Alphacool Heatmaster 2 User manual

Alphacool International GmbH
Heatmaster 2
Operating Manual

Heatmaster 2
1
Copyright
© Copyright 2011 Alphacool International GmbH. All rights including translation reserved. Analog and digital
reproduction of any kind, except a copy of the end user customer, requires the written permission of the
Alphacool International Gmbh. This manual is written according to the technical standards at the time of
printing.
Errors, emissions and printing errors excepted

Heatmaster 2
2
Contents
INTRODUCTION ________________________________________________________5
EXTENT OF DELIVERY___________________________________________________5
WARRANTY____________________________________________________________5
SAFETY NOTICE________________________________________________________6
INTENDED USE_________________________________________________________6
SYSTEM REQUIREMENTS________________________________________________6
SOCKET ASSIGNMENT __________________________________________________7
Overview _____________________________________________________________________________ 7
Power supply _________________________________________________________________________ 7
Fan channels / pumps / slow sensors _____________________________________________________ 7
Pumps______________________________________________________________________________ 8
Flow rate sensors _____________________________________________________________________ 8
Connection array ______________________________________________________________________ 8
USB________________________________________________________________________________ 8
HM BUS ____________________________________________________________________________ 9
Emergency shutdown__________________________________________________________________ 9
PC shut down ________________________________________________________________________ 9
NTC 1 -6 temperature sensors___________________________________________________________ 9
Water level __________________________________________________________________________ 9
LED 1 silent alarm ____________________________________________________________________ 9
LED 2 alarm _________________________________________________________________________ 9
LED 3 warning _______________________________________________________________________ 9
Relay 1-3 ___________________________________________________________________________ 9
Button 1-3 ___________________________________________________________________________ 9
Heatmaster reset _____________________________________________________________________ 9
5V Standby __________________________________________________________________________ 9
12V and 5V output ____________________________________________________________________ 9
INSTALLATION ________________________________________________________10
Hardware installation __________________________________________________________________ 10
Software installation___________________________________________________________________ 10
USE OF THE SOFTWARE________________________________________________16
General configuration _________________________________________________________________ 16

Heatmaster 2
3
Name _____________________________________________________________________________ 16
Temperature unit ____________________________________________________________________ 16
Language __________________________________________________________________________ 16
Data request interval__________________________________________________________________ 16
Switching time_______________________________________________________________________ 16
Display configuration__________________________________________________________________ 17
Brightness in sleep mode ______________________________________________________________ 17
Brightness of stand-by lighting __________________________________________________________ 17
Standby time________________________________________________________________________ 17
Fan configuration _____________________________________________________________________ 17
Name _____________________________________________________________________________ 17
Status _____________________________________________________________________________ 17
Speed monitoring ____________________________________________________________________ 17
Fan switch-off in case of failure _________________________________________________________ 17
Action in case of fan failure ____________________________________________________________ 17
Determine Min. / Max. speed ___________________________________________________________ 17
Speed factor ________________________________________________________________________ 18
Manual temperature control ____________________________________________________________ 18
Automatic temperature control __________________________________________________________ 18
Temperature sensors configuration______________________________________________________ 18
Name: _____________________________________________________________________________ 18
Status _____________________________________________________________________________ 18
Emergency shutdown_________________________________________________________________ 18
Settings____________________________________________________________________________ 18
Temperature values __________________________________________________________________ 19
Pump / flow rate sensor configuration____________________________________________________ 19
Name _____________________________________________________________________________ 19
Status _____________________________________________________________________________ 19
Type ______________________________________________________________________________ 19
Factor _____________________________________________________________________________ 19
Pump settings_______________________________________________________________________ 19
Flow rate sensor settings ______________________________________________________________ 19
Coolant level control configuration ______________________________________________________ 20
Name _____________________________________________________________________________ 20
Status _____________________________________________________________________________ 20
Type ______________________________________________________________________________ 20
Action in case of critical coolant level_____________________________________________________ 20
Orientation _________________________________________________________________________ 20
Alarm settings_______________________________________________________________________ 20
Calibrate analogue sensor now _________________________________________________________ 20
Online button / relay configuration_______________________________________________________ 20
Switching of a relay via a button_________________________________________________________ 20
Switching of a relay for a limited period of time _____________________________________________ 20
Action via button _____________________________________________________________________ 21
Temperature-triggered relay switching____________________________________________________ 21
Offline button / relay configuration_______________________________________________________ 21
Starting schedule ____________________________________________________________________ 21
Button / relay settings_________________________________________________________________ 21

