Alstom GEM80 User manual

GEM80 Fieldbus Modules
Technical Manual
Publication No. T2035EN
Issue 002 (07/05)
ABCD

GEM80 1. Introduction
Issue 002 (07/05) Fieldbus Technical Manual T2035 Page 1
1. Introduction........................................................................................................... 2
1.1 Preface ........................................................................................................................... 2
1.2 Introduction to Fieldbus ................................................................................................. 2
2. Common Technical Specification ........................................................................... 3
2.1 Electrical ........................................................................................................................ 3
2.2 Physical .......................................................................................................................... 3
2.3 Environmental................................................................................................................3
2.4 Standards....................................................................................................................... 3
3. Hardware Layout................................................................................................... 4
4. Installation ............................................................................................................ 5
4.1 Introduction ................................................................................................................... 5
4.2 Module Installation ........................................................................................................ 5
4.3 Module Identification ..................................................................................................... 6
5. Operation.............................................................................................................. 7
5.1 Introduction ................................................................................................................... 7
5.2 Module Configuration Parameters ................................................................................. 7
5.2.1 Validity Flag (Pn and Pn+12) ......................................................................................... 9
5.2.2 Device Type (Pn+1 to Pn+2 and Pn+17 to Pn+18) ......................................................10
5.2.3 Scan Rate (Pn+3 and Pn+19)....................................................................................... 10
5.2.4 Input Buffer (Pn+4 to Pn+6 and Pn+20 to Pn+22) ......................................................10
5.2.5 Output Buffer (Pn+7 to Pn+9 and Pn+23 to Pn+25).................................................... 10
5.2.6 Version Buffer (Pn+10 to Pn+12 and Pn+26 to Pn+28)............................................... 10
5.2.7 Reserved Parameters.................................................................................................... 10
5.3 System Configuration................................................................................................... 11
6. Maintenance and Fault Finding ........................................................................... 12
6.1 Fixed F-Table ............................................................................................................... 12
6.1.1 Error Code ................................................................................................................... 12
6.1.2 Exchange Mode............................................................................................................ 13
6.1.3 Exchange Counter........................................................................................................ 14
6.1.4 Presence Indication ...................................................................................................... 14
6.2 Version Buffer .............................................................................................................. 15
6.3 Fixed V-Table ............................................................................................................... 15
7. Hilscher System software (SyCon)........................................................................ 16
7.1 Preface ......................................................................................................................... 16
7.2 Introduction to the Hilscher System software................................................................ 16
7.3 Installation of the Hilscher System software ................................................................. 16
7.4 Hilscher Profibus System software (SyCon) Operation Guide .......................................18
7.4.1 Start to build a representation of your Fieldbus system................................................ 19
7.4.2 Inserting Slaves............................................................................................................ 22
7.5 Download Configuration.............................................................................................. 25
7.5.1 Common Error Message during Download – 170 – GEM80 RUNNING ........................ 27
7.6 Importing Slave Configuration Files (.GSD).................................................................. 28
8. Spares, Service and Support....................................................................................

GEM80 1. Introduction
Issue 002 (07/05) Fieldbus Technical Manual T2035 Page 2
1. Introduction
1.1 Preface
This manual provides the information necessary to configure and install various
Fieldbus modules into GEM80 Controllers. The manual covers the modules’ technical
and physical specifications, installation, operation and general use. Examples and
application notes are also included.
1.2 Introduction to Fieldbus
Fieldbus is a generic term for communication between a GEM80 Controller and plant
input and output. The currently supported protocols are Profibus FMS/DP, CANopen
and DeviceNET. Master functionality is supported in each case.
The Fieldbus plug-in modules are peripherals of the GEMLAN-T compatible processor
module. Up to two modules in any combination are supported per controller. A power
converter module must also be fitted; this can power up to two Fieldbus modules
simultaneously.
Each Fieldbus module has a front panel to permit connection to the Fieldbus network
and to a diagnostic serial link. Ribbon cables connect the module and the panel. The
panel also has LED indicators, which mimic the Fieldbus module’s on-board indicators.
The GEM80-500 can support up to 5 plug-in modules; each Fieldbus module fitted
consumes one from this allowance.

