alphainnoTec Luxtronik User manual

83055600bUK – Translation of the original instruction manual (HMD 2)
UK
Controller part 2 (Qualified technician)
Scope of delivery, Montage, Electrical connections
Software update
Commissioning / Switching on for the first time
Addressed heat pump
Program area “Service“
Appendix
Operating Instructions
Luxtronik
Heating- and Heat Pump Control

2
We reserve the right to make technical changes | 83055600bUK – Translation of the original instruction manual (HMD 2) | ait-deutschland GmbH
Please read rst
This operating manual is part 2 of the 2-part operating manual for
the heating and heat pump controller. Ensure that you have part 1
of this operating manual. If part 1 is missing, request it from your
supplier
This operating manual provides important information on the
handling of the unit. It is an integral part of the product and must
be stored so that it is accessible in the immediate vicinity of the
unit. It must remain available throughout the entire service life of
the unit. It must be handed over to subsequent owners or opera-
tors of the unit.
Read the operating manual before working on or operating the
unit. This applies in particular to the chapter on safety. Always fol-
low all instructions completely and without restrictions.
It is possible that this operating manual may contain instructions
that seem incomprehensible or unclear. In case of questions or
uncertainty, contact the factory customer service department or
the manufacturer’s local service partner.
This operating manual is intended only for persons assigned to
work on or operate the unit. Treat all constituent parts condenti-
ally. The information contained herein is protected by copyright.
No part of this information may be reproduced, transmitted, co-
pied, stored in electronic data systems or translated into another
language, either wholly or in part, without the express written
permission of the manufacturer
Symbols
Information for operators.
Information or instructions for qualied technicians and
authorised service personnel.
DANGER!
Indicates a direct impending danger resulting in severe
injuries or death.
DANGER!
Indicates danger to life due to electric current!
WARNING!
Indicates a possibly dangerous situation that could re-
sult in severe injuries or death.
CAUTION!
Indicates a possibly dangerous situation that could re-
sult in medium or light injuries.
ATTENTION
Indicates a possibly dangerous situation, which could re-
sult in property damage.
NOTICE
Emphasized information.
€
ENERGY SAVINGTIP
Indicates suggestions that help to save energy, raw mate-
rials and costs.
Users and qualied technicians can set data.
Authorized tter can set data; password required.
Authorised service personnel can set data. Access via
USB stick only.
Factory pre-setting, no data change possible
Reference to other sections in the operating instructions.
Reference to other documents of the manufacturer.

3
We reserve the right to make technical changes | 83055600bUK – Translation of the original instruction manual (HMD 2) | ait-deutschland GmbH
Contents
MAKING SETTINGS
............................................................................................... 16
Determine data access.............................................................................. 16
Calling up short programs...................................................................... 16
Determining temperatures.................................................................... 16
Determining priorities .............................................................................. 18
Determining system setting.................................................................. 18
Ventilating the system..............................................................................22
Fix startup parameters..............................................................................23
energy eciency pump...........................................................................23
SELECTING LANGUAGE OF THE SCREEN DISPLAY
..................................... 24
DETERMINING DATE AND TIME
....................................................................... 24
SCREED HEATING PROGRAM
............................................................................ 24
Setting temperatures and time intervals....................................... 24
Starting screed heating program....................................................... 24
Manually terminating screed heating program.........................25
SYSTEM CONFIGURATION
................................................................................. 26
STARTUP GUIDE
.................................................................................................... 26
STARTUP GUIDE PARAMETERS BACK
............................................................. 26
DATA LOGGER
........................................................................................................ 26
CONTROL PANEL
................................................................................................... 26
Adjusting the contrast of the
control element display....................................................................... 26
Web server....................................................................................................... 26
Remote maintenance................................................................................ 26
device assignment ...................................................................................... 26
APPENDIX
ERROR DIAGNOSIS / ERROR MESSAGES.................................................. 27
Acknowledging a fault.................................................................................30
Flashing codes on controller board......................................................30
TECHNICAL DATA .................................................................................................. 31
Installation .......................................................................................................... 31
Outputs ................................................................................................................ 31
Inputs..................................................................................................................... 31
Connections....................................................................................................... 31
Interfaces............................................................................................................. 31
Protection class................................................................................................ 31
Temperature sensor characteristics ..................................................... 31
Sensor measuring range............................................................................. 31
SYSTEM SETTING DURING COMMISSIONING...................................... 32
IMPORTANT ABBREVIATIONS........................................................................34
INFORMATION FOR USERS, QUALIFIED TECHNICIANS AND
AUTHORISED SERVICE PERSONNEL
PLEASE READ FIRST.................................................................................................2
SYMBOLS.......................................................................................................................2
SCOPE OF DELIVERY, MONTAGE, ELECTRICAL CONNECTIONS,
INSTALLATION OF SENSORS, DISMANTLING
SCOPE OF DELIVERY...............................................................................................4
ELECTRICAL CONNECTIONS..............................................................................4
Basic wiring of the heating and
heat pump controller...............................................................................4
Connections of the operating element ................................................5
Assembly and Installation of Sensors.....................................................5
External Sensor................................................................................................5
Hot water sensor.............................................................................................6
External return ow sensor.......................................................................6
DISMANTLING............................................................................................................6
Removal of the buer battery....................................................................6
SOFTWARE UPDATE................................................................................................6
COMMISSIONING / SWITCHING ON
FOR THE FIRST TIME........................................................................................7
Commissioning (Startup guide).................................................................7
Startup assistant parameters back...........................................................8
SMART GRID
..............................................................................................................9
Adjustable under system settings:....................................................9
Terminal diagram.........................................................................................9
ADDRESSED HEAT PUMP
ADDRESSED HEAT PUMP.................................................................................. 10
Changing the addressed heat pump in submenus..................... 10
PROGRAM AREA “SERVICE“
SEKECT PROGRAM AREA
.....................................................................................11
QUERY INFORMATION
..........................................................................................11
Query Temperatures...................................................................................11
Query inputs................................................................................................... 12
Query outputs............................................................................................... 12
Calling up timings ....................................................................................... 13
Query operating hours............................................................................. 13
Calling up error memories...................................................................... 14
Calling up disconnections ...................................................................... 14
Calling up the machine status.............................................................. 15
Heat quantity ................................................................................................. 15
BACnet ............................................................................................................... 15

