alphainnoTec Luxtronik User manual

83055400dUK – Translation of the original instruction manual (2.1)
UK
Operating Instructions
Luxtronik
Controller part 2 (Qualified technician)
Scope of delivery, Montage, Electrical connections
Software update
Commissioning / Switching on for the first time
Program area “Service“
Appendix
Heating- and Heat Pump Control

2
We reserve the right to make technical changes | 83055400dUK – Translation of the original instruction manual (2.1) | ait-deutschland GmbH
Please read rst
This operating manual is part 2 of the 2-part operating manual for
the heating and heat pump controller. Ensure that you have part 1
of this operating manual. If part 1 is missing, request it from your
supplier
This operating manual provides important information on the
handling of the unit. It is an integral part of the product and must
be stored so that it is accessible in the immediate vicinity of the
unit. It must remain available throughout the entire service life of
the unit. It must be handed over to subsequent owners or opera-
tors of the unit.
Read the operating manual before working on or operating the
unit. This applies in particular to the chapter on safety. Always fol-
low all instructions completely and without restrictions.
It is possible that this operating manual may contain instructions
that seem incomprehensible or unclear. In case of questions or
uncertainty, contact the factory customer service department or
the manufacturer’s local service partner.
This operating manual is intended only for persons assigned to
work on or operate the unit. Treat all constituent parts condenti-
ally. The information contained herein is protected by copyright.
No part of this information may be reproduced, transmitted, co-
pied, stored in electronic data systems or translated into another
language, either wholly or in part, without the express written
permission of the manufacturer
Symbols
Information for operators.
Information or instructions for qualied technicians and
authorised service personnel.
DANGER!
Indicates a direct impending danger resulting in severe
injuries or death.
DANGER!
Indicates danger to life due to electric current!
WARNING!
Indicates a possibly dangerous situation that could re-
sult in severe injuries or death.
CAUTION!
Indicates a possibly dangerous situation that could re-
sult in medium or light injuries.
ATTENTION
Indicates a possibly dangerous situation, which could re-
sult in property damage.
NOTICE
Emphasized information.
€
ENERGY SAVINGTIP
Indicates suggestions that help to save energy, raw mate-
rials and costs.
Users and qualied technicians can set data.
Authorized tter can set data; password required.
Authorised service personnel can set data. Access via
USB stick only.
Factory pre-setting, no data change possible
Reference to other sections in the operating instructions.
Reference to other documents of the manufacturer.

3
We reserve the right to make technical changes | 83055400dUK – Translation of the original instruction manual (2.1) | ait-deutschland GmbH
Contents
MAKING SETTINGS
................................................................................................17
Determine data access...............................................................................17
Calling up short programs...................................................................... 18
Determining temperatures.................................................................... 18
Determining system setting.................................................................. 20
Determining priorities ..............................................................................20
Ventilating the system.............................................................................. 24
Fix Startup parameters............................................................................. 25
energy eciency pump...........................................................................25
Second heat generator............................................................................. 26
SILENT MODE, ONLY LWCV, LWV, LWAV, LWP
............................................. 26
HOT GAS UTILISATION, ONLY LWP
................................................................. 27
SELECTING LANGUAGE OF THE SCREEN DISPLAY
.....................................28
DETERMINING DATE AND TIME
....................................................................... 28
Setting temperatures and time intervals....................................... 28
SCREED HEATING PROGRAM
............................................................................ 28
Starting screed heating program....................................................... 28
Manually terminating screed heating program......................... 29
SYSTEM CONFIGURATION
.................................................................................29
STARTUP GUIDE
....................................................................................................30
STARTUP GUIDE PARAMETERS BACK
............................................................. 30
DATA LOGGER
........................................................................................................ 31
CONTROL PANEL
................................................................................................... 31
Adjusting the contrast of the
control element display....................................................................... 31
Web server....................................................................................................... 31
Remote maintenance................................................................................ 31
APPENDIX
ERROR DIAGNOSIS / ERROR MESSAGES.................................................. 32
Acknowledging a fault................................................................................. 35
Flashing codes on controller board...................................................... 35
TECHNICAL DATA .................................................................................................. 36
Installation ..........................................................................................................36
Outputs ................................................................................................................ 36
Inputs..................................................................................................................... 36
Connections....................................................................................................... 36
Interfaces.............................................................................................................36
Protection class................................................................................................36
Temperature sensor characteristic curve.......................................... 37
Sensor measuring range............................................................................. 37
OVERVIEW: DEFROST CYCLE, AIR DEFROST, FLOW MAX .............38
SYSTEM SETTING DURING COMMISSIONING...................................... 39
IMPORTANT ABBREVIATIONS........................................................................ 42
INFORMATION FOR USERS, QUALIFIED TECHNICIANS AND
AUTHORISED SERVICE PERSONNEL
PLEASE READ FIRST.................................................................................................2
SYMBOLS.......................................................................................................................2
SCOPE OF DELIVERY, MONTAGE, ELECTRICAL CONNECTIONS,
INSTALLATION OF SENSORS, DISMANTLING
SCOPE OF DELIVERY...............................................................................................5
Installed control scope of supply..............................................................5
Wall control scope of supply, LW169H(A)V..........................................5
MONTAGE......................................................................................................................5
Installing the installation control..............................................................5
Assembly of the wall control, LW169H(A)V .........................................5
ELECTRICAL CONNECTIONS..............................................................................6
Installation of the Wall control...................................................................6
Control unit variants ........................................................................................8
Assembly and Installation of Sensors.....................................................9
Hot water sensor.............................................................................................9
External return ow sensor.......................................................................9
DISMANTLING ......................................................................................................... 10
Removal of the buer battery................................................................. 10
SOFTWAREUPDATE.............................................................................................. 10
COMMISSIONING / SWITCHING ON
FOR THE FIRST TIME..................................................................................... 10
SMART GRID
........................................................................................................... 12
Adjustable under system settings:................................................. 12
Terminal diagram...................................................................................... 12
PROGRAM AREA “SERVICE“
SEKECT PROGRAM AREA
.................................................................................... 14
QUERY INFORMATION
......................................................................................... 14
Query Temperatures.................................................................................. 14
Query inputs................................................................................................... 14
Query outputs............................................................................................... 15
Calling up timings ....................................................................................... 15
Query operating hours............................................................................. 15
Calling up error memories...................................................................... 16
Calling up disconnections ...................................................................... 16
Calling up the machine status.............................................................. 16
Heat quantity ..................................................................................................17
BACnet ................................................................................................................17

