
44 ซ.บรมราชชนนี 70 ถ.บรมราชชนนี ศาลาธรรมสพน์ ทวีวัฒนา กทม. 10170.
Website: https://www.add-furnace.com/ โทร: 02-888-3472
CORROSIVE CHEMICALS
Corrosivechemicalscanalsoattackthemoduleandgas
control and eventually cause a failure. Where chemicals
maybeusedroutinelyforcleaning,makesurethecleaning
solution cannot reach the controls. Where chemicals are
likely to be suspended in air, as in some industrial and
agricultural applications, protect the ignition module from
exposure with a NEMA 4 enclosure; see the Electronic
Ignition Service Manual, form 70-6604.
DUST OR GREASEACCUMULATION
Heavy accumulation of dust or grease may cause the
controls to malfunction. Where dust or grease may be a
problem,providecoversforthemoduleandthegascontrol
INSTALLATION
WHEN INSTALLING THIS IGNITION SYSTEM…
1.
Read these instructions carefully. Failure to follow
themcoulddamagethecomponentsorcauseahazardous
condition.
2.
Check the ratings given in the instructions and onthe
components to make sure they are suitable for your appli-
cation.
3.
Installer must bea trained, experienced service tech-
nician.
4.
After installation is complete, check out component
operation as provided in these instructions.
that will limit environmental contamination. A NEMA 4
enclosureisrecommendedfortheignitionmodule;seethe
Electronic Ignition Service Manual, form 70-6604.
HEAT
The controls can be damaged by excessively high
temperatures. Make sure the maximum ambient tempera-
ture at the control locations will not exceed the rating of the
control. If the appliance normally operates at very high
temperatures,insulation,shielding,andaircirculationmay
be necessary to protect the controls. Proper insulation or
shielding should be provided by the appliance manufac-
turer; make sure adequate air circulation is maintained
when the appliance is installed.
•
In many such applications, particularly commercial
cooking, the equipment operates 100,000-200,000
cyclesperyear.Suchheavycyclingcanwearoutthe
gas control in one to two years. A normal forced air
furnace, for which the controls were originally in-
tended, typically operates less than 20,000 cycles
per year.
•
Exposure to water, dirt, chemicals, and heat can
damagethemodule orthegascontrolandshutdown
thecontrol system.ANEMA 4enclosurecanreduce
exposure to environmental contaminants. See Elec-
tronic Ignition Service Manual, form 70-6604.
Themaintenanceprogramshouldincluderegularcheck-
out of the system as outlined under Checkout, page 11.
Maintenancefrequencymustbedeterminedindividually
for each application. Some considerations are:
•
Cyclingfrequency.Appliancesthatmaycyclemore
than 20,000 times annually should be checked
monthly.
•
Intermittent use. Appliances that are used seasonally
should be checked before shutdown and again be-
fore the next use.
PERFORM PREINSTALLATION SAFETY INSPECTION
The preinstallation checks described in ANSI Standard
Z21.71 on page 19 must be done before the replacement
module is installed. If a condition which could result in
unsafe operation is detected, the appliance should beshut
off and the owner advised of the unsafe condition. Any
potentially unsafe condition must be corrected before pro-
ceeding with the installation.
Maintenance Requirements in Severe Environments
Regular preventive maintenance is important in any
application, but especially so in commercial cooking, agri-
cultural, and industrial applications because:
•
=
Consequence of unexpected shutdown. Where the
cost of an unexpected shutdown would be high, the
system should be checked more often.
•
Dusty, wet, or corrosive environment. Since these
environments can cause the controls to deteriorate
more rapidly, the system should be checked more
often.
Any control should be replaced if it does not perform
properly on checkout or troubleshooting. In addition, re-
place any module if it is wet or looks like it has ever been
wet. Protective enclosures as outlined under “Planning the
Installation” arerecommended regardless ofcheckout fre-
quency.
MOUNT IGNITION MODULE
Select a location close enough to the burner to allow a
short (3 ft. [0.9 m] max.), direct cable route to the igniter.
Ambient temperature at the module must be within the
range listed under APPLICATION, page 1. The module
must be protected from water, moisture, corrosive chemi-
cals and excessive dust and grease.
FIRE OR EXPLOSION HAZARD
MAY CAUSE PROPERTY DAMAGE, SEVERE
INJURY OR DEATH
Donotattempttotakethemoduleapartortoclean
it. Improper reassembly and cleaning may cause
unreliable operation.
1.
Disconnectpowersupplybeforebeginningwiring
to prevent electrical shock or equipment damage.
2.
If a new gas control is to be installed, turn off gas
supply before starting installation. Conduct Gas
Leak Test according to gas control manufac-
turer’s instructions after the gas control is in-
stalled.
3.
If module must be mounted near moisture or
water, provide suitable waterproofenclosure.
CAN CAUSE SERIOUS INJURY OR DEATH.
1.
The ignition module can malfunction if it gets
wet,leadingtoaccumulationofexplosivegas.
•
Never install where water can flood, drip or
condense on module.
•
Never try to use a module that has been
wet—replace it.
2.
Liquefied petroleum (LP) gas is heavier than
air and will not vent upward naturally.
•
Do not light pilot or operate electric
switches,lights,orappliances untilyouare
sure the appliance area is free ofgas.