4
We reserve the right to make technical changes | 83055600bUK – Translation of the original instruction manual (HMD 2) | ait-deutschland GmbH
BASIC WIRING OF THE HEATING AND
HEAT PUMP CONTROLLER
1 EVU bridges (must be removed when
connecting a oating contact)
2 TRL return sensor terminal (on NTC8)
3 Cable duct with covers
4 Terminal block for 1~/N/PE/230 V voltage supply
5 Cable entries
6 Terminal block for heat pump 1 or heat pump 2
connection cables (must be labelled accordingly)
7 Terminal block for heat pump 1 or heat pump 2
connection cables (must be labelled accordingly)
8 Terminal block for electric heating element connection cable
9 Connection terminals (X10 Modbus) for LINBus
communication cables to heat pump 1 and heat pump 2
10 Control card of the heating and heat pump control
11 Slot for optional “2.1-EP” circuit board
12 LIN-BUS communication cable between control
board and control unit (wired in the factory)
13 Operating element
Instruction manual for your appliance, “Connection
layout” and “Circuit diagrams” for your appliance type
NOTICE
The inputs and outputs on the control board are assigned
by the terminal diagram of the hydraulic module. In addi-
tion, you will nd the assignment on the switchbox cover.
Scope of delivery
NOTICE
Function-critical temperature sensors (return, inlet, hot
gas) are installed in the heat pump and are not part of the
scope of supply of the heating and heat pump regulator.
The heating and heat pump regulator is supplied in two variants.
The variant supplied is dependent on the device type of the heat
pump to the controlled.
Electrical connections
DANGER!
Danger of fatal injury due to electric current!
Electrical connections may be installed only by qualied
electricians.
Before opening the unit, disconnect the system from the
power supply and secure it from being switched back on!
WARNING!
During installation and while carrying out electrical
work, comply with the relevant EN-, VDE and/or local sa-
fety regulations.
Comply with technical connection requirements of the
responsible power supply company (if required by the
latter)!
NOTICE
The description of the basic electrical wiring and the wiring
diagram of the connection of hydraulic module and heat
pumps, refer to the operating instructions of the hydraulic
module2
Operating instructions “Hydraulic module 2““

5
We reserve the right to make technical changes | 83055600bUK – Translation of the original instruction manual (HMD 2) | ait-deutschland GmbH
ASSEMBLY AND INSTALLATION OF SENSORS
EXTERNAL SENSOR
The external sensor is a function-critical accessory and included
in the scope of supply.
NOTICE
If the external sensor is not installed or defective, the hea-
ting and heat pump regulator automatically sets the exter-
nal temperature to -5 °C. The status display of the opera-
ting element lights up red, the screen of the operating ele-
ment reports a fault.
ATTENTION
Mount the external sensor on the north or northeast side
of buildings. The sensor must not be exposed to direct
sunlight.
Open the housing of the external sensor and align ≥ 2 m over
the base of the fastening point. The cable gland must point
to the base…
1 xternal sensor housing
2 Fastening holes
3 Cable gland
4 External sensor
Pencil on fastening holes and drill, insert dowels and screw
housing of the external sensor onto the wall…
NOTICE
Dowels and screws for fastening the external sensor are
not included in the scope of supply.
Loosen cable gland from the housing of the external sensor,
lead the 2-wire cable (Ø ≤ 1.5 mm² per wire, cable length ≤ 50
m) through the cable gland into the housing…
Clamp on cable, tighten cable gland and close the housing of
the external sensor.
CONNECTIONS OF THE OPERATING ELEMENT
R RS485 for connecting the
room control unit (RBE)
N Network
L LIN-BUS to the control board
S not assigned

6
We reserve the right to make technical changes | 83055600bUK – Translation of the original instruction manual (HMD 2) | ait-deutschland GmbH
Dismantling
DANGER!
Danger of fatal injury due to electric current!
Electrical connections may be installed only by qualied
electricians.
Before opening the unit, disconnect the system from the
power supply and secure it from being switched back
on!
REMOVAL OF THE BUFFER BATTERY
ATTENTION
Before scrapping the heating and heat pump regulator, re-
move the buer battery on the main board. You can use
a screwdriver to remove the battery from its bracket. Dis-
pose of battery and electronic components in keeping
with environmental considerations.
Software Update
A software version < V2.63 must no longer be loaded on a unit wi-
th software version ≥V2.63.
Output-controlled air/water heat pumps may only be operated
with software version V3.xx and higher..
HOT WATER SENSOR
The domestic hot water sensor is an optional accessory and only
functionally-relevant for a separate domestic hot water tank. You
may only use domestic hot water sensors which have been appro-
ved by the manufacturer of the heat pump..
ATTENTION
The domestic hot water tank must be lled before connec-
ting the domestic hot water sensor to the heating and heat
pump regulator.
If not already prepared at the factory, mount the domestic hot
water sensor (Ø = 6 mm) on the halfway level of the domestic hot
water tank – and always above the internal heat exchanger of the
domestic hot water tank.
1 Hot-water tank
2 Domestic hot water sensor (Ø = 6 mm)
3 Heat exchanger
4 Cold water connection
5 Domestic hot water connection
EXTERNAL RETURN FLOW SENSOR
The return ow sensor (optional accessory) is functionally-rele-
vant for hydraulic integration of an isolating tank (multifunction
tank …). This has to be installed as follows:
ZUP TRLext HUP
1 Separation or multi-functional storage tank
2 Circulation pump in the separation
storage tank (heat pump circuit)
3 Circulation pump from the separation
storage tank (heating circuit)
4 External return sensor (Ø = 6 mm)
ZUP Charging loop, heat pump
HUP Discharging loop, heating circuit
Connect the return ow sensor coming from the isolating tank to
the circuit board of the heating and heat pump regulator.
See terminal diagram in the operating manual of the hy-
draulic module2