Heatmaster 2
4
Temperature comparison configuration __________________________________________________ 22
Active _____________________________________________________________________________ 22
Name _____________________________________________________________________________ 22
Sensor 1 / Sensor 2 __________________________________________________________________ 22
SPECIAL NOTE ________________________________________________________22
Note regarding emergency shutdown ____________________________________________________ 22
Standard settings in the software________________________________________________________ 22
FAQ –Frequently asked questions ______________________________________________________ 22
EXPANDABILITY_______________________________________________________22
TROUBLESHOOTING ___________________________________________________23
TECHNICAL DATA _____________________________________________________23
DISPOSAL ____________________________________________________________23
APPENDIX ____________________________________________________________24
Expansion for Internet / LAN upgrade ____________________________________________________ 24
Master software control _______________________________________________________________ 24
E-Mail notifications ___________________________________________________________________ 24
Remote servicing via Internet___________________________________________________________ 24
Expansion for analogue adaptor_________________________________________________________ 24
Battery mount ________________________________________________________________________ 24
Mounting holes for the water block (optional expansion) ____________________________________ 24
A compatible water block is the water block alphacool Keatmaster 2 cooler (Item No. 11045)_____ 24

Heatmaster 2
5
Introduction
Dear customer,
we congratulate you on having purchased one of the most innovative and powerful controller units currently
available on the PC water cooling market. The Alphacool Heatmaster 2 was developed in Germany over
multiple years and constantly improved. Now, after a development and testing period of almost 3 years, we
introduce this unique product. The manufacturing process is completely done in Germany, hence ensuring
the highest possible quality and excellent quality control.
We have made this operating manual as extensive as possible, but with the many possibilities the Alphacool
Heatmaster 2 offers, we cannot exclude the possibility of questions still remaining unanswered. If you have
any questions, please contact us via the manufacturer homepage at www.Alphacool.com or via E-Mail at
A multitude of expansion possibilities is implemented into the hardware. Changes in the layout cannot be
excluded. Hence it is possible that the images in the manual may differ from the product, please excuse this
in advance.
Extent of delivery
The following items are included:
1x Alphacool Heatmaster 2
4x Temperature sensors with approx. 50 cm cable
1x Internal 4-Pin USB connection cable
1x Jumper
1x Mounting material
1x Short manual
Warranty
Data, drawings, images, technical data, weight, dimensions and feature descriptions provided in brochures,
catalogues, newsletters, advertisements or price lists, have only informative character. We take no
responsibility for the correctness of this data. Regarding the type and extent of the order only the information
provided with the order and order confirmation are determining.
1. If a defect covered by the warranty occurs, you have the right to demand supplementary
performance in the extent of the provisions of the law, to withdraw from the contract or to reduce the
purchase price. The statute of limitations on the warranty claims on the delivered items is two years
from receipt of the product if you are end user consumer ((§ 13 BGB). If you are an entrepreneur (§
14 BGB), this period is reduced to one year.
2. The warrant claim is only valid in combination with the invoice, sales slip or a confirmation of your
warranty claim by ALPHCAOOL INTERNATIONAL GMBH.
3. It lies solemnly in the discretion of ALPHACOOL INTERNATIONAL GMBH to repair or replace the
defective product or components. The replaced product or component becomes property of the
ALPHACOOL INTERNATIONAL GMBH.
4. All warranty claims are handled by ALPHACOOL INTERNATIONAL GMBH or an authorized
specialized dealer. If the repair is not done by an authorized dealer or commissioned person,
ALPHACOOL INTERNATIONAL GMBH will cover neither cost nor liability, except if the repair was
coordinated with ALPHACOOL INTERNATIONAL GMBH in advance.
5. Any cost resulting from rebuilding or upgrading of the product will not be covered by ALPHACOOL
INTERNATIONAL GMBH.
6. The warranty by ALPHACOOL INTERNATIONAL GMBH does not include the following points:
I. Regular checks, maintenance or repairs or the replacement of wearing parts.
II. Operating errors or defects resulting from improper installation.
III. Damages caused by storm, water, fire overvoltage, act of nature beyond control or war improper