GEM80 2. Common Technical Specification
Issue 002 (07/05) Fieldbus Technical Manual T2035 Page 3
2. Common Technical Specification
2.1 Electrical
Power Consumption 650mA from host GEM80 +5v
LED Indication Green LED - Run
Yellow LED - Ready / Communication
Red LED - Error
2.2 Physical
Dimensions 90 x 96 x 23 (L x W x H)
2.3 Environmental
Operating
Temperature 0 to +55 deg. C
2.4 Standards
Noise Immunity EN50082 - 2

GEM80 3. Hardware Layout
Issue 002 (07/05) Fieldbus Technical Manual T2035 Page 4
3. Hardware Layout
Fieldbus Front panel and Module (Profibus shown)
Power Converte
r
Fieldbus front panel
Module
Identification
Rotary Switch
Section 4.3

GEM80 4. Installation
Issue 002 (07/05) Fieldbus Technical Manual T2035 Page 5
4. Installation
4.1 Introduction
The Fieldbus Modules contain electrostatic sensitive devices. Handling precautions must
be observed.
If it is necessary, in the case of repair, to return any PCBs, they must be enclosed in a
static shielding bag, e.g. 3M Type 2100, be suitably protected by foam plastic
wrapping, and packed in a box labelled 'Caution Static Sensitive PCBs
CAUTION
This equipment contains solid state devices, which may be affected by
electrostatic discharge. Observe static handling precautions.
4.2 Module Installation
The Fieldbus Modules are peripherals of the TCP/IP Ethernet module (9716-4020).
Prior to the installation of any Fieldbus modules, ensure that a TCP/IP Ethernet module
is correctly installed and configured. Refer to the GEM80-500 Series Controller
Technical Manual for installation instructions and the GEMLAN-T Technical Manual for
configuration instructions for the TCP/IP Ethernet module.
Before installation, the Fieldbus module must be hardware configured by setting the
Module Identification rotary switch. Refer to section 4.3.
With the controller powered down remove the front panel mains and watchdog
connector. Move the controller to a suitable location and proceed as follows, noting
that all references to left and right refer to the controller when viewed from the front.
(a) Release the upper right-hand side cover and power supply assembly. Lay the
controller down on its left-hand side and remove the four M3 Pozi-pan head
earthing/grounding screws. Retain for re-assembly.
(b) Lift the cover and slide the louvered side under the controller.
(c) The TCP/IP Ethernet module should now be visible. This is retained using four M3 x
6 mm screws and spring washers. Remove these screws and washers and retain for
re-assembly.
(d) Secure the TCP/IP Ethernet module in position by substituting 4 mounting pillars for
the M3 x 6mm screws.
(e) The site is now ready to receive a Fieldbus module.
(f) Check that the connector pins on the underside of the Fieldbus module are correctly
aligned. Orientate the module so that the matching connectors are in line. Gently
push the connector halves together until the module sits flat on the mounting
pillars.
(g) Insert the front panel mounted Fieldbus and diagnostic ribbon cables to their
associated headers.
(h) Secure the Fieldbus module in position using 4 more mounting pillars.
(i) If all required Fieldbus modules are now fitted proceed at instruction (j), otherwise
continue at instruction (e).
(j) The site is now ready to receive the power converter module.