7
We reserve the right to make technical changes | 83055600bUK – Translation of the original instruction manual (HMD 2) | ait-deutschland GmbH
For the number of the control setting, please refer to the hydraulic dia-
grams we have published
If 2 heat pumps are operated at the hydraulic module, the heating
and heat pump controller must now address each individual he-
at pump. Heat pump 1 is addressed rst, which is why the LINBus
connection to heat pump 2 has to be disconnected temporarily
from the control board of the heating and heat pump controller.
NOTICE
If necessary the assignment of the heat pump be repeated
any time.
page 26, “device assignment“
NOTICE
Do not press the conrmation prompt in the screen until
the LINBus connection to heat pump 2 has been discon-
nected from the control board.
As soon as the conrmation prompt is pressed the addressing of
heat pump 1 begins.
The screen does not change until it has nished addressing heat pump 1
NOTICE
Do not press the conrmation prompt on the screen until
the LINBus connection to heat pump 2 has been plugged
into the control board and the LINBus connection to heat
pump 1 has been unplugged from the control board.
Commissioning / Switching on
for the rst time
COMMISSIONING STARTUP GUIDE
ATTENTION
The Startup guide must always be run, as it is the only way
to address the connected heat pumps.
The control unit is equipped with a commissioning assistant. This
assistant will guide you through the most important settings of
the regulator during initial commissioning. The “GO” symbol in
the main menu ashes. Click on the symbol to launch the com-
missioning assistant. The symbol will disappear as soon as initi-
al commissioning is complete. For more information on the com-
missioning assistant, please refer to the corresponding sections in
this operating manual..
If you are not yet familiar with the control and the displayed
screens, read rst: part 1 of the controller manual, section
“Basic information on operation“
When switched on for the rst time the language selection ap-
pears rst.
Select the language of the display, part 1 of the controller
manual, section “Basic information on operation“.
The following display then appears:
NOTICE
The display always appears when the controller is swit-
ched on or on changing to the standards menu..
This screen is no longer displayed if the heat pump or
ZWE1 has more than 10 operating hours.
ATTENTION
The unit can be damaged if the display is conrmed with
OK, although the system is not properly lled.
Click on the symbol to launch the commissioning assistant. You
will be guided step-by-step through several selection options
used to set up your heat pump

8
We reserve the right to make technical changes | 83055600bUK – Translation of the original instruction manual (HMD 2) | ait-deutschland GmbH
NOTICE
The heating phase until the compressor starts can take se-
veral hours when starting up air/water heat pumps for the
rst time.
NOTICE
In the case of LWD units the ow is monitored while the
pump is running. If the ow is not ok, the heat pump does
not start up and no error is displayed. To this end, check
the ASD input, if it is not set to ON the ow is too low..
page 12, “Query inputs“
STARTUP ASSISTANT PARAMETERS BACK
If your heat pump was commissioned by an authorised customer
service partner and the startup parameters have been stored, you
can use this menu item to restore these parameters.
This may be helpful if settings have been changed and let to a
system malfunction. Please Notice that all settings such as hea-
ting curves, system settings, set values will be reset to the values
applicable at commissioning.
This does not apply to the time switches.
You will be guided through the following menu items:
As soon as the conrmation prompt is pressed the addressing of
heat pump 2 begins.
The screen does not change until it has nished addressing heat pump 2
NOTICE
Do not press the conrmation prompt in the screen until
the LINBus connection to heat pump 1 has been plugged
into the control board.
As soon as the prompt is conrmed the system checks whether
the connection with both heat pumps can be established.
Following successful checking and connection to both heat pumps the Startup
guide continues with further input prompts, which concern the settings of your
system, for example, with.
Danach erscheint folgender Bildschirm:

9
We reserve the right to make technical changes | 83055600bUK – Translation of the original instruction manual (HMD 2) | ait-deutschland GmbH
SMART GRID
Use of the Smart Grid option depends on the unit type and soft-
ware version.
If you have any questions regarding the availability of the Smart
Grid functionality in your electricity tari, please contact your
electricity supply company
The function is connected via two contacts of the utility lock,
from which four possible operating states result.
.NOTICE
If utility lock is applied, the Smart Grid functional may not
be activated.
ADJUSTABLE UNDER SYSTEM SETTINGS:
Current operating state visible under Information->Inputs
Operating state 1 (1:0)
Corresponds to the current utility lock.
Operating state 2 (0:0) - deviation from standard control behavi-
our:
The heat pump operates exclusively within the range of the set-
point hysteresis (i.e. below the setpoint).
Heating: If the system temperature drops to below the lower hy-
steresis, the heat pump is switched on and heats the system up to
the setpoint. The upper hysteresis is ignored. The heat pump on-
ly heats until there is no longer any need to worry about possi-
ble comfort losses. Domestic water heating takes place as normal.
Operating state 3 (0:1) - corresponds to standard control behavi-
our:
The target temperature is the set setpoint temperature for hea-
ting and domestic hot water. These set temperatures are held ta-
king into account the respective hystereses.
Operating state 4 (1:1) - deviation from standard control behavi-
our:
The heat pump operates exclusively within the range of the set-
point + hysteresis (i.e. above the setpoint).
Heating: If the system temperature drops to the setpoint, the he-
at pump is switched on and heats the system up to the setpoint +
hysteresis points
DHW: The controller generates a positive hysteresis whose magni-
tude is equal to the lower hysteresis and regulates in this area (set
temperature + upper hysteresis).
TERMINAL DIAGRAM
Klemmenplan SG-Ready HZ-I/O
-
-X4 -X3-2
SG1
SG2
Legende:
Betriebsmittel
A1
A3
SG1
SG2 IN3
IN4
DE
Funktion
Reglerplatine; Achtung: I-max = 6,3A/230VAC
Unterverteilung Hausinstallation
Smart Grid Ansteuerung 1
Smart Grid Ansteuerung 2
831210
123 45678
12 8
A
B
C
D
E
F
A
B
C
D
E
F
Blatt
Bl.
1
1
3 4567
AIT 831210
Klemmenplan
ait-deutschland GmbH
L1
L1
L1
L
2
2
IN1
IN2
IN3A1A2A1A2
IN4
IN5
A3
A1
Änderung Datum
Datum
Bearbeiter
Geprüft
NormName
09.10.2015
Pfleger
R.
Klemmenplan SG-Ready HZ-I/O
-
-X4 -X3-2
SG1
SG2
Legend:
Equipement
A1
A3
SG1
SG2 IN3
IN4
UK
Function
Controller board; Attention: I-max = 6,3A/230VAC
Sub-distribution unit internal installation
Smart Grid activation 1
Smart Grid activation 2
831210
123 45678
12 8
A
B
C
D
E
F
A
B
C
D
E
F
Blatt
Bl.
1
1
3 4567
AIT 831210
Klemmenplan
ait-deutschland GmbH
L1
L1
L1
L
2
2
IN1
IN2
IN3A1A2A1A2
IN4
IN5
A3
A1
Änderung Datum
Datum
Bearbeiter
Geprüft
NormName
09.10.2015
Pfleger
R.

10
We reserve the right to make technical changes | 83055600bUK – Translation of the original instruction manual (HMD 2) | ait-deutschland GmbH
Addressed heat pump
Addressed heat pump
Refer to the navigation screen to see which heat pump is cur-
rently addressed or controlled by the system‘s „Service“ area. In
the example shown it is heat pump I, which you can see from the
number 1 (see arrow) displayed in the navigation screen:
NOTICE
Depending on whether number 1 (for heat pump 1) or
number 2 (for heat pump 2) appears in a main or submenu,
the displayed information or settings made refer to heat
pump 1 or heat pump 2. So if the number 2 is displayed in
the place marked by the arrow in your navigation screen,
this means that heat pump 2 is currently addressed in the
system‘s „Service“ area..
If you want to call up information for the heat pump currently dis-
played (1 or 2) in the system area „Service“ or want to make set-
tings, please skip to the following section: „Select program area“.
However, if you want to call up information or make settings for
the other heat pump, use the rotary pushbutton to move to the
number required (here in this example, number 1)
NOTICE
The selection you make here with the denition of number
1 (for heat pump 1) or the number 2 (for heat pump 2), ap-
plies to the whole system area „Service“.
CHANGING THE ADDRESSED HEAT PUMP IN
SUBMENUS
Please note the displayed number in the title row of the respec-
tive submenu:
Example::
If you want to switch between heat pump 1 and heat pump 2 whi-
le working within the system area „Service“, you can make this
change in the submenus of the system area „Services“.

11
We reserve the right to make technical changes | 83055200cDE – Translation of the original instruction manual (HMD 2) | ait-deutschland GmbH
QUERY TEMPERATURES
NOTICE
Note the number displayed in the top menu row (marked here
by the arrow). It provides information about which heat pump
is currently addressed..
In order to change the addressed heat pump, refer to the
section: page 10, “Changing the addressed heat pump in
submenus“
The menu is not shown in full here. Further menu items appear if you scroll down the
screen
.
Inlet Flow temperature heating circle
Return Return ow temp. of heating circle
Ret. targ. Return setpoint heating circle
Return external Return temp. in separate tank.
Hot gas Hot gas temperature
amb. temp. External temperature
Mean temperature Average temperature
outside over (function heating limit)
Act. service water Domestic hot water actual
temperature
Targ. service water Domestic hot water target
temperature
Heats in Heat source inlet temperature
Heats out Heat source outlet temperature
Mixing circle 1 fore. Mixing circle 1
Forward ow temperature
Mixing circle 1 desir. Mixing circle 1
Forward ow set temperature
Room temperatures Is displayed if the room control unit is
connected
In addition – depending on the unit type of the connected heat
pump – the cooling circuit information provided by sensors in the
cooling circuit appears here.
NOTICE
Some sensors will not be detected until the controller has
been restarted after the installation of the corresponding
sensor.
Program area “Service“
SEKECT PROGRAM AREA
QUERY INFORMATION