4
We reserve the right to make technical changes | 83055400dUK – Translation of the original instruction manual (2.1) | ait-deutschland GmbH

5
We reserve the right to make technical changes | 83055400dUK – Translation of the original instruction manual (2.1) | ait-deutschland GmbH
Montage
INSTALLING THE INSTALLATION CONTROL
In the case of devices for internal mounting, the control card of
the heating and heat pump is integrated in the electrical switch
cabinet of the device.
Operating instructions of your heat pump, assembly of
the operating element
ASSEMBLY OF THE WALL CONTROL, LW160HAV,
LW161HAV
For all work to be carried out:
NOTICE
Observe the locally-applicable accident prevention regula-
tions, statutory provisions, ordinances and directives.
WARNING!
Only qualied technicians may mount the heating and
heat pump control.
Position the drill template at the point where the heating and
heat pump control is to be located.
ATTENTION
Check the potential mounting location for concealed wi-
ring. Position the drill template in such way that no con-
cealed wiring can be drilled into or damaged during the
subsequent assembly work.
NOTICE
You need to ensure ≥ 2 cm free space to the right and left
of the drill template, so that there is enough space for the
side fastening screws of the housing cover.
Fix drill template onto the wall with adhesive tape, drill holes
(Ø 6 mm, depth ≥ 55 mm).
Take drill template o the wall, insert dowels in the holes,
screw in screws (spacing from the substrate to the screw head
approximately 10mm).
Scope of delivery
NOTICE
Function-critical temperature sensors (return, inlet, hot
gas) are installed in the heat pump and are not part of the
scope of supply of the heating and heat pump regulator.
The heating and heat pump regulator is supplied in two variants.
The variant supplied is dependent on the device type of the heat
pump to the controlled.
INSTALLED CONTROL SCOPE OF SUPPLY
In the case of devices for internal mounting, the control card of
the heating and heat pump regulator is integrated in the relevant
device as an “installed control”. The “installed control” scope of
supply is included in the scope of supply of the device for inter-
nal mounting.
• Heating and heat pump regulator,
• consisting of control card (with terminals) and operating ele-
ment (with status display, screen and “rotary pushbutton”).
• External sensor for the surface mounting.
• operating manual.
• “Brief description of the heat pump control”.
WALL CONTROL SCOPE OF SUPPLY, LW160HAV,
LW161HAV
In the case of devices for external mounting, the control card of
the heating and heat pump control is not integrated in the rele-
vant device. The “wall control” scope of supply is not included in
the scope of supply of the device for external mounting.
• Heating and heat pump control for surface mounting,
• consisting of control card (with terminals), housing and ope-
rating element (with status display, screen and “rotary push-
button”).
• Wall mounting materials (drill template, screws, dowels for so-
lid masonry).
• External sensor for the surface mounting.
• Operating instructions.
• “Brief description of the heat pump control“.
What to do rst:
Check the supplied product for signs of external damage du-
ring delivery.
Check that nothing is missing from the scope of supply. Imme-
diately submit a complaint in the event of delivery defects.

6
We reserve the right to make technical changes | 83055400dUK – Translation of the original instruction manual (2.1) | ait-deutschland GmbH
Electrical connections
DANGER!
Danger of fatal injury due to electric current!
Electrical connections may be installed only by qualied
electricians.
Before opening the unit, disconnect the system from the
power supply and secure it from being switched back on!
WARNING!
During installation and while carrying out electrical
work, comply with the relevant EN-, VDE and/or local sa-
fety regulations.
Comply with technical connection requirements of the
responsible power supply company (if required by the
latter)!
Follow the information in the operating instructions of your heat
pump for establishing the electrical connections.
Operating instructions of your device, “Electrical Con-
nections“, “Terminal Diagram“ and “Circuit Diagrams“ for
your device type
NOTICE
Internal fuse 6,3AT.
INSTALLATION OF THE WALL CONTROL
If not yet carried out: Remove housing cover of the heating
and heat pump contro.
pagpage 6, Instruction –
NOTICE
The wall mounting material included in the scope of sup-
ply requires solid masonry.
Loosen right and left fastening screw of the housing cover for
the heating and heat pump contro.
Remove housing cover and set aside in a safe place.
Hang the heating and heat pump control into the screws on
the wall. Tighten the screws..
1 Rear view 2 Front view
If the electrical installation is not to be carried out immediate-
ly afterwards: Put the housing cover back on and tighten the
side fastening screws.