Heatmaster 2
6
connection to the mains, insufficient or improper ventilation or other reasons which cannot be
influenced by ALPHACOOL INTERNATIONAL GMBH.
IV. Damages caused by transport or improper packaging.
7. The applicable national laws in the country of the end user customer, such as claims towards the
seller, as articled in the contract, remain unaffected by this warranty agreement. ALPHACOOL
INTERNATIONAL GMBH, its branches and distributors, do not take any liability for direct or indirect
damages or losses, if no mandatory legal provisions contradict this.
8. ALPHACOOL INTERNATIONAL GMBH does not take over the warranty of the manufacturer on the
electronic components. The installation of the heatsink takes place at the customer’s own risk.
Safety notice
Please thoroughly read this safety notice to prevent possible errors which may lead to problems or damage
to your hardware.
Not suitable for children under 12 years (contains swallowable small components). Some components on the
Alphacool Heatmaster 2 may become very hot. Please be aware of the danger of burning and be extremely
cautious when touching the device.
Read this operating manual thoroughly before installation.
Before beginning working on your system please back up your data.
The Alphacool Heatmaster 2 must be installed solidly in a free space in the enclosure.
Please make sure that the USB connector is connected with the correct polarity. If the USB cable is
connected with wrong polarity, both the Mainboard as well as the Alphacool Heatmaster 2 can be damaged.
Never plug the power connector in or out whilst the PC is switched on. This can destroy the hardware of your
PC (PSU, USB connector, mainboard etc.) or even the Alphacool Heatmaster 2.
Never connect or disconnect fans, flow rate sensors, temperature sensors, relays, LEDs or other sensors or
devices whilst the system is running. This may damage the Alphacool Heatmaster 2 or even the PC
hardware.
Never interrupt a Firmware update. This may irreparably damage the controller software of the Alphacool
Heatmaster 2, resulting in the controller needing re-programming with a special programming device.
Never interrupt the software start-up of the PC software.
Do not shut down your PC suddenly by e.g. cutting the power or switching off the PSU whilst the system is
running.
Never touch the Alphacool Heatmaster 2 or one of the connected devices whilst switched on.
Intended use
The Alphacool International Gmbh cooling components are approved by Alphacool International Gmbh for
cooling of computer components. If they are used for any other purpose the warranty is voided.
System requirements
Minimum system requirements:
CPU: 500Mhz or better, recommended 1000Mhz
RAM 512 MB
50 - 100 MB HDD space
USB 1.1
Windows XP Service Pack 3, Windows Vista, Windows 7.