12
We reserve the right to make technical changes | 83055200cDE – Translation of the original instruction manual (HMD 2) | ait-deutschland GmbH
QUERY OUTPUTS
NOTICE
Note the number displayed in the top menu row (marked here
by the arrow). It provides information about which heat pump
is currently addressed..
In order to change the addressed heat pump, refer to the
section: page 10, “Changing the addressed heat pump in
submenus“
The menu is not shown in full here. Further menu items appear if you scroll down the
screen.
CV-Defrost. valve Valve / Circuit reversal
ON = Thaw mode or rather cycle
reversal becomes active
DHW pump Domestic hot water circulation pump
Floor heat. pump 1 Floor heating circulation pump
Heat. sys. pump Heating circulation pump
Mixer 1 Open Mixer 1 opens
On = opens / O = no control
Mixer 1 Close Mixer 1 Close
On = closes / O = no control
Ventilation Ventilation of the heat pump housing
for certain L/W devices.
For L/W size types (coding “L2G”),
second stage of the ventilator
Fan-heats. pump Ventilator, well or brine circulation
pump
Compressor 1 Compressor 1 in heat pump
Compressor 2 Compressor 2 in heat pump
CP Circulation pump
Suppl. pump Additional circulating pump
2nd heat gen. 1 Second heat generator 1
2nd heat gen. 2 Second heat generator 2– Collective
fault (function collective fault:
Continuous ON in the event of a fault,
cycles 1x per second with automatic
RESET enabled)
Control signal UWP Circulation pump output in %
RPM Ventilator Current speed of the heat pump’s fan
RPM Compressor Current speed of the heat pump’
compressor
QUERY INPUTS
NOTICE
Note the number displayed in the top menu row (marked here
by the arrow). It provides information about which heat pump
is currently addressed..
In order to change the addressed heat pump, refer to the
section: page 10, “Changing the addressed heat pump in
submenus“
The menu is not shown in full here. Further menu items appear if you scroll down the
screen.
NOTICE
This menu shows whether the digital inputs of the control-
ler are switched on or o.
Defr/Brin/Flow Defrost, Brine pressure, ow
Depending on the device type, the input can full various
functions:
For L/W-devices Defrost end pressostat:
On = Defrost is
terminated.
For LWD, S/W and W/W devices with ow switch connected at
the factory:
On = Flow okay.
For S/W devices without ow switch connected at the factory, a
brine pressostat can be connected:
On = brine pressure
sucient.
SW-therm. switch Domestic hot water thermostat
On = Domestic hot water requirement
Electr. suppl. O-time of the electrical supply
O = O-time
High pressure High-pressure pressostat
O = Pressure okay
Motor protect. Motor protection
On = Motor protection okay.
Low pressure Low pressure pressostat
On = Pressure okay.
PEX Connection of an external current
anode
(possible for some devices)
AIn Input analog

13
We reserve the right to make technical changes | 83055200cDE – Translation of the original instruction manual (HMD 2) | ait-deutschland GmbH
QUERY OPERATING HOURS
NOTICE
Note the number displayed in the top menu row (marked here
by the arrow). It provides information about which heat pump
is currently addressed..
In order to change the addressed heat pump, refer to the
section: page 10, “Changing the addressed heat pump in
submenus“
The menu is not shown in full here. Further menu items appear if you scroll down the
screen
.
Op. h. comp1 Operation hours compressor 1
Impulses comp. 1 Impulses compressor 1
Duration comp. 1 average duration compressor 1
Op. h. comp2 Operation hours compressor 2
Impulses comp. 2 Impulses compressor 2
Duration comp. 2 average duration compressor 2
Operation hours 2hg1 Operation hours
Second heat generator 1
Operation hours 2hg2 Operation hours
Second heat generator 2
Operation hours hp Operation hours Heat pump
Operation hours heat Operation hours Heating
Operation hours hw Operation hours
Domestic hot water
Operation hours cool Operation hours Cooling
NOTICE
The compressors are only energised alternately follow-
ing the impulses. A variation in the operation hours of the
compressors is, therefore, possible.
CALLING UP TIMINGS
NOTICE
Note the number displayed in the top menu row (marked here
by the arrow). It provides information about which heat pump
is currently addressed..
In order to change the addressed heat pump, refer to the
section: page 10, “Changing the addressed heat pump in
submenus“
The menu is not shown in full here. Further menu items appear if you scroll down the
screen
.
HP since Heat pump running since
(Time indication respectively in hh:mm:ss)
2 hg 1 since Second heat generator 1 running since
2 hg since Second heat generator 2 running since
Switch on Net input delay
Swi c time O-time switching cycle
Read-CPd Compressor Read-CPd
HC Add-time Heating control more time
HC Less-time Heating time less time
ThDsin.sin Thermal disinfection running since
Stop SW O-time domestic hot water
Defrosting Time until the next defrosting (LW)

14
We reserve the right to make technical changes | 83055200cDE – Translation of the original instruction manual (HMD 2) | ait-deutschland GmbH
CALLING UP DISCONNECTIONS
NOTICE
Note the number displayed in the top menu row (marked here
by the arrow). It provides information about which heat pump
is currently addressed..
In order to change the addressed heat pump, refer to the
section: page 10, “Changing the addressed heat pump in
submenus“
04.08.08
Date of the disconnection (here by way of example)
17:28
Time of the disconnection (here by way of example)
hp / hp fault
Disconnection code (here by way of example)
Error hp = heat pump fault
err.inst. = system fault
m.o. 2hg = mode of operation second heat
generator
El. Sup. bl = el. sup. blockade
Defr. air. = air defrost (only L/W devices)
TPLmax = temperature limits of application
maximum
TPLmin = temperature limits of application
minimum
(in reversible LWD possible shutdown due to frost protection in
cooling mode - evaporation too long
below 0°C)
Low lim = lower limit of application
no requ. = no request
NOTICE
Maximum the last ve disconnections are displayed.
CALLING UP ERROR MEMORIES
720
Error code (here by way of example)
04.08.08
Date of the resulting error (here by way of example)
15:17
Time of the resulting error (here by way of example)
Meaning of the error codes: pagepage 27
NOTICE
Maximum the last ve resulting errors are displayed.