7
We reserve the right to make technical changes | 83055400dUK – Translation of the original instruction manual (2.1) | ait-deutschland GmbH
1 Connected 1~/N/PE/230 V power supply for
wall-mounted controller and outdoor unit
2 Connected TRL return sensor (on NTC8)
3 Laying cables in the cable ducts
4 Connected BUS communication cable
5 Connected PWM control signal for circulation pump
If necessary, install additional external cables.
Instruction manual for your appliance, “Connection
layout” and “Circuit diagrams” for your appliance type
NOTICE
The inputs and outputs on the control board are assigned
as shown on the device’s terminal connection diagram.
In addition, the assignment is shown on the inside of the
housing of the wall-mounted controller.
Place covers on the cable ducts. Swivel folding bracket of the
cable entry back into the initial position and allow to latch into
place below the fastening screw. Tighten fastening screw.
Put the housing cover back on and tighten the side fastening
screws..
ATTENTION
1 Terminal block for 1~/N/PE/230 V voltage supply
2 EVU bridges (must be removed when
connecting a oating contact)
3 TRL return sensor terminal (on NTC8)
4 Cable ducts with covers (covers now
shown here in the gure)
5 Cable entry with folding bracket
6 Fastening screw of the folding bracket
7 Terminal (X10 Modbus) for BUS cable to the outdoor unit
8 Slot for optional “2.1-EP” circuit board
9 LIN-BUS communication cable between control
board and control unit (wired in the factory)
10 Control card of the heating and heat pump control
11 Operating element
12 Connection for circulation pump PWM control signal
Loosen fastening screw of the folding bracket for the cable
entry and pull the folding bracket downwards until it is pos-
sible to fold away upwards. Fold folding bracket upwards and
away to the side .
Remove covers from the cable ducts.
Connect the BUS communication cable, which leads to the he-
at pump, to terminal X10 of the controller board.
Then route the BUS communication cable downwards and
through the cable ducts and through the cable entry to the
outside.
ATTENTION
The BUS communication cable and power cables must be
laid with a spacing > 10 cm between them.
Connect the 230 V voltage supply line to the voltage supply
terminal block.
NOTICE
Internal fuse 6.3AT.
The terminal block has spring-type terminals to maximum
2.5 mm2.
Insulate the cable jacket so that the jacket end is located
between the sealing lip and cable duct..
Connect the 230V power supply for the outdoor unit to the
terminal block and route it downwards through the cable
ducts and through the cable entry to the outdoor unit outside.
Connect the PWM control signal for the circulation pump to
the terminal block --X10.
A separately packed return sensor (TRL) with appropriate in-
stallation materials is enclosed with the air/water heat pump
for outdoor installation. Use cable ties and heat transfer com-
pound to x the return sensor to the return (heat-conducting
pipe) to the heat pump as shown in the gure and connect (to
NTC8) as shown in the circuit diagram.
Basic wirng:

8
We reserve the right to make technical changes | 83055400dUK – Translation of the original instruction manual (2.1) | ait-deutschland GmbH
CONTROL UNIT VARIANTS
Depending on the heat pump type, the control unit integrated in
the heating and heat pump controller is equipped with the fol-
lowing interfaces:
TYPE 1
N Network
S Connection to the control board
TYPE 2
N Netwoerk
L LIN-BUS
S Connection to the control board
TYPE 3
R RS485 for connecting the
room control unit (RBE)
N Network
L LIN-BUS to the control board
S not assigned, LWV, LWCV, LWAV Mod-Bus
Route all lines that you connect to the heating and heat
pump control outside the heating and heat pump in a
cable duct (necessary for strain relief; to be realised at the
customer).
ATTENTION
The BUS communication cable must be laid at a spacing >
10 cm from other cables. Therefore, lay with the appropri-
ate spacing in a separate cable duct.
1 230 V power supply to the outdoor unit
2 PWM control signal for circulation pump
3 other 230 V outputs (circulation pumps, mixers, etc.)
4 BUS communication cable to the outdoor unit
5 Sensor cables including the TRL return sensor
on the return to the heat pump
6 other 230 V inputs (electricity outage etc.)
7 1~/N/PE/230V power supply (to the terminal block);
cable cross-section max. 2.5 mm², internal fuse 6.3 AT
K Cable ducts
Installation instructions for this in the operating instruc-
tions of your heat pump.