Heatmaster 2
7
Windows 98 SE, Windows 2000 Service Pack 4 with limitations.
Depending on the operation being processed the software requires some of the CPU computing power. If
you have transferred the settings to the Alphacool Heatmaster 2 and the software has been shut down, no
more CPU time is needed. The Alphacool Heatmaster 2 then runs autonomously and fulfills its purpose of
controlling and monitoring your cooling system. The Alphacool Heatmaster 2 is even network- and internet
capable with the optionally available LAN adaptor. This allows the Alphacool Heatmaster to be configured
from another PC, meaning that no software needs to be installed on the monitored system, hence not
requiring any CPU time on the system.
More information on possible expansions can be found at the manufacturer homepage www.Alphacool.com
Socket assignment
Overview
Power supply
The Alphacool Heatmaster 2 is connected to the power supply via a 4-Pin Molex plug, just like a HDD or
optical drive. Both voltage (12V and 5V) are needed, the 5V for the micro controller and 12V for the power
connectors, supplying fans and pumps. Should you intend to connect the Alphacool Heatmaster 2 to another
power source than a PC PSU (e.g. in an external enclosure or via a laboratory power supply), please note
that not only a 12V rail is needed, the 5V power rail is also required. If you intend to run the unit in stand-by
(e.g. to allow booting of the system to be triggered by the Alphacool Heatmaster 2), a 5V standby power
supply must be connected via the connection array (see overview).
Fan channels / pumps / slow sensors
Up to 6 fans can be connected to and individually controlled by the Alphacool Heatmaster 2. Additionally it is
possible to connect multiple fans to one channel via a Y-cable or similar adaptor. In such a configuration the

Heatmaster 2
8
fan speed signal from only one fan can be monitored, but the other fans run at the same voltage. Such a
configuration is especially useful if many fans need to be connected to a cooling array. For example, three
radiator fans can be connected to one channel. Bundling of radiator fans also comes in very handy if large
radiators such as the Mora or Phobya Nova (9 fans each). The maximum permissible number of connected
fans depends on the power consumption of the fans. Up to 18W of power may be drawn from an individual
channel passiv cooled..We propose to use an aktiv fan. The power consumption of a standard 120mm fan is
approximately 2.5 to 3.6W. Before connecting multiple fans please check the maximum power draw of the
fans. Should the 10W per channel not suffice, an active cooling system of the driver components can
increase the maximum power output up to 38W. Regarding this please consult the appendix.
The last three channels (3-Pin) are unregulated for the pumps / flow sensors, as these are controlled
separately by the software. Theoretically it is also possible to connect a fan, but the channels are unable to
detect it as such, resulting in constant 12V operation of the connected fan. The 3 channels for pumps / flow
sensors aren’t necessarily compatible with the according components. This means that in some cases it is
e.g. necessary to connect a 3-Pin plug to the pump / flow sensor. Please check in advance if the pump is
suitable for the limitations of the Alphacool Heatmaster 2 (18W per channel). On the 3 channels the 12V DC
voltage from the PSU is simply passed through, hence additional voltage adjustments are not possible. If you
wish to control the speed of your pump, this is possible with an analogue adaptor which is connected parallel
to the 6 fan channels. This allows a pump to be connected and controlled in speed e.g. according to a
measured temperature. Such analogue adaptors will be available soon. The following products can be
connected to the pump / flow sensor channels:
Pumps
EK-DCP 2,2 /4,0
Laing DDC-1T / Laing DDC-1T Plus ( requires active cooling) (as well as the RT models)
Laing DDC-1T Plus (RT-Models) (Active Air cooling needed)
Laing D4/ Laing D5 (Active cooling needed)
Alphacool TPP644 / VPP655 ((Active cooling needed)
Phobya DC12-220/260/400
Please note that the Alphacool pump adaptor may be needed for some models!
Flow rate sensors
Bach DFS 1/25io
Some Digmesa DF sensors
GMR DF Sensor including electronics
Innovatek FlowMeter
Regarding different pumps respectively the precise connection possibilities please consult our website
www.alphacool.com.
Connection array
USB
Connector for the USB cable.

