/2(B,C)
EMERGENCY
SWITCH
TO ADDITIONAL
EMERGENCY
SWITCHES
SMOKE
DETECTOR
FACTORY
CONNECTED
ANNUNCIATOR
LAMPS
TONE
SPEAKER
TEST BUTTON
TONE-
OFF
LAMP TONE-
OFF
BUTTON
117 VAC
16 VAC SS106
TRANSFORMER
(SEE NOTE)
SS106
TRANSFORMER
16 VAC
117 VAC
PK612A
NOTE: PM110/4N
MODULES ONLY
T1
T2
D
F
PK2019/A
R1
R2
R3
B
A
W
S
P
D
N
T1
T2
PK601A
IL514 General Wiring Figure 6 Rev4 110210 1
R1
R2
R3
B
A
W
S
P
D
N
T1
T2
PK2019/A
TO STATIONS
R1
R2
R3
B
A
W
S
P
D
N
T1
T2
PK2019/A
IL514 General Wiring Figure 7 Rev1 110210 1
Common
Normally
Open
Normally
Closed
Common
Normally
Open
Normally
Closed
- # 18
SS106
Transformer
16 VAC
117 VAC
- # 18
SS106
Transformer
16 VAC
117 VAC
Tone
Off
Button
Tone
Off
Button Tone
Off
Lamp
Tone
Off
Lamp
Annunciator
Lamps
Panel 2
Annunciator
Lamps
Panel 1
Tone
Speaker Tone
Speaker
Panel 1 Panel 2

IL514CM800/CM900Emergency Call SystemManual • Page7
Copyright©TekToneSound& Signal Mfg.,Inc.AllRights Reserved.
SystemOperatingInstructions
System operators must read the following operating
instructions concerning system equipment and terms used in
conjunction with the equipment.
CM800, CM900 Annunciators
Answer Emergency Calls: Emergency calls are indicated by
simultaneous operation of the following signals:
• Steady illumination of the associated station selector
lamp,whichismarkedtoindicatecallorigin.
• Rapidly pulsating audible tone. The audible call signal
may be canceled by pressing the tone-off button. The
tone-off light will illuminate to indicate that tone is
silenced. Thetone-offbuttonmaybepressedatanytime
to verify operation of the tone-off lamp.
Callsignals may only be canceled at the point of origin,and
all calls must be answered in person.
TestStationAnnunciatorLamp(ifsoequipped):Onelamptest
button is provided on each panel of annunciator lamps.
Press the lamp test button—all annunciator lamps on that
panel should be illuminated.
ImproperOperation:IftheCM800orCM900Annunciatorfails
to operate as described, contact qualified maintenance
personnel.Ifa malfunctionoccursduringacall-in,causing
alackofindicationof call origin onthemasterstation,first
determinetheoriginofthecallbyobservingwhichcorridor
lightisilluminated,andtheninformqualified personnel.
SF117-, SF118-series Emergency Call Stations
Place an Emergency Call: Pull the call cord and wait for an
Attendant. (Note: The SF118 series station has a red call-
placed light that illuminates when the cord is pulled.)
Reset the Station: Push the slide switch up.
Improper Operation: If the station does not operate as de-
scribed, contact qualified personnel. There are no user
serviceable parts on SF117 series and SF118 series Emer-
gency Call Stations.
SF154 Emergency Call Station
Place an Emergency Call: Press the switch in so that the red
area of the switch is visible, and wait for an Attendant.
Reset the Station: Press the switch out so that the red area of
the switch is not visible.
Improper Operation: If the station does not operate as de-
scribed, contact qualified personnel. There are no user
serviceablepartsontheSF154EmergencyCallStation.
IR019, IR019B Remote Annunciator Tone Speakers
Emergency Calls: Emergency calls are indicated by a rapidly
pulsating audible tone. The audible tone signal can be
silenced by pressing the tone-off switch. (The IR019 is not
equippedwithatone-offlight.)TheIR019andIR019Btone
mimics the annunciator tone—either steady or pulsing.
Improper Operation: If the speaker does not operate as de-
scribed, contact qualified personnel. There are no user
serviceablepartsontheIR019andIR019BRemoteAnnun-
ciator Tone Speakers.
LI381 Corridor Light
Emergency Calls: Emergency calls are indicated by steady
illuminationofthecorridorlightassociatedwiththecalling
station.
Improper Operation: If the corridor light does not operate as
described,contactqualifiedservicepersonnel.Thereareno
userserviceablepartsontheLI381CorridorLight,otherthan
bulbs.
LI382, LI382LED Corridor Lights
Emergency Calls: Emergency calls are indicated by steady
illuminationofthecorridorlightassociatedwiththecalling
station. The second light can be used for other call types
initiatedfromthesamezone.
Improper Operation: If the corridor light does not operate as
described,contactqualifiedservicepersonnel.Thereareno
userserviceablepartsontheLI382CorridorLight,otherthan
bulbs.TherearenouserserviceablepartsontheLI382LED
CorridorLight.
LI118B, LI123B Corridor Lights
Emergency Calls: Emergency calls are indicated by steady
illumination of the corridor light and a steady buzzer.
Improper Operation: If the corridor light does not operate as
described,contactqualifiedservicepersonnel.Thereareno
user serviceable parts on the LI118 and LI123B Corridor
Lights, other than bulbs.
BE005, BE007 Corridor Bells
Emergency Calls: Emergency calls are indicated by a steady
ringing of the corridor bells.
Improper Operation: If the corridor bell does not operate as
described,contactqualifiedservicepersonnel.Thereareno
user serviceable parts on the BE005 and BE007 Corridor
Bells.

This manual suits for next models
1
Table of contents
Other Alpha Communications Control System manuals
Popular Control System manuals by other brands

Sel
Sel SEL-411L-2 manual

BRULA
BRULA BRULA NEO Installation and service instructions

Universal Remote Control
Universal Remote Control MX-3000 brochure

Compool
Compool Cp3810 Installation & operating instructions

CAME
CAME PS ONE installation manual

Roger Technology
Roger Technology H70 Series INSTRUCTIONS AND RECOMMENDATIONS FOR THE INSTALLER