GEM80 4. Installation
Issue 002 (07/05) Fieldbus Technical Manual T2035 Page 6
(k) Check that the connector pins on the underside of the power converter module are
correctly aligned. Orientate the module so that the matching connectors are in line
and the mounting holes correspond with the two mounting pillars nearest to the
front of the controller. Gently push the connector halves together until the module
sits flat on the mounting pillars.
(l) Secure the power converter module in position with 2 of the screws and washers
removed at instruction (c). The unused screws and washers may be stored in the
other two mounting pillars.
(m) Remove a blanking panel from the front of the controller, to make space for each
of the Fieldbus module front panels. The blanking panels are secured with two M3
Pozi-pan screws, remove and retain the screws.
(n) Secure the Fieldbus front panel(s) in position using the screws removed at
instruction (m).
(o) Replace the upper right-hand side cover and power supply assembly. Secure in
position using the screws removed at instruction (a).
WARNING
Insertion or removal of modules with the equipment
energised will cause malfunction of the equipment.
4.3 Module Identification
A rotary switch located on the fieldbus module PCB achieves module identification. A
maximum of two fieldbus modules can be installed into a GEM80-500, each identified
in the system by reserved rotary switch position 2 or 3.
The GEM80-500 Fieldbus driver will find the module with the lowest switch position
and use the configuration parameters from Pn to configure this module, this is referred
to as Module #1. The next module if fitted will use parameters from Pn+16, this
referred to as Module #2 (see section 5.2).
If a single Fieldbus module is fitted, the rotary switch must be set to position 2 (Module
#1). If two modules are fitted, one rotary switch must be set to positions 2 (Module
#1) and the other to position 3 (Module #2).
If a module is removed, ensure that the remaining module’s rotary switch is set to
position 2 and that the configuration data starting at Pn are suitable for the application.
N.B. If two modules are fitted, setting the rotary switch to the same position will cause
malfunction of both modules. Selecting any position other than 2 or 3 will cause
malfunction of the host processor.

GEM80 5. Operation
Issue 002 (07/05) Fieldbus Technical Manual T2035 Page 7
5. Operation
5.1 Introduction
CAUTION
The inclusion and configuration of one or more FIELDBUS modules grants read
and write access to GEM80 data tables. It is the user’s responsibility to ensure
that adequate safeguards are used to prevent dangerous situations arising.
5.2 Module Configuration Parameters
An Advanced GEM80 Programmer (or equivalent) must be used to supply the module
configuration parameters. These parameters must be entered into the P-table of the
host GEM80 Controller by the user before the module can be used. The GEMLAN-T
Module accesses these parameters on behalf of the Fieldbus module(s) after
completion of its boot procedure. The GEMLAN-T Module takes approximately one
minute to complete its boot procedure.
Note:
If the parameters are subsequently altered, they will be recognised and
validated by the GEMLAN-T Module following a recompilation. During
the validation, Fieldbus communication is halted. If the validation
should fail, the communication remains halted.
Remember that P-table entries above P149 will only exist if specifically
declared in the user program.
For the GEMLAN-T module to access the configuration data successfully, a value must
be written into P74. This value acts as a pointer to the P-table location containing the
configuration parameters for Fieldbus module #1. Fieldbus module #2 parameters
follow those of module #1 in the P-table.
E.G. if P74 contains a value of 300, the configuration parameters start at P300.
Inserting a value of 0 into P74 renders inactive all Fieldbus modules of the host
controller.
A detailed description of each configuration parameter is provided in the following
paragraphs. Table 5-1 provides a reference table. Table 5-2 is an example of the use
of the P-tables.