15
We reserve the right to make technical changes | 83055200cDE – Translation of the original instruction manual (HMD 2) | ait-deutschland GmbH
HEAT QUANTITY
Many heat pump types are equipped with heat quantity recording
by pressure sensors in the cooling circuit of the heat pump. In the-
se heat pumps the heat quantity can be read out directly – for all
other units in the Luxtronik 2.0 series the external heat quantity
meter can be retrotted (accessory).
NOTICE
Note the number displayed in the top menu row (marked here
by the arrow). It provides information about which heat pump
is currently addressed..
In order to change the addressed heat pump, refer to the
section: page 10, “Changing the addressed heat pump in
submenus“
Heating Recorded heat quantity for heating in
kWh
Domestic hot water Recorded heat quantity for hot water in
kWh
Total Sum of the recorded heat quantities in
kWh
Since: 1.1.1970 Date of the last recording. (here by way
of example).
Go to and click the date to reset the heat quantity recording to ze-
ro. In this way the heat quantity can be recorded for a period de-
ned by you (start date = displayed date).
NOTICE
If applicable, after displaying the recorded heat quantity
for hot water, the recorded heat quantity for swimming
pool is displayed.
BACnet
DeviceID Unique identication number of the
unit in the BAC net network
DeviceName Name of the unit in the BAC net
network
Modelname Model designation of the unit
Location Location of the unit
Port
BAC net communication port of the unit
CALLING UP THE MACHINE STATUS
NOTICE
Note the number displayed in the top menu row (marked here
by the arrow). It provides information about which heat pump
is currently addressed..
In order to change the addressed heat pump, refer to the
section: page 10, “Changing the addressed heat pump in
submenus“
Type of heat pump Type of heat pump
Software version of the heating and heat pump
regulator
Bivalent level Bivalent level:
1 = a compressor may operate
2 = two compressors may operate
3 = additional heat generator
may operate as well
Operation mode Current operation mode:
Heating
Domestic hot water
Defros
Only for output-controlled heat pump:
Current capacity Heating output currently provided by
the output-controlled compressor.
This heating output can be used to set
the overow valve in a storage tank
integrated in series according to the
setting diagram in the unit instructions.
Capacity demand Required output for output-controlled
compressor controlled by the heating
and heat pump controller.
Software version SEC Current software version of the inverter
controller of the output-controlled heat
pump

16
We reserve the right to make technical changes | 83055200cDE – Translation of the original instruction manual (HMD 2) | ait-deutschland GmbH
CALLING UP SHORT PROGRAMS
Part 1 of the controller maunual, program area “Service“,
section “Calling up short programs“.
DETERMINING TEMPERATURES
NOTICE
Note the number displayed in the top menu row (marked here
by the arrow). It provides information about which heat pump
is currently addressed..
In order to change the addressed heat pump, refer to the
section: page 10, “Changing the addressed heat pump in
submenus“
The menu is not shown in full here. Further menu items appear if you scroll down the
screen.
Move to the respective required menu eld, activate, set the temperature value and con-
rm by pressing the “turn-push button“.
Finally scroll all the way down, cancel or save the settings.
Limit Return Return limit
Setting the maximum return setpoint temperatures in
heating mode.
X External temperature
Y Return temperature
A Heating curve-end point
B Return limit (in the example shown: 40°C)
MAKING SETTINGS
DETERMINE DATA ACCESS
Enter numbersn
entry elds of the four digits numerical code:
Activate the rst entry eld of the numerical code by
pressing the “turn-push button“.
Set the rst digit by turning the “turn-push button“ and
conrm the entry by pressing the button.
Move to the respective next entry eld and repeat the
steps described above.
Finally, move to “ “ and save the entries by pressing
the “turn-push button“.
The entry elds are automatically set to 0000. The cursor
goes automatically to the navigation arrow. The program
provides information in the menu line “Access” on the se-
lected status of the data access.
Datea access
Information on the current status of the data access
(here: user)
ATTENTION
After the service work, always reset the data access to cu-
stomer.
Incorrect settings not oriented towards the system com-
ponents can result in faults up to serious damage to the
system. Access to fundamental settings of the system must
therefore be locked for unauthorised persons.
NOTICE
The manufacturer is not liable for damage resulting from
wrong program settings not oriented towards the system
components.

17
We reserve the right to make technical changes | 83055200cDE – Translation of the original instruction manual (HMD 2) | ait-deutschland GmbH
Exception:
In the event of a fault and the setting fault with a 2 hg, the
second heat generators are released independently of the set
external temperature.
Tp-defr.Air.
Temperature air defrost
A value is only displayed for L/W devices and if the air defrost
is switched on.
Setting for the release temperature for the air defrost. Below
the set temperature, the air defrosting is locked.
ATTENTION
Set air defrost only if device type is approved for air de-
frost.
TDI-Solltemp.
TDI setpoint temperature
Setting for the setpoint temperature for the thermal
disinfection in the domestic hot water preparation.
Hysterese.DHW
Hysteresis of domestic hot water
Setting for the control hysteresis for the domestic hot water
preparation (negative hysteresis).
A There will be no request for domestic hot water
preparation in this temperature range
B There will be a request for domestic hot water
preparation in this temperature range
C Domestic hot water target
D negative hysteresis
Flow 2. CP DHW
Flow 2nd compressor Domestic hot water
Is only displayed for devices with 2 compressors.
Setting for the ow temperature from which domestic hot
water is prepared with a compressor.
Optimisation of the charging time and the attainable
domestic hot water temperatures..
T-outd. max
maximum external temperature
A value is only displayed for L/W devices
Setting for the maximum external temperature from which
the heat pump is locked.
Second heat generators are released as required..
T-outd. min
minimum external temperature
A value is only displayed for L/W devices.
Setting for the minimum external temperature under which
the heat pump is locked.
Second heat generators are released as required..
T-HG max
maximum hot gas temperature
Setting for the maximum permissible temperature in the
cooling circle of the heat pump.
T-def.airend
Temperature air defrost end
A value is only displayed for L/W devices and if the air defrost
is switched on.
Setting for the temperature at which the air defrosting is
terminated at the outlet of the evaporator.
Lowering to
Maximum lowering
Setting for the external temperature up to which a night
lowering is carried out.
Hysteresis HR
setting for the control hysteresis of the
heating regulator
Set a greater hysteresis for very reactive
heating systems, and a lower hysteresis
for less reactive heating systems.
Example: Hysteresis heating circle
return = 2K
A There will be no request for heating in this
temperature range
B There will be a request for heating in this
temperature range
C Hysteresis
D Neutral zone
E Return setpoint temperature
Hysteresis of output-controlled heat pump
This “Hysteresis HC” function is not available for output
controlled heat pumps. Here the return setpoint is controlled
by the output control of the compressor:
a a d c b
+4K
RS
RS Return setpoint
a Continuous operation of the heat pump with
individual heating output
b Switch o as soon as the setpoint is exceeded
by 4 K
c Switch on as soon as the temperature falls
below the return setpoint
d Activating the additional heat generator after
enable time, if the temperature is permanently
below the return setpoint and the compressor
operates with maximum output; switch back to
pure heat pump mode when return setpoint is
reached
RT incr.max
Return increase maximum
Setting for the maximum permissible overshoots of the return
temperature. If the return temperature is overshot, internal
minimum running times are ignored and all heat generators
switched o. Always set value higher than the value of the
hysteresis HC.
Release 2 CP
Release 2nd compresso
A value is only displayed for devices with two compressors.
Setting of the minimum external temperature from which the
second compressor can be released in heating mode. Above
the set external temperature, the second compressor remains
locked in heating mode
Release 2hg
Release second heat generator
Setting for the external temperature from which the second heat
generator can be released if required. Above the set external
temperature, the second heat generators remain locked.