9
We reserve the right to make technical changes | 83055400dUK – Translation of the original instruction manual (2.1) | ait-deutschland GmbH
HOT WATER SENSOR
The domestic hot water sensor is an optional accessory and only
functionally-relevant for a separate domestic hot water tank. You
may only use domestic hot water sensors which have been appro-
ved by the manufacturer of the heat pump..
ATTENTION
The domestic hot water tank must be lled before connec-
ting the domestic hot water sensor to the heating and heat
pump regulator.
If not already prepared at the factory, mount the domestic hot
water sensor (Ø = 6 mm) on the halfway level of the domestic hot
water tank – and always above the internal heat exchanger of the
domestic hot water tank.
1 Hot-water tank
2 Domestic hot water sensor (Ø = 6 mm)
3 Heat exchanger
4 Cold water connection
5 Domestic hot water connection
EXTERNAL RETURN FLOW SENSOR
The return ow sensor (optional accessory) is functionally-rele-
vant for hydraulic integration of an isolating tank (multifunction
tank .). This has to be installed as follows:
ZUP TRLext HUP
1 Separation or multi-functional storage tank
2 Circulation pump in the separation
storage tank (heat pump circuit)
3 Circulation pump from the separation
storage tank (heating circuit)
4 External return sensor (Ø = 6 mm)
ZUP Charging loop, heat pump
HUP Discharging loop, heating circuit
Connect the return ow sensor coming from the isolating tank to
the circuit board of the heating and heat pump regulator.
ASSEMBLY AND INSTALLATION OF SENSORS
The external sensor is a function-critical accessory and included
in the scope of supply.
NOTICE
If the external sensor is not installed or defective, the hea-
ting and heat pump regulator automatically sets the exter-
nal temperature to -5 °C. The status display of the opera-
ting element lights up red, the screen of the operating ele-
ment reports a fault.
ATTENTION
Mount the external sensor on the north or northeast side
of buildings. The sensor must not be exposed to direct
sunlight.
Open the housing of the external sensor and align ≥ 2 m over
the base of the fastening point. The cable gland must point
to the base.
1 xternal sensor housing
2 Fastening holes
3 Cable gland
4 External sensor
Pencil on fastening holes and drill, insert dowels and screw
housing of the external sensor onto the wal.
NOTICE
Dowels and screws for fastening the external sensor are
not included in the scope of supply.
Loosen cable gland from the housing of the external sensor,
lead the 2-wire cable (Ø ≤ 1.5 mm² per wire, cable length ≤ 50
m) through the cable gland into the housing.
Clamp on cable, tighten cable gland and close the housing of
the external sensor.

10
We reserve the right to make technical changes | 83055400dUK – Translation of the original instruction manual (2.1) | ait-deutschland GmbH
Dismantling
DANGER!
Danger of fatal injury due to electric current!
Electrical connections may be installed only by qualied
electricians.
Before opening the unit, disconnect the system from the
power supply and secure it from being switched back
on!
REMOVAL OF THE BUFFER BATTERY
ATTENTION
Before scrapping the heating and heat pump regulator, re-
move the buer battery on the main board. You can use
a screwdriver to remove the battery from its bracket. Dis-
pose of battery and electronic components in keeping
with environmental considerations.
Softwareupdate
A software version < V2.63 must no longer be loaded on a unit
(only LWD... and SWP371-SWP691 and SWP291H-SWP561H) with
software version ≥V2.63..
Output-controlled air/water heat pumps may only be operated
with software version V3.xx and higher..
Commissioning / Switching on
for the rst time
When switched on for the rst time the language selection ap-
pears rst.
Select the display language: part 1 of the conroller
manual, section “Basis information on the operation“.
You see:
When the heat pump is switched on for the rst time the
above display appears.
The display always appears when the controller is swit-
ched on or on changing to the standards menu. This
screen is no longer displayed if the heat pump or ZWE1
has more than 10 operating hours.
No ZWE (second heat generator) is released by the controller until
the display is conrmed with OK.
NOTICE
No heat generator runs during a cold start of air/water heat
pumps.
ATTENTION
The unit can be damaged if the display is conrmed with
OK, although the system is not properly lled.
On switching on the controller voltage, under certain circum-
stances the following is displayed:
After deleting this display the unit can be operated properly.
Otherwise test the 3 pole cable for the BUS connection.
The following display then appears:
NOTICE
The heating phase until the compressor starts can take se-
veral hours when starting up air/water heat pumps for the
rst time.

11
We reserve the right to make technical changes | 83055400dUK – Translation of the original instruction manual (2.1) | ait-deutschland GmbH
NOTICE
In the case of LWD units the ow is monitored while the
pump is running. If the ow is not ok, the heat pump does
not start up and no error is displayed. To this end, check
the ASD input, if it is not set to ON the ow is too low.
page 14, “Query inputs“
The selection possibility for the heat source for SWP:
NOTICE
For SWP it is necessary to select whether water or brine
is to be used as the heat source uid, otherwise the unit
doesn’t work. The set uid can be viewed under System
Settings and can be changed from Customer Service ac-
cess level. TWQ-Min can be changed using the customer
service access, if brine is selected. For Low pressure cut-o
value with water: 7 bar. For Low pressure cut-o value with
brine: 4 bar.
Brine
This setting must be selected if the heat pump is opera-
ted with a brine - water mixture. Whether probes or sur-
face collectors are used is irrelevant.
Water |/| Brine
This setting must be selected if the heat pump is opera-
ted with an intermediate heat exchanger, and water is
used as the heat source medium on the primary side and
a brine-water mixture is used on the secondary side.
Water |/| Water:
This setting must be selected if the heat pump is opera-
ted with an intermediate heat exchanger and water is
used as the heat source medium on the primary and on
the secondary side. For the water/water setting the heat
source inlet temperature must be at least 7°C or higher.
Further Informations: page 30, “Startup guide“ and
page 30, “Startup guide parameters back“