GEM80 5. Operation
Issue 002 (07/05) Fieldbus Technical Manual T2035 Page 8
Table 5-1 P Table Configuration Parameters
Table Function Comment
P74 Pointer to configuration data. e.g. 300 = parameters start at P300
MODULE #1 parameters
Pn Validity flag @4801 ( Must be this value )
Pn+1 Device type (HIGH)
Pn+2 Device type (LOW)
Safety Check
Pn+3 Scan Rate Rate in ms, 0 = free running
Pn+4 Input table letter In LS byte, MS byte =0.
Pn+5 Input table offset
Pn+6 Input table quantity
Pn+7 Output table letter In LS byte, MS byte =0.
Pn+8 Output table offset
Pn+9 Output table quantity
Pn+10 Version table letter In LS byte, MS byte =0.
Pn+11 Version table offset
Pn+12 Version table quantity
Pn+13 Reserved (Must be 0)
Pn+14 Reserved (Must be 0)
Pn+15 Reserved (Must be 0)
MODULE #2 parameters
Pn+16 Validity flag @4802 ( Must be this value )
Pn+17 Device type (HIGH)
Pn+18 Device type (LOW)
Safety Check
Pn+19 Scan Rate Rate in ms, 0 = free running
Pn+20 Input table letter In LS byte, MS byte =0.
Pn+21 Input table offset
Pn+22 Input table quantity
Pn+23 Output table letter In LS byte, MS byte =0.
Pn+24 Output table offset
Pn+25 Output table quantity
Pn+26 Version table letter In LS byte, MS byte =0.
Pn+27 Version table offset
Pn+28 Version table quantity
Pn+29 Reserved (Must be 0)
Pn+30 Reserved (Must be 0)
Pn+31 Reserved (Must be 0)

GEM80 5. Operation
Issue 002 (07/05) Fieldbus Technical Manual T2035 Page 9
Table 5-2 P-Table Example
P74 300 Pointer to P300
P300 @4801 Module #1
P301 @7910
P302 @9040
Profibus Master
P303 100 100 ms scan
P304 @0047
P305 1000
P306 100
P307 @0048
P308 2000
P309 50
P310 @0046
P311 500
P312 25
P313 0
P314 0
P315 0
G Table
G1000
Length 100 entries, 200 bytes.
H table
H2000
Length 50 entries, 100 bytes
F Table
F500
Length 25 entries, 50 bytes.
P316 @4802 Module #2
P317 @7910
P318 @9051
DeviceNet Master
P319 0Free running
P320 @0047
P321 1100
P322 50
P323 @0048
P324 2050
P325 100
P326 @0046
P327 F525
P328 25
P329 0
P330 0
P331 0
G Table
G1100
Length 50 entries, 100 bytes.
H table
H2050
Length 100 entries, 200 bytes
F Table
F525
Length 25 entries, 50 bytes
@ Denotes a Hexadecimal Value, .i.e. all other values are decimal
5.2.1 Validity Flag (Pn and Pn+12)
The first P-table entry of each module’s configuration data contains a validity flag. Its
function is to prevent an uninitialised ‘P’-table from being used as configuration
parameters. The user must insert the hexadecimal value @4801 (module #1) or
@4802 (module #2) into the relevant table entry to signify that the module
configuration data is valid.
The insertion of any other value into the table entry renders inactive the associated
Fieldbus module.

GEM80 5. Operation
Issue 002 (07/05) Fieldbus Technical Manual T2035 Page 10
5.2.2 Device Type (Pn+1 to Pn+2 and Pn+17 to Pn+18)
These parameters are used to check that the number of modules fitted and their types
correspond to that expected by the user. It is recommended to program an F1 trip
should this safety check fail. Refer to section 6.1.1
Protocol Board Ref. Device
Type
(HIGH)
Device
Type
(LOW)
Profibus Master CIF104P-PB\V @7910 @9040
DeciveNet Master CIF104P-DNM\V @7910 @9051
CANopen Master CIF104P-COM\V @7910 @9050
Profibus Slave
DeciveNet Slave
CANopen Slave
5.2.3 Scan Rate (Pn+3 and Pn+19)
This parameter is used to control the repetition rate of transfers (both input and output)
between the GEM80 tables and the respective Fieldbus module. Scan rates for each
module may be set independently. The value entered represents a rate in milliseconds,
but the rate will limit to 2000 milliseconds. A value of 0 selects free running and a
transfer will occur between each scan of the ladder program.
5.2.4 Input Buffer (Pn+4 to Pn+6 and Pn+20 to Pn+22)
These 3 entries, table letter, offset and quantity together define a buffer for the receipt
of plant data. The table must exist, have write access and have sufficient entries to cater
for the quantity requested. If the buffer does not exist, then the configuration fails.
5.2.5 Output Buffer (Pn+7 to Pn+9 and Pn+23 to Pn+25)
These 3 entries, table letter, offset and quantity together define a buffer for the source
of plant data. The table must exist, have read access and have sufficient entries to cater
for the quantity requested. If the buffer does not exist, then the configuration fails.
5.2.6 Version Buffer (Pn+10 to Pn+12 and Pn+26 to Pn+28)
These 3 entries, table letter, offset and quantity together define a buffer for the receipt
of module version information. If the table letter contains 0, it is assumed that the user
does not wish to read this information, in which case the offset and quantity are
ignored. If the table letter contains any other value, the table must exist, have write
access and have sufficient entries to cater for the quantity requested.
5.2.7 Reserved Parameters
All parameters marked as reserved are for future expansion and must contain the value
0.