18
We reserve the right to make technical changes | 83055200cDE – Translation of the original instruction manual (HMD 2) | ait-deutschland GmbH
Min. ow cooling
Minimum CoolingFlow temperature
If the temperature at the cooling sensor falls below this
temperature (depending on integration TB1, TB2 or TRL), the
cooling is interrupted (factory setting 18 °C). At the same time,
the displayed value is the minimum value for settable cooling
setpoint temperatures.
Scroll all the way down,
cancel or save the settings.
DETERMINING PRIORITIES
Part 1 of the controller manual, program area “Service“,
section “Determining priorities“.
DETERMINING SYSTEM SETTING
NOTICE
Note the number displayed in the top menu row (marked here
by the arrow). It provides information about which heat pump
is currently addressed..
In order to change the addressed heat pump, refer to the
section: page 10, “Changing the addressed heat pump in
submenus“
The menu is not shown in full here. Further menu items
appear if you scroll down the screen.
Activate and select the required parameters, make the re-
quired setting and conrm by pressing the “turn-push
button“.
Scroll all the way down, cancel or save the settings.
ATTENTION
Incorrect settings not oriented towards the system compo-
nents put the safety and functional capability of the sys-
tem at risk and can lead to damage.
If the actual external temperature falls below the set value,
the lowering temperature is ignored.
Flow Max.)
Maximum ow temperature
If this temperature is exceeded in the ow, a compressor of
the heat pump is switched o. This applies to all supply types!
Flow max. MK1
Maximum ow temperature following
the charger mixer
Is only displayed if mixing circle 1 is set to charger mixer.
The forward ow sensor at TB1 will then be used to limit the
ow temperature following the mixer. This means: if the TB1
exceeds the value set here, the charger mixer will be moved
in >Closed< direction.
min. AT Flow max.)
Heat source temperature-dependent
adjustment of the ow temperature.
Heat source temperature-dependent adjustment of the ow
temperature.
The outside temperature, up to which the ow max.
temperature with the heat pump may be increased, is
adjusted here.
Below this outside temperature, the actual VL maximum
temperature of the heat pump will fall linearally to the value
“Forward ow EG“.
Flow limit of applic. )
Heat source temperature-
dependent adjustment of the ow
temperature.
Here, the maximum forward ow temperature of the heat
pump is set at an outside temperature of -20°C.
For further details, see point “min. AT VL max.” and the
following diagrams:
VL
AT
-20°C min. AT Flow max.
Flow max.
Limitation
of use
VL = Forward ow
AT = outside temperature
Hysteresis 2.CP short
Hysteresis heating control
Shorten HR hysteresis. HR. Hysteresis heating regulator
from which the cut-in time of the 2nd. compressor stage is
shortened (See “System setting”).
Cutting-in compressor 2:
A No cut-in
B Shortened cut-in
C Return ow set value
D Heat regulator hysteresis
E Hysteresis HR shortened
Max. DHW temp.
Maximum Hot Water temperature
A value, which is set to limit the maximum set temperature of
the hot water.