12
We reserve the right to make technical changes | 83055400dUK – Translation of the original instruction manual (2.1) | ait-deutschland GmbH
SMART GRID
Use of the Smart Grid option depends on the unit type and soft-
ware version.
If you have any questions regarding the availability of the Smart
Grid functionality in your electricity tari, please contact your
electricity supply company
The function is connected via two contacts of the utility lock,
from which four possible operating states result.
.NOTICE
If utility lock is applied, the Smart Grid functional may not
be activated.
ADJUSTABLE UNDER SYSTEM SETTINGS:
Current operating state visible under Information->Inputs
Operating state 1 (1:0)
Corresponds to the current utility lock.
Operating state 2 (0:0) - deviation from standard control behavi-
our:
The heat pump operates exclusively within the range of the set-
point hysteresis (i.e. below the setpoint).
Heating: If the system temperature drops to below the lower hy-
steresis, the heat pump is switched on and heats the system up to
the setpoint. The upper hysteresis is ignored. The heat pump on-
ly heats until there is no longer any need to worry about possi-
ble comfort losses. Domestic water heating takes place as normal.
Operating state 3 (0:1) - corresponds to standard control behavi-
our:
The target temperature is the set setpoint temperature for hea-
ting and domestic hot water. These set temperatures are held ta-
king into account the respective hystereses.
Operating state 4 (1:1) - deviation from standard control behavi-
our:
The heat pump operates exclusively within the range of the set-
point + hysteresis (i.e. above the setpoint).
Heating: If the system temperature drops to the setpoint, the he-
at pump is switched on and heats the system up to the setpoint +
hysteresis points
DHW: The controller generates a positive hysteresis whose magni-
tude is equal to the lower hysteresis and regulates in this area (set
temperature + upper hysteresis).
TERMINAL DIAGRAM
SW H3
•
SWCV H1/H3
•
WZSV H3
•
PWZSV H1/H2/H3
Klemmenplan SG-Ready IO-Max
-
-X4 -X3-2
SG1
SG2
Legende:
Betriebsmittel
A1
A3
SG1
SG2 IN5
IN6
DE
Funktion
Reglerplatine; Achtung: I-max = 6,3A/230VAC
Unterverteilung Hausinstallation
Smart Grid Ansteuerung 1
Smart Grid Ansteuerung 2
831211
123 45678
12 8
A
B
C
D
E
F
A
B
C
D
E
F
Blatt
Bl.
1
1
3 4567
AIT 831211
Klemmenplan
ait-deutschland GmbH
L1
L1
L1
L
2
2
IN1
IN2
IN3A1A2A1A2
IN4
IN5
IN6
IN7
A3
A1
Änderung Datum
Datum
Bearbeiter
Geprüft
NormName
09.10.2015
Pfleger
R.
Klemmenplan SG-Ready IO-Max
-
-X4 -X3-2
SG1
SG2
Legend:
Equipement
A1
A3
SG1
SG2 IN5
IN6
UK
Function
Controller board; Attention: I-max = 6,3A/230VAC
Sub-distribution unit internal installation
Smart Grid activation 1
Smart Grid activation 2
831211
123 45678
12 8
A
B
C
D
E
F
A
B
C
D
E
F
Blatt
Bl.
1
1
3 4567
AIT 831211
Klemmenplan
ait-deutschland GmbH
L1
L1
L1
L
2
2
IN1
IN2
IN3A1A2A1A2
IN4
IN5
IN6
IN7
A3
A1
Änderung Datum
Datum
Bearbeiter
Geprüft
NormName
09.10.2015
Pfleger
R.

13
We reserve the right to make technical changes | 83055400dUK – Translation of the original instruction manual (2.1) | ait-deutschland GmbH
Klemmenplan SG-Ready HZ-I/O
-
-X4 -X3-2
SG1
SG2
Legend:
Equipement
A1
A3
SG1
SG2 IN3
IN4
UK
Function
Controller board; Attention: I-max = 6,3A/230VAC
Sub-distribution unit internal installation
Smart Grid activation 1
Smart Grid activation 2
831210
123 45678
12 8
A
B
C
D
E
F
A
B
C
D
E
F
Blatt
Bl.
1
1
3 4567
AIT 831210
Klemmenplan
ait-deutschland GmbH
L1
L1
L1
L
2
2
IN1
IN2
IN3A1A2A1A2
IN4
IN5
A3
A1
Änderung Datum
Datum
Bearbeiter
Geprüft
NormName
09.10.2015
Pfleger
R.
LWCV
•
LWDV
•
LWA HV
• LWP
Klemmenplan SG-Ready HZ-I/O
-
-X4 -X3-2
SG1
SG2
Legende:
Betriebsmittel
A1
A3
SG1
SG2 IN3
IN4
DE
Funktion
Reglerplatine; Achtung: I-max = 6,3A/230VAC
Unterverteilung Hausinstallation
Smart Grid Ansteuerung 1
Smart Grid Ansteuerung 2
831210
123 45678
12 8
A
B
C
D
E
F
A
B
C
D
E
F
Blatt
Bl.
1
1
3 4567
AIT 831210
Klemmenplan
ait-deutschland GmbH
L1
L1
L1
L
2
2
IN1
IN2
IN3A1A2A1A2
IN4
IN5
A3
A1
Änderung Datum
Datum
Bearbeiter
Geprüft
NormName
09.10.2015
Pfleger
R.