Heatmaster 2
9
ALWAYS ensure correct connection to the pins! If incorrect connections are made or pins are
shorted out, damage may be caused to the Alphacool Heatmaster and / or the connected hardware.
Pay special attention to the correct connection of the USB cable. If the cable is connected improperly
damage may be caused to the Alphacool Heatmaster 2 or the connected hardware. Never remove the
USB connection cable when the system is switched on. The Heatmaster 2 is not hot-plug capable.
HM BUS
Heatmaster 2 BUS-utilization inquiry.
Emergency shutdown
Output for switching of a relay. Via this feature the hardware can be switched off immediately in case of an
emergency. The switching current must not exceed 100mA. Data corruption cannot be ruled out if the
emergency shutdown is activated.
PC shut down
This output can be connected to the Mainboard. When the shut-down signal is sent, the output works like the
power switch of the system.
NTC 1 -6 temperature sensors
Here the temperature sensors can be connected. Use only sensors with a resistance of 5k Ohm or 10k Oh.
The Heatmaster 2 detects these after a reset. The setting can also be made manually.
Water level
To this input an analogue coolant level sensor can be connected. With this sensor the Heatmaster is able to
give a warning if the coolant level is too low.
LED 1 silent alarm
Status LED. This connector is active when the silent alarm is activated. The switching current must not
exceed 2mA.
LED 2 alarm
Status LED. Is active when the alarm is activated. The switching current must not exceed 2mA.
LED 3 warning
Status LED. Is active when a warning is activated. The switching current must not exceed 2mA.
Relay 1-3
With the outputs relays can be controlled, the switching current must not exceed 80mA.
Button 1-3
Inputs for 3 buttons. The buttons must be equipped with a make contact to allow the Heatmaster 2 to
interpret the signal correctly.
Heatmaster reset
With the Jumper the Heatmaster can be restarted. To restart remove the jumper for a short period of time
and plug it in again.
When conducting a hardware reset it is necessary to disconnect the Heatmaster 2 in the software if
the software is started.
IMPORTANT: A reset switches off all outputs!
5V Standby
Power supply for stand-by operation. The PSU must be able to supply at least 1A of current at 5V.
12V and 5V output
Power supply for external devices.

Heatmaster 2
10
Installation
Hardware installation
Shut down your PC and separate the system from the mains.
Ensure that there is no remaining static charge in your body or the enclosure. We recommend using anti-
static gloves and touching the Alphacool Heatmaster 2 only with anti-static gloves. Avoid any direct contact
with the components on the PCB.
Take the Alphacool Heatmaster 2 from the packaging and mount the unit in a suitable spot in the enclosure.
Connect the USB connection cable first.
Make sure that the USB connectors are connected with the correct polarity both on Mainboard and
Alphacool Heatmaster 2!
Please note that connection with wrong polarity may lead to destruction of the Mainboard and / or
the Alphacool Heatmaster 2.
Now connect the power cable (4-Pin plug). Be very careful not to damage the other components on the
board.
Now connect the components which are to be controlled or monitored (e.g. fans, sensors, relays, buttons,
pumps or LEDs).
It is possible to automatically boot and shut down the PC via the Alphacool Heatmaster. For this feature the
Power-Connect cable (not included) is needed. Should you already have ordered this cable it can now be
installed.
Shut the enclosure of your PC, reconnect it to the mains and start up your PC.
Software installation
Download the software from http://www.alphacool.com/download/hm2.zip. Unzip the file. The unzipped folder
contains two setup files. Start the Setup_USB file.
First choose the desired language.
The installation assistant starts. Click on
„Next“ to begin.

Heatmaster 2
11
Accept the terms and conditions to proceed
with the installation.
Choose the target folder for the installation.
Click on „Install“ to proceed.
Setup_USB will copy the required files.
For the connection between PC and
Alphacool Heatmaster 2 a special USB
driver is used. This driver is now being
installed.

Heatmaster 2
12
Accept the terms and conditions to proceed
with the installation. Click on „Next“ to
proceed.
Choose the target folder for the installation
of the USB driver. Click on „Next“ to
proceed.
Click on “Install” to proceed with the
installation.
The required files are being copied.

Heatmaster 2
13
Click on “Install” to implement the
hardware.
The setup will search for connected
devices.
Confirm by clicking “OK” to complete the
installation.
The driver installation is now complete.
Click on “Finish” to close the setup
software.

Heatmaster 2
14
Reboot your system.
After the driver has been installed the software can be installed. To start the software setup, open the file
“Setup_HM2”.
Choose the desired language.
The installation assistant will start. Click on
“Next” to proceed.
Accept the terms and conditions to
proceed with the installation.