GEM80 5. Operation
Issue 002 (07/05) Fieldbus Technical Manual T2035 Page 11
5.3 System Configuration
Having correctly installed and configured the Fieldbus modules it is then possible to
configure the Fieldbus system using the Hilscher SyCon tool. A detailed description of
the use of this tool is beyond the scope of this manual, although an operation guide is
included in section 7. For full instructions refer to the Hilscher documentation provided
on the CD.
This Windows based tool can communicate with the Fieldbus module using a serial link
or over an Ethernet network using TCP/IP. We recommend that you use TCP/IP and the
guide in section 7 follows this route.
The serial link method bypasses the GEM80-500 completely by communicating
directly with the Fieldbus module. This method is suitable for monitoring the network
operation but should not be used for system configuration downloading. As it
communicates directly, new system configurations will be downloaded whether or not
the host GEM80 controller is in a running or halted state.
The TCP/IP method connects directly to the GEM80 TCP/IP Ethernet module. As a
result the GEM80 Ethernet module is able to examine the commands sent from the
SyCon tool before passing them to the associated Fieldbus module. The running state
of the host GEM80 is also examined by the Ethernet module, attempts to modify
important system parameters will be refused if the host GEM is in the running state.
This results in an error code of 170 at the SyCon tool. The TCP/IP method is also
suitable for monitoring the network operation.
See section 7 for further information on the operation of the SyCon tool.

GEM80 6. Maintenance and Fault Finding
Issue 002 (07/05) Fieldbus Technical Manual T2035 Page 12
6. Maintenance and Fault Finding
6.1 Fixed F-Table
This section contains general guidance for the maintenance of a controller containing
Fieldbus modules.
Each module is allocated 14 fixed F-Tables, used to report errors and statistical
information.
F-Table
Module 1
F-Table
Module 2
Description Notes
F372 F386 Error Code
F373 F387 Pointer 1
F374 F388 Pointer 2
See section 6.1.1
F375 F389 Exchange Mode See section 6.1.2
F376 F390 Exchange Counter (LS word)
F377 F391 Exchange Counter (MS word)
See section 6.1.3
F378 F392
F379 F393
F380 F394
F381 F395
F382 F396
F383 F397
F384 F398
F385 F399
Presence Indication See section 6.1.4
6.1.1 Error Code
The Error Code field and the associated pointers are used to identify problems with the
configuration data or failure of the associated Fieldbus module. On power-up these
fields are cleared. On recompilation, syntax checking is performed on the configuration
and problems are reported as follows.
Error Code
Value States
On
Fault/Warning Condition Comment
52 & 0 Fault Table
Fault
The parameter indicated by
Pointer 1 is a disallowed table.
OR
The parameters indicated by
Pointers 1 & 2 would cross the
table boundary.
Modify user program.
93 & 0 Fault Parameter
Fault
The parameter indicated by
Pointer 1 is out of range.
Modify user program.
17 4 & 0 Fault Module No module of the selected type is