19
We reserve the right to make technical changes | 83055200cDE – Translation of the original instruction manual (HMD 2) | ait-deutschland GmbH
NOTICE
For reversible LWD MK1 can also be set to “Hz+Cool” or
“Cooling” without the expansion board by using the t-
ter or customer service access. The cooling is controlled via
the return sensor.
hg1 type
Type of the second heat generator 1
No no 2 hg connected, system works,
monovalently
El,Rod Heating rod connected as 2 hg, system,
works mono-energetically
Boiler Boiler connected as 2 hg, system works
bivalently The “boiler” setting only
requires one
charger mixer as the boiler is switched
on continuously if required and the
temperature is not controlled by the
2nd heat gen. 1 output
Thermal
Thermal (gas boiler) connected as 2 hg,
is activated as heating rod, but can be
released during electrical supply o-tim
ZWE1 Fkt
Function of the second heat
generator1
No no 2 hg connected, system works,
monovalently
Heating 2 hg located as a heating rod in the,
buer tank
HW a. SW (Heating and domestic hot water) ZWE sitzt hydraulisch
2 hg located hydraulically in the ow of
the heat pump. 2 hg is own through
if the heating or domestic hot
water circulation pump is runnin
ATTENTION
In case of installed instantaneous water heaters, which are
located in the ow of the heat pump, „Hz u. WW“ must be
set as the function..
Error
Error
with 2hg in the event of a fault in the heat
pump, connected 2 hgs are energised
according to requirements (HW + SW)
no 2hg in the event of a fault in the heat pump,
connected 2 hgs are only energised
if the return temperature < 15 °C
(antifreeze); (only heating)
DHW 1
Domestic Hot Water 1
sensor Domestic hot water preparation is
initiated or terminated via a sensor on
the domestic hot water tank
Thermal Domestic hot water is initiated or
terminated via a thermostat on the
domestic hot water tank
NOTICE
Connect domestic hot water thermostat on the same ter-
minals as the domestic hot water sensor (low voltage). The
domestic hot water thermostat must be suitable for low
voltage (oating contact).
NOTICE
Enter deviations from the relevant factory settings in the
overview “System setting for the commissioning”.
pagpage 32, “System setting during commissioning“
El. sup. blockade
Electrical supply o-times
no 2hg 2hg at electrical supply o-time also
locked
with 2hg 2hg released for electrical supply
Setting only takes eect as 2 hg for boiler or thermal.
Rooms tat.
Room station (Room remote adjuster)
No No room remote adjuster connected
RFV Room remote adjuster connected
RBE Room control unit connected
Integration
Hydraulic Integration
Setting the hydraulic integration of the buer tank
Return (Return) hydraulic integration with row tank
(ow/return)
Sep. tank (separating tank)hydraulic integration with
parallel tank (multifunction tank,…)
NOTICE
Setting the hydraulic integration of the buer tank
Mixing circle 1
Mixing circle 1
Setting the functioning of the mixer control
Charge Mixer serves as charger mixer, possibly
for a boiler
A Boiler
B Heat pump
TB1 sensor ow (optional)
Discharge Mixer serves as a control mixer,
possibly for oor heating
TB1 sensor ow (optional)
Cool Mixer serves as a control mixer
for passive cooling function (LWD
reversible active)
No Mixer without function

20
We reserve the right to make technical changes | 83055200cDE – Translation of the original instruction manual (HMD 2) | ait-deutschland GmbH
Pump opt.
Pump optimisation
No Heating circulation pumps always
run, unless another supply type is
requested (domestic hot water, …) or
the device is switched o
Yes Heating circulation pumps are
switched o, if required
The heating circulation pumps will
be switched if the heat pump has
not been requested for more than 3
hours. The heating circulation pumps
will then cycle for 5 minutes every 30
minutes until the heat pump receives
another request.
If the external temperature is above
the return setpoint temperature, the
heating circulation pumps will be
switched o permanently. They will
be switched on for 1 minute every 150
hours to prevent them from becoming
stuck
Access.
Data access authorisation
The “Fitter” (= Qualied technicians) provides access to
parameters without a password, which otherwise requires
“Customer service” access.
Control CP
Compressor monitoring
O Compressor monitoring switched o
On Compressor monitoring switched on,
if the rotating eld of the supply line
is incorrect, a “Net On“ fault will be
detectedt
Error number 729, pagpage 27
While the compressor is starting up, compressor monitoring
checks the change in temperature in the hot gas. If the
temperature of the hot gas does not change while the
compressor is running, a malfunction is displayed..
ATTENTION
Only switch on compression monitoring for error locating
during maintenance work.
In the case of devices with a power supply monitor, the
compressor monitoring is switched o in the factory set-
ting.
Setting hc
Control of the heating circle
Set AT ow setpoint temperature of the
heating is calculated via a set heating
curve
Fixed Tp ow setpoint temperature can be
selected independently of the external
temperature specication
Settinng mc1
Regelung Mischkreis 1
Set AT return setpoint temperature of the
heating is calculated via a set heating
curve
Fixed Tp return ow setpoint temperature can
be selected independently of the
external temperature specication
Thermostat closed (= signal On) = Domestic hot water re-
quirement.
DHW 2
Domestic Hot Water 2
CP Setting CP means circulation pump.
For the corresponding settings, please refer to the descrip-
tion of the circulation pump in the operating manual in-
tended for end customers, found in program section “Do-
mestic hot water” under the section entitled “Circulation“.
h.wCP Setting h.w.CP means that the CP
output will be active during domestic
hot water preparation and switch o
30 seconds after domestic hot water
preparation is complete..
DHW 3
Domestic Hot Water 3
with CP Additional circulation pump runs
during domestic hot water preparation
no CP Additional circulation pump does
not run during domestic hot water
preparation
DHW 4
Domestic Hot Water 4
Sollwert Heat pump attempts to reach the set
setpoint value of the domestic hot
water temperature
DHW 5
Domestic Hot Water 5
with HSP Heating circulation pump runs during
domestic hot water preparation
no HSP Heating circulation pump does not run
during domestic hot water preparation
DHW+WP max
Maximum running time domestic hot
water preparation + Heat pump
After the set time has expired, the 2nd heat generator in the
domestic hot water preparation energises, but only if this has
been released previously in the heating mode!
Defr cycle max
Defrost cycle time, maximum time
between two defrost processes
Option only possible for L/W devices:
You can nd the time to be set for the relevant L/W device in
the operating instructions. If you do not nd any data there,
the following applies:
Defrost. Air
Air defrost
Option only possible for L/W devices:
No Air defrost not released
Yes Air defrost generally released above
the set temperature
Defr.Air max
Maximum duration of air defrost
Option only possible for L/W devices and if air defrost is
released
Defrost 2
Option only possible for L/W devices with 2 compressors
with 1CP Defrost with only one compressor
with 2CP Defrost with two compressors, if these
also supply before defrosting
Other manuals for Luxtronik
5
Table of contents
Other alphainnoTec Control Unit manuals
Popular Control Unit manuals by other brands

Guntermann & Drunck
Guntermann & Drunck G&D UCON-Audio-s Installation and operation

ABB
ABB FMBA-01 user manual

Ebyte
Ebyte E104-BT52 user manual

Agilent Technologies
Agilent Technologies Turbo-V user manual

Diankong Electronics
Diankong Electronics DK-BT-MUSIC-21A quick guide

JPEG Camera
JPEG Camera SC03MPE user manual