Heatmaster 2
15
Choose the folder for installation of the
Heatmaster 2 software. Click on „Next“ to
proceed.
Choose a start menu folder. Click on
“Install” to proceed.
The Heatmaster 2 software is now being
installed.
All settings are now made and the
Heatmaster 2 software has been installed.
Click on “Finish” to start the Heatmaster 2
software.

Heatmaster 2
16
Use of the software
Click on the Icon „Establish connection“ to open the monitoring and control window of the Heatmaster 2.
Two windows will pop up, indicating that the Heatmaster has been detected and that the configuration has
been opened. If everything has started correctly, this will be displayed again.
The general overview of the Heatmaster 2 opens and the connected components are listed.
General configuration Name
Here you can set the device name of your Heatmaster 2. This is
especially important if multiple devices are connected e.g. in a
server or network.
Temperature unit
The temperature can be displayed in °C or °K. The setting made
here will be automatically transferred to all settings which are
related to the temperature.
Language
Choose between multiple languages. The basic version already
has language files for: German, English, French, Spanish and
Italian
Data request interval
Here the intervals at which the PC-Software synchronizes data
with the hardware can be set. The longer the intervals, the less
traffic between PC and Heatmaster is created. 2.
Switching time
Here the period can be set for which the relay will switch in

Heatmaster 2
17
hardare to allow the Mainboard to recognize this as a switching contact. Normally the pre-set 8 seconds
should be plenty. The setting should only be changes if there are problems with the Mainboard.
Display configuration
Important note in advance:
To use this feature a display must be connected to the data
cable. The display must also allow brightness adjustments.
Multiple displays will be able soon, for more information go to
www.Alphacool.com
Brightness during operation:
Here the brightness of the display lighting during operation can
be set.
Brightness in sleep mode
Here the display brightness in sleep mode can be set
(recommended setting: 0%)
Brightness of stand-by lighting
If no activity is detected, the display can be switched to stand-
by mode. We recommend reducing the brightness ion stand-by
mode.
Standby time
Here the period of time of inactivity after which the display will
go into stand-by mode can be set.
Fan configuration
Here the fan channel for which the settings will be made can be
Name
It is possible to name every fan channel individually. The name
may contain up to 255 characters made up of letters and
numbers.
Status
Sets the mode of the fan between: Inactive, not connected and
active
Speed monitoring
Here it can be set if the fan is equipped with a speed monitoring
feature. This is usually only the case i fit is equipped with a rpm
lead.
Fan switch-off in case of failure
If the fan is controlled by the Heatmaster to a target speed or
voltage, but does not send a signal back, this feature will prevent
the Heatmaster from trying to spin up the fan until the next
system start-up.
Action in case of fan failure
here different alarm levels can be set. If the fan is a system-
critical fan it is often useful to set an alarm or even system shut-down here.
Determine Min. / Max. speed
We recommend determining the minimum and maximum speed once per each fan to allow the Heatmaster 2
to determine the relevant data. If fluctuating values for maximum and minimum speed are to be expected, a
check after every start-up can also be set.