GEM80 6. Maintenance and Fault Finding
Issue 002 (07/05) Fieldbus Technical Manual T2035 Page 13
Fault fitted or the module has failed.
Check Pn+1 or Pn+17 or replace
the module.
34 5 & 1 Warning Input
Truncation
The parameters indicated by
Pointers 1 & 2 produce a buffer
which is too small to receive the
configured Fieldbus data.
Check the Fieldbus requirements
and extend the buffer.
66 6 & 1 Warning Output
Truncation
The parameters indicated by
Pointers 1 & 2 produce a buffer
which is too small for the source
of the configured Fieldbus data.
Check the Fieldbus requirements
and extend the buffer.
-32767 15 & 0 Fault Watchdog
Timeout
Scan rate is too slow or the
watchdog time is too fast or the
module has failed.
Check Pn+3 or Pn+19 against
the SyCon watchdog time,
reconfigure and power-cycle the
GEM80 or replace the faulty
Fieldbus module
The following rungs of ladder program will cause a user requested F1 trip if any
configured module should fail. An F1 trip will also be produced if the module type does
not match with the safety values entered in the configuration data.
---] [------------------------------------( )---
F372.4 F1.0
---] [------------------------------------( )---
F386.4 F1.1
6.1.2 Exchange Mode
The Exchange Mode LS byte contains the communications state indicator in bit 0. This is
set to 1 if the Fieldbus is performing transfers; otherwise it is cleared to 0. The
remainder of the byte is reserved and is cleared to 0.
The Exchange Mode MS byte contains the process data handshake mode as configured
by SyCon.
•Value = 1. Bus synchronous, device controlled.
•Value = 2. Buffered, device controlled.
•Value = 3. Non-consistent, uncontrolled.
•Value = 4. Buffered, host controlled (recommended).
•Value = 5. Bus synchronous, host controlled.
The recommended setting is buffered host controlled. This will have the least impact on
the controller’s scan rate.

GEM80 6. Maintenance and Fault Finding
Issue 002 (07/05) Fieldbus Technical Manual T2035 Page 14
All device controlled or uncontrolled settings should be avoided as the Fieldbus
communication will start as soon as power is applied, without waiting for the Ethernet
module (9716-4020) to initialise. The Fieldbus slaves will therefore not be under the
control of the GEM80.
6.1.3 Exchange Counter
This unsigned 32-bit variable contains the count of transfers between the GEM80 and
the Fieldbus module.
6.1.4 Presence Indication
The Fieldbus module maintains a bit array of the active devices detected on the
communications link. It is recommended that the application monitors this bit array and
takes appropriate action on loss of I/O. Word 0 bit 0 represents the master itself and
will always contain 0. Word 0 Bit 1represents the device with address 1 etc.
Presence Words 4 to 7 are not required when using DeviceNET and should be ignored.
Module 1 Module 2 Description
F378 F392 Presence Word 0 (Addresses 0 to 15)
F379 F393 Presence Word 1 (Addresses 16 to 31)
F380 F394 Presence Word 2 (Addresses 32 to 47)
F381 F395 Presence Word 3 (Addresses 48 to 63)
F382 F396 Presence Word 4 (Addresses 64 to 79)
F383 F397 Presence Word 5 (Addresses 80 to 95)
F384 F398 Presence Word 6 (Addresses 96 to 111)
F385 F399 Presence Word 7 (Addresses 112 to 127)