14
We reserve the right to make technical changes | 83055400dUK – Translation of the original instruction manual (2.1) | ait-deutschland GmbH
Room temperatures Is displayed if the room control unit is
connected
In addition – depending on the unit type of the connected heat
pump – the cooling circuit information provided by sensors in the
cooling circuit appears here.
QUERY INPUTS
The menu is not shown in full here. Further menu items
appear if you scroll down the screen.
NOTICE
This menu shows whether the digital inputs of the control-
ler are switched on or o.
Defr/Brin/Flow Defrost, Brine pressure, ow
Depending on the device type, the input can full various
functions:
For L/W-devices Defrost end pressostat:
On = Defrost is terminated.
For LWD, S/W and W/W devices with ow switch connected at
the factory:
On = Flow okay.
For S/W devices without ow switch connected at the factory, a
brine pressostat can be connected:
On = brine pressure sucient.
SW-therm. switch Domestic hot water thermostat
On = Domestic hot water requirement
Electr. suppl. O-time of the electrical supply
O = O-time
High pressure High-pressure pressostat
O = Pressure okay
Motor protect. Motor protection
On = Motor protection okay.
Low pressure Low pressure pressostat
On = Pressure okay.
PEX Connection of an external current
anode
(possible for some devices)
AIn Input analog
Program area “Service“
SEKECT PROGRAM AREA
QUERY INFORMATION
QUERY TEMPERATURES
The menu is not shown in full here. Further menu items
appear if you scroll down the screen
.
Inlet Flow temperature heating circle
Return Return ow temp. of heating circle
Ret. targ. Return setpoint heating circle
Return external Return temp. in separate tank.
Hot gas Hot gas temperature
amb. temp. External temperature
Mean temperature Average temperature
outside over (function heating limit)
Act. service water Domestic hot water actual
temperature
Targ. service water Domestic hot water target
temperature
Heats in Heat source inlet temperature
Heats out Heat source outlet temperature
Mixing circle 1 fore. Mixing circle 1
Forward ow temperature
Mixing circle 1 desir. Mixing circle 1
Forward ow set temperature

15
We reserve the right to make technical changes | 83055400dUK – Translation of the original instruction manual (2.1) | ait-deutschland GmbH
CALLING UP TIMINGS
The menu is not shown in full here. Further menu items
appear if you scroll down the screen
.
HP since Heat pump running since
(Time indication respectively in
hh:mm:ss)
2 hg 1 since Second heat generator 1 running since
2 hg since Second heat generator 2 running since
Switch on Net input delay
Swi c time O-time switching cycle
Read-CPd Compressor Read-CPd
HC Add-time Heating control more time
HC Less-time Heating time less time
ThDsin.sin Thermal disinfection running since
Stop SW O-time domestic hot water
Defrosting Time until the next defrosting (LW)
QUERY OPERATING HOURS
The menu is not shown in full here. Further menu items
appear if you scroll down the screen
.
Op. h. comp1 Operation hours compressor 1
Impulses comp. 1 Impulses compressor 1
Duration comp. 1 average duration compressor 1
Op. h. comp2 Operation hours compressor 2
Impulses comp. 2 Impulses compressor 2
Duration comp. 2 average duration compressor 2
Operation hours 2hg1 Operation hours second heat
generator 1
Operation hours 2hg2 Operation hours second heat
generator 2
Operation hours hp Operation hours Heat pump
Operation hours heat Operation hours Heating
Operation hours hw Operation hours
Domestic hot water
Operation hours cool Operation hours Cooling
NOTICE
The compressors are only energised alternately follow-
ing the impulses. A variation in the operation hours of the
compressors is, therefore, possible.
QUERY OUTPUTS
The menu is not shown in full here. Further menu items
appear if you scroll down the screen.
CV-Defrost. valve Valve / Circuit reversal
ON = Thaw mode or rather cycle
reversal becomes active
DHW pump Domestic hot water circulation pump
Floor heat. pump 1 Floor heating circulation pump
Heat. sys. pump Heating circulation pump
Mixer 1 Open Mixer 1 opens
On = opens / O = no control
Mixer 1 Close Mixer 1 Close
On = closes / O = no control
Ventilation Ventilation of the heat pump housing
for certain L/W devices.
For L/W size types (coding “L2G”),
second stage of the ventilator
Fan-heats. pump Ventilator, well or brine circulation
pump
Compressor 1 Compressor 1 in heat pump
Compressor 2 Compressor 2 in heat pump
CP Circulation pump
Suppl. pump Additional circulating pump
2nd heat gen. 1 Second heat generator 1
2nd heat gen. 2 Second heat generator 2– Collective
fault (function collective fault:
Continuous ON in the event of a fault,
cycles 1x per second with automatic
RESET enabled)
Control signal UWP Circulation pump output in %
RPM Ventilator Current speed of the heat pump’s fan
RPM Compressor Current speed of the heat pump’
compressor

16
We reserve the right to make technical changes | 83055400dUK – Translation of the original instruction manual (2.1) | ait-deutschland GmbH
CALLING UP THE MACHINE STATUS
Type of heat pump Type of heat pump
Software version of the heating and heat pump
regulator
Bivalent level Bivalent level:
1 = a compressor may operate
2 = two compressors may operate
3 = additional heat generator
may operate as well
Operation mode Current operation mode:
Heating
Domestic hot water
Defros
Only for output-controlled heat pump:
Current capacity Heating output currently provided by
the output-controlled compressor.
This heating output can be used to set
the overow valve in a storage tank
integrated in series according to the
setting diagram in the unit instructions.
Capacity demand Required output for output-controlled
compressor controlled by the heating
and heat pump controller.
Software version SEC Current software version of the inverter
controller of the output-controlled heat
pump
CALLING UP ERROR MEMORIES
720
Error code (here by way of example)
04.08.08
Date of the resulting error (here by way of example)
15:17
Time of the resulting error (here by way of example)
Meaning of the error codes: page 32
NOTICE
Maximum the last ve resulting errors are displayed.
CALLING UP DISCONNECTIONS
04.08.08
Date of the disconnection (here by way of example)
17:28
Time of the disconnection (here by way of example)
hp / hp fault
Disconnection code (here by way of example)
Error hp = heat pump fault
err.inst. = system fault
m.o. 2hg = mode of operation second heat
generator
El. Sup. bl = el. sup. blockade
Defr. air. = air defrost (only L/W devices)
TPLmax = temperature limits of application
maximum
TPLmin = temperature limits of application
minimum
(in reversible LWD possible shutdown due to frost protection in
cooling mode - evaporation too long
below 0°C)
Low lim = lower limit of application
no requ. = no request
NOTICE
Maximum the last ve disconnections are displayed.