Heatmaster 2
18
Speed factor
This factor represents how many signals per revolution are sent by the fan. Normal PC fans have a value of
2 impulses per revolution. In rare cases or with unusual fans this value may also be higher or lower. Some
fans have reduced signal quality at low speeds, hence not allowing a speed signal to be registered. Is the fan
is operated outside of the “clean signal range” it is also possible to set the voltage as the control unit instead
of the rpm signal. If the voltage is set as control unit the Heatmaster is unable to monitor the functionality of
the fan.
Manual temperature control
Voltage and fan speed can be set manually by setting the target value on the sliding bar
.
Automatic temperature control
One or even two sensors can be assigned to each fan, allowing automatic speed control of the fan
depending on the temperature. If two sensors are assigned, the one with the higher monitored temperature
will automatically be used for determination of the fan’s target speed. Now the following options can be used:
Linear: A linear speed curve between starting temperature and maximum temperature will be used
for determination of the fan target speed.
Progressive: The control curve begins with a flat slope and becomes steeper the closer the
monitored temperature is to the maximum.
Target value: The fan will start to spin below the set target temperature and the automatic fan speed
control will try to hold the target temperature as constantly as possible. Due to many factors coming
into account when trying to maintain a certain temperature, such as heat dissipation, pump
performance, room temperature etc. or contradicting control factors, it is not always possible for the
Alphacool Heatmaster 2 to maintain the set target temperature. This is not an error or reason for
reclamation, but rather caused by the many possible settings of the Heatmaster 2 as well as the
complexity of a water cooling system.
Switch-off hysteresis: Temperature difference value which prevents pointless start-up and switch-off
of the fan near the starting temperature. The more directly the system reacts, the higher this value
should be set. Alternatively the starting speed of the fan can be decreased. In systems with slow
temperature changes, e.g. due to high thermal capacity, a low hysteresis value is of advantage.
Temperature sensors configuration Here the sensor channel for which the settings will be made can
be chosen
IMPORTANT: Only set the status to ON if a sensor is actually
connected. Otherwise false values will be displayed.
Name:
It is possible to set a name for every sensor channel individually.
The name may contain up to 255 characters made up of letters
and numbers.
Status
Sets the status of the sensor to: Off, not connected or On.
Emergency shutdown
If this feature is set to ON, the system will initiate an emergency
shutdown of your PC system if set temperature is reached
Settings
Here sensor-specific settings can be made. The Heatmaster
software has two NTC tables which are set for the currently sold
5kOhm respectively 10kOhm temperature sensors. With the
correction value “rough” measuring errors can be significantly
reduced. Should the included NTC table cause major deviations, it is possible to save another NTC table
which can be used. This feature is also very useful when completely different sensors are being used. Hence
the Heatmaster 2 is compatible with virtually all currently available and future resistance-based temperature
sensors. The Heatmaster 2 allows only one NTC table to be used at a time, which will be used for all
connected sensors.

Heatmaster 2
19
Temperature values
The values for “warning”, “alarm” and “emergency shutdown” can only be set with ascending temperature
values in this order. Hence it is not possible to monitor the system for undercutting of a certain bottom
temperature with this feature. Setting of an alarm or setting when undercutting a certain temperature is
possible with the “Online button / relay” feature though.
Pump / flow rate sensor configuration
Here the pump / flow rate sensor channel for which the settings are going to be made can be chosen.
Name
It is possible to set a name for every channel individually. The
name may contain up to 255 characters made up of letters and
numbers.
Status
Sets the status of the channel to: Off, not connected or On.
Type
Here the channel can be set to pump or flow rate sensor mode
Factor
This factor represents how many signals the pump / flow rate
sensor sends per revolution. Normal flow rate sensors have a
value of two. In rare cases or with different components this
factor may also be lower or higher. For pumps this value must
be determined by the user.
Pump settings
If a pump is connected, it can be monitored. Should the speed
of the pump undercut a certain value an “action in case of pump
failure” can be set. The choices are: No warning, alarm or
emergency shutdown
Flow rate sensor settings
If the conversion factor “Signals per liter” for the sensor is known, the unit can be set to “liters per hour” or
“Gallons per hour”. Similar to the temperature monitoring it is possible to set an action if a certain value is
undercut. Different values for warning, alarm an emergency shutdown can be set.
Other manuals for Heatmaster 2
1
Table of contents
Other Alphacool Control Unit manuals
Popular Control Unit manuals by other brands

Thyracont
Thyracont VD12 operating instructions

Gemu
Gemu 605 Installation, operating and maintenance instructions

Siemens
Siemens SIRIUS 8WD44 28-0B quick start guide

VIGOUR
VIGOUR individual Assembly instructions and operation manual

Velleman
Velleman VMA204 user manual

Edwards
Edwards GXS instruction manual