GEM80 6. Maintenance and Fault Finding
Issue 002 (07/05) Fieldbus Technical Manual T2035 Page 15
6.2 Version Buffer
The version buffer is optional; it is disabled by clearing Pn+10 for module 1 or Pn+26
for module 2. When configured, information about the associated module’s hardware
and software is copied to the buffer. The copy occurs once when the controller is
powered-up and again on recompilation of the controller. If insufficient entries are
allocated by the user the report will truncate.
Note. The information presented will be required when contacting the ALSTOM
customer support department.
Table (BYTE)
Offset
Content Format Example Interpretation
0@0501
2
Manufacture
Date
BCD
@0320
01/05/2003
4@7910
6
Device
Type
BCD
@9040
10794090
8@0000
10
Serial
Number
BCD
@2200
00000022
12 Memory size BYTE @08 8Kbytes
13 Type BYTE @03 Type 3
14 Model ASCII @31 Model ‘1’
15 @43
16 @49
17
Identification ASCII
@46
‘CIF’
18 @4250
20 @432D
22 @404F
24 @4942
26 @3143
28 @3430
30 @2D50
32
Firmware
Name
ASCII
@4250
‘PB-COMBIC104P-PB’
34 @3056
36 @2E31
38 @3730
40 @2030
42 @3931
44 @312E
46 @2E30
48
Firmware
Version
ASCII
@3230
‘V01.070’ ’19.10.02’
6.3 Fixed V-Table
The GEM80-500 controller has five V-Table entries (V67 to V71 inclusive) reserved for
plug-in module identifiers. The Fieldbus modules will also present their identifiers in
these table entries. The values presented are the lower half of the device type as read
from the Fieldbus module. These values follow on from the modules fitted directly to the
base board. These table entries are reported in the order that they are found by the
driver.

GEM80 7. Hilscher System software (SyCon)
Issue 002 (07/05) Fieldbus Technical Manual T2035 Page 16
7. Hilscher System software (SyCon)
7.1 Preface
This section provides a guide to the use of the Hilscher System Software supplied with
the various Fieldbus modules that can be installed in the GEM80-500 Controller.
It illustrates the configuration and down load of a PROFIBUS configuration to a
GEM80-500 PROFIBUS MASTER (Part Number 9723-4020) using the supplied Hilscher
System software.
For other Fieldbus modules the steps taken will be similar, but the selected module and
slave specific data will change.
Detailed information on the operation of this software can be found in the Hilscher
documentation provided on the CD.
7.2 Introduction to the Hilscher System software.
The Hilscher System software is supplied unlicensed and as such can only be used
to generate a configuration with one slave.
It can be used however, to download multi-slave configurations that have already been
created on a licensed copy.
Once installed you can license your copy at any time by selecting HELP / LICENSING,
filling in your details and printing the order form. A charge will apply.
7.3 Installation of the Hilscher System software
To install the Hilscher System software insert the installation CD into the appropriate
drive of the computer, the installation should auto run.
Should it fail to auto run, use Windows Explorer to select the installation program
“autorun.exe”. This will start the installation process and prompt you as to what actions
to take in order to install the required software and drivers.
The installation process will prompt you to select the component you require.

GEM80 7. Hilscher System software (SyCon)
Issue 002 (07/05) Fieldbus Technical Manual T2035 Page 17
You will be presented with the following window.
Select the options shown above, then NEXT to continue.
You will be presented with the Welcome to Configuration window, proceed with
NEXT.
Select Components to load window
You require the CIF Device Driver and your selected Fieldbus. All other options can be
de-selected to save disk space if required. For this example we have selected
PROFIBUS.
Select the required options then NEXT to continue.
Select an appropriate program folder location, NEXT to continue.
At this point installation will commence for the items you selected. You will be prompted
before each selection is installed.

GEM80 7. Hilscher System software (SyCon)
Issue 002 (07/05) Fieldbus Technical Manual T2035 Page 18
7.4 Hilscher Profibus System software (SyCon) Operation Guide
To run the utility select SyCon from program files
This will launch the SyCon.EXE Main Window (Network View) shown below.
From this window select – FILE then NEW

GEM80 7. Hilscher System software (SyCon)
Issue 002 (07/05) Fieldbus Technical Manual T2035 Page 19
This creates a blank configuration file, a container to hold the representation of your
Fieldbus system.
7.4.1 Start to build a representation of your Fieldbus system.
Start by inserting the Fieldbus master module. This represents the module installed in
GEM80-500.
To do so select - INSERT then MASTER
Position the master module at top of the line representing the network cable, the area
above enclosed by the rectangle, right click to drop.
Next select the required master module.
Table of contents