17
We reserve the right to make technical changes | 83055400dUK – Translation of the original instruction manual (2.1) | ait-deutschland GmbH
MAKING SETTINGS
DETERMINE DATA ACCESS
Enter numbersn
entry elds of the four digits numerical code:
Activate the rst entry eld of the numerical code by
pressing the “turn-push button“.
Set the rst digit by turning the “turn-push button“ and
conrm the entry by pressing the button.
Move to the respective next entry eld and repeat the
steps described above.
Finally, move to “ “ and save the entries by pressing
the “turn-push button“.
The entry elds are automatically set to 0000. The cursor
goes automatically to the navigation arrow. The program
provides information in the menu line “Access” on the se-
lected status of the data access.
Datea access
Information on the current status of the data access
(here: user)
ATTENTION
After the service work, always reset the data access to cu-
stomer.
Incorrect settings not oriented towards the system compo-
nents can result in faults up to serious damage to the sys-
tem. Access to fundamental settings of the system must
therefore be locked for unauthorised persons.
NOTICE
The manufacturer is not liable for damage resulting from
wrong program settings not oriented towards the system
components.
HEAT QUANTITY
Many heat pump types are equipped with heat quantity recording
by pressure sensors in the cooling circuit of the heat pump. In the-
se heat pumps the heat quantity can be read out directly – for all
other units in the Luxtronik 2.0 series the external heat quantity
meter can be retrotted (accessory).
Heating Recorded heat quantity for heating in
kWh
Domestic hot water Recorded heat quantity for hot water
in kWh
Total Sum of the recorded heat quantities in
kWh
Since: 1.1.1970 Date of the last recording. (here by way
of example).
Go to and click the date to reset the heat quantity recording to ze-
ro. In this way the heat quantity can be recorded for a period de-
ned by you (start date = displayed date).
NOTICE
If applicable, after displaying the recorded heat quantity
for hot water, the recorded heat quantity for swimming
pool is displayed.
BACnet
DeviceID Unique identication number of the
unit in the BAC net network
DeviceName Name of the unit in the BAC net
network
Modelname Model designation of the unit
Location Location of the unit
Port BAC net communication port of the
unit

18
We reserve the right to make technical changes | 83055400dUK – Translation of the original instruction manual (2.1) | ait-deutschland GmbH
A There will be no request for heating in this
temperature range
B There will be a request for heating in this
temperature range
C Hysteresis
D Neutral zone
E Return setpoint temperature
Hysteresis of output-controlled heat pump
This “Hysteresis HC” function is not available for output
controlled heat pumps and LW160H(A)V. Here the return
setpoint is controlled by the output control of the
compressor:
a a d c b
+4K
RS
RS Return setpoint
a Continuous operation of the heat pump with
individual heating output
b Switch o as soon as the setpoint is exceeded
by 4 K
c Switch on as soon as the temperature falls
below the return setpoint
d Activating the additional heat generator after
enable time, if the temperature is permanently
below the return setpoint and the compressor
operates with maximum output; switch back to
pure heat pump mode when return setpoint is
reached
RT incr.max
Return increase maximum
Setting for the maximum permissible overshoots of the return
temperature. If the return temperature is overshot, internal
minimum running times are ignored and all heat generators
switched o. Always set value higher than the value of the
hysteresis HC.
Release 2 CP
Release 2nd compresso
A value is only displayed for devices with two compressors.
Setting of the minimum external temperature from which the
second compressor can be released in heating mode. Above
the set external temperature, the second compressor remains
locked in heating mode
Release 2hg
Release second heat generator
Setting for the external temperature from which the second
heat generator can be released if required. Above the set
external temperature, the second heat generators remain
locked.
Exception:
CALLING UP SHORT PROGRAMS
Part 1 of the controller maunual, program area “Service“,
section “Calling up short programs“.
DETERMINING TEMPERATURES
The menu is not shown in full here. Further menu items
appear if you scroll down the screen.
Move to the respective required menu eld, activate, set
the temperature value and conrm by pressing the “turn-
push button“.
Finally scroll all the way down, cancel or save the settings.
Limit Return Return limit
Setting the maximum return setpoint temperatures in
heating mode.
X External temperature
Y Return temperature
A Heating curve-end point
B Return limit (in the example shown: 40°C)
Hysteresis HR
setting for the control hysteresis of the
heating regulator
Set a greater hysteresis for very reactive
heating systems, and a lower hysteresis
for less reactive heating systems.
Example: Hysteresis heating circle
return = 2K

19
We reserve the right to make technical changes | 83055400dUK – Translation of the original instruction manual (2.1) | ait-deutschland GmbH
T-HG max
maximum hot gas temperature
Setting for the maximum permissible temperature in the
cooling circle of the heat pump.
T-def.airend
Temperature air defrost end
A value is only displayed for L/W devices and if the air defrost
is switched on.
Setting for the temperature at which the air defrosting is
terminated at the outlet of the evaporator.
pagpage 38, “Overview: Defrost cycle, Air defrost,
Flow Max“
Lowering to
Maximum lowering
Setting for the external temperature up to which a night
lowering is carried out.
If the actual external temperature falls below the set value,
the lowering temperature is ignored.
Minimum return set-point temperature
Minimum return set-point temperature, will not be exceeded
in operation.
Minimum MK1 ow
Minimum ow temperature, will not be exceeded in
operation.
Flow Max.)
Maximum ow temperature
If this temperature is exceeded in the ow, a compressor of
the heat pump is switched o. This applies to all supply types!
page 38
Flow max. MK1
Maximum ow temperature following
the charger mixer
Is only displayed if mixing circle 1 is set to charger mixer.
The forward ow sensor at TB1 will then be used to limit the
ow temperature following the mixer. This means: if the TB1
exceeds the value set here, the charger mixer will be moved
in >Closed< direction.
min. AT Flow max.)
Heat source temperature-dependent
adjustment of the ow temperature.
Heat source temperature-dependent adjustment of the ow
temperature.
The outside temperature, up to which the ow max.
temperature with the heat pump may be increased, is
adjusted here.
Below this outside temperature, the actual VL maximum
temperature of the heat pump will fall linearally to the value
“Forward ow EG“.
Flow limit of applic. )
Heat source temperature-
dependent adjustment of the ow
temperature.
Here, the maximum forward ow temperature of the heat
pump is set at an outside temperature of -20°C.
For further details, see point “min. AT VL max.” and the
following diagrams:
In the event of a fault and the setting fault with a 2 hg, the
second heat generators are released independently of the set
external temperature.
Tp-defr.Air.
Temperature air defrost
A value is only displayed for L/W devices and if the air defrost
is switched on.
Setting for the release temperature for the air defrost. Below
the set temperature, the air defrosting is locked.
ATTENTION
Set air defrost only if device type is approved for air de-
frost.
TDI-Solltemp.
TDI setpoint temperature
Setting for the setpoint temperature for the thermal
disinfection in the domestic hot water preparation.
Hysterese.DHW
Hysteresis of domestic hot water
Setting for the control hysteresis for the domestic hot water
preparation (negative hysteresis).
A There will be no request for domestic hot water
preparation in this temperature range
B There will be a request for domestic hot water
preparation in this temperature range
C Domestic hot water target
D negative hysteresis
Flow 2. CP DHW
Flow 2nd compressor
Domestic hot water
Is only displayed for devices with 2 compressors.
Setting for the ow temperature from which domestic hot
water is prepared with a compressor.
Optimisation of the charging time and the attainable
domestic hot water temperatures..
T-outd. max
maximum external temperature
A value is only displayed for L/W devices
Setting for the maximum external temperature from which
the heat pump is locked.
Second heat generators are released as required..
T-outd. min
minimum external temperature
A value is only displayed for L/W devices.
Setting for the minimum external temperature under which
the heat pump is locked.
Second heat generators are released as required..
T-HS min Minimum heat source temperature
A value is only displayed for S/W- or W/W devices.
Setting for the minimum permissible temperature at the heat
source outow of the heat pump..
for S/W devices:
With AS access, a value above -9 °C can be set
(necessary for integration with intermediate
exchangers) for S/W devices
for W/W devices
The setting is only available with manufacturer
access..

20
We reserve the right to make technical changes | 83055400dUK – Translation of the original instruction manual (2.1) | ait-deutschland GmbH
DETERMINING SYSTEM SETTING
The menu is not shown in full here. Further menu items
appear if you scroll down the screen.
Activate and select the required parameters, make the re-
quired setting and conrm by pressing the “turn-push
button“.
Scroll all the way down, cancel or save the settings.
ATTENTION
Incorrect settings not oriented towards the system compo-
nents put the safety and functional capability of the sys-
tem at risk and can lead to damage.
NOTICE
Enter deviations from the relevant factory settings in the
overview “System setting for the commissioning”.
pagpage 39, “System setting during commissioning“
El. sup. blockade
Electrical supply o-times
no 2hg 2hg at electrical supply o-time also
locked
with 2hg 2hg released for electrical supply
Setting only takes eect as 2 hg for boiler or thermal.
Rooms tat.
Raumstation (Raumfernversteller)
No No room remote adjuster connected
RFV Room remote adjuster connected
RBE Room control unit connected
Integration
Hydraulic Integration
Setting the hydraulic integration of the buer tank
Return (Return) hydraulic integration with row tank
(ow/return)
Sep. tank (separating tank)hydraulic integration with parallel tank
(multifunction tank,.)
VL
AT
-20°C min. AT Flow max.
Flow max.
Limitation
of use
VL = Forward ow
AT = outside temperature
Hysteresis 2.CP short
Hysteresis heating control
Shorten HR hysteresis. HR. Hysteresis heating regulator
from which the cut-in time of the 2nd. compressor stage is
shortened (See “System setting”).
Cutting-in compressor 2:
A No cut-in
B Shortened cut-in
C Return ow set value
D Heat regulator hysteresis
E Hysteresis HR shortened
Max. DHW temp.
Maximum Hot Water temperature
A value, which is set to limit the maximum set temperature of
the hot water.
Min. ow cooling
Minimum CoolingFlow temperature
If the temperature at the cooling sensor falls below this
temperature (depending on integration TB1, TB2 or TRL), the
cooling is interrupted (factory setting 18 °C). At the same time,
the displayed value is the minimum value for settable cooling
setpoint temperatures.
Scroll all the way down,
cancel or save the settings.
DETERMINING PRIORITIES
Part 1 of the controller manual, program area “Service“,
section “Determining priorities“.
Other manuals for Luxtronik
5
Table of contents
Other alphainnoTec Controllers manuals