Ambirad SmartCom3 User manual


1 Single Zone System.
SmartCom Mulitizone
NEUT
LIVE 1/L 2/N 10 S/R0S/R1D0 D1 O0 O1 B1 B0 B2 C2 C0 C1 66 64 20
41 40 7 8 9 25 14 5 6
Exhaust
Fan
L2
L1 (HOT)
GND
Drawing No. : 900289 R6 USA
NOTES:
REMOTE SWITCH INPUTS
should be connected by 18 Awg
cable. Max length is 325ft.
Low voltage switching inputs to
be normally open (closed circuit
to enable).
Connect to B0 & B1 for remote
ON (ie BMS time control).
REMOTE SENSOR(s) may be
placed at a max distance of 325ft
from the control unit, using
shielded 18 Awg cable.
Wiring should be kept separate
from mains wiring to minimize
noise pick up. Set within
Engineers functions for any
remote sensors.
Burner
one
Burner
two
L2
L1 (HOT)
GND
20 amp Supply
120V 60Hz 1 Ph
C
40VA
Trans
Relay
S-0700
L1
G
R
Relay
S-0755
Black Bulb
Sensor
Outside
Sensor
(where applicable)
(COMMON)
eg E.M.S.
(REMOTE ON)
(REMOTE OFF)
L2
(n.c.)

2 Split Zone System.
SmartCom Mulitizone
NEUT
LIVE
(COMMON)
eg
E.M.S.
(REMOTE ON)
(REMOTE OFF)
1/L 2/N 10 S/R0S/R1D0 D1 O0 O1 B1 B0 B2 C2 C0 C1 66 64 20
41 40 7 8 9 25 14 5 6
To other slave
controllers
SmartCom Mulitizone
NEUT
LIVE
(COMMON)
(REMOTE ON)
(REMOTE OFF)
1/L 2/N 10 S/R0S/R1D0 D1 O0 O1 B1 B0 B2 C2 C0 C1 66 64 20
41 40 7 8 9 25 14 5 6
To other slave
controllers
eg E.M.S.
(Slave 1)
(Master)
Drawing No. :
900290 R6 USA
NOTES:
NETWORK. Master-slave (Network)
communication is by shielded
twisted pair cable, RS485
compatible such as Belden 9841.
Maximum overall system length of
1650ft Connect screen to C0.
NOTE: Diagram shows a master
and ONE slave configuration**.
Wire further slaves in parallel.
REMOTE SWITCH INPUTS should
be connected by 18 Awg cable.
Max length is 325ft.
Low voltage switching inputs to be
normally open (closed circuit to
enable).
Connect to B0 & B1 for remote ON
(ie BMS time control).
REMOTE SENSOR(s) may be
placed at a max distance of 325ft
from the control unit, using shielded
18 Awg cable.
Wiring should be kept separate
from mains wiring to minimize noise
pick up. Set within Engineers
functions for all remote sensors.
Burners
Zone A
Burners
Zone B
20 amp Supply
120V 60Hz 1 Ph
C
Relay
S-0755 W1
S-0700
Exhaust
Fan
L2
L1 (HOT)
GND
Black Bulb
Sensor
Black Bulb
Sensor
Outside
Sensor
(where applicable)
Black Bulb
Sensor
L2
L1 (HOT)
GND 15 amp Supply
120V 60Hz 1 Ph
C
40VA
Trans
Relay
S-0700
L1
G
R
L2
C
40VA
Trans
Relay
L1
G
R
L2
L2
L1 (HOT)
GND
(n.c.)

3 Multizone System.
SmartCom Mulitizone
NEUT
LIVE
(COMMON)
(REMOTE ON)
(REMOTE OFF)
1/L 2/N 10 S/R0S/R1D0 D1 O0 O1 B1 B0 B2 C2 C0 C1 66 64 20
41407 8 925 145 6
To other slave
controllers
To other slave
controllers
(Master)
Drawing No. :
900454 R1 USA
NOTES:
NETWORK. Master-slave (Network)
communication is by shielded
twisted pair cable, RS485
compatible such as Belden 9841.
Maximum overall system length of
1650ft Connect screen to C0.
NOTE: Diagram shows a master
and ONE slave configuration**.
Wire further slaves in parallel.
REMOTE SWITCH INPUTS should
be connected by 18 Awg cable.
Max length is 325ft.
Low voltage switching inputs to be
normally open (closed circuit to
enable).
Connect to B0 & B1 for remote ON
(ie BMS time control).
REMOTE SENSOR(s) may be
placed at a max distance of 325ft
from the control unit, using shielded
18 Awg cable.
Wiring should be kept separate
from mains wiring to minimize noise
pick up. Set within Engineers
functions for any remote sensors.
Burners
Zone A
Exhaust
Fan
SmartCom Mulitizone
NEUT
LIVE
(COMMON)
(REMOTE ON)
(REMOTE OFF)
1/L 2/N 10 S/R0S/R1D0 D1 O0 O1 B1 B0 B2 C2 C0 C1 66 64 20
41407 8 925 145 6
Exhaust
Fan
(Slave 1)
Burners
Zone B
eg
E.M.S.
Black Bulb
Sensor
Black Bulb
Sensor
Outside
Sensor
(where applicable)
eg
E.M.S.
Black Bulb
Sensor
Black Bulb
Sensor
Outside
Sensor
(where applicable)
20 amp Supply
120V 60Hz 1 Ph
C
Relay
W1
S-0700
C
40VA
Trans
Relay
L1
G
R
L2
L2
L1 (HOT)
GND
L2
L1 (HOT)
GND
20 amp Supply
120V 60Hz 1 Ph
C
Relay
W1
S-0700
C
40VA
Trans
Relay
L1
G
R
L2
L2
L1 (HOT)
GND
L2
L1 (HOT)
GND
(n.c.)

4 Single Zone System c/w Motorised Damper.
Drawing No. : 900289R6 D USA
NOTES:
REMOTE SWITCH INPUTS
should be connected by 18 Awg
cable. Max length is 325ft.
Low voltage switching inputs to
be normally open (closed circuit
to enable).
Connect to B0 & B1 for remote
ON (ie BMS time control).
REMOTE SENSOR(s) may be
placed at a max distance of 325ft
from the control unit, using
shielded 18 Awg cable.
Wiring should be kept separate
from mains wiring to minimize
noise pick up. Set within
Engineers functions for any
remote sensors.
SmartCom Mulitizone
NEUT
LIVE 1/L 2/N 10 S/R0S/R1D0 D1 O0 O1 B1 B0 B2 C2 C0 C1 66 64 20
41 40 7 8 9 25 14 5 6
L2
L1 (HOT)
GND
Burner
one
Burner
two
L2
L1 (HOT)
GND
20 amp Supply
120V 60Hz 1 Ph
C
40VA
Trans
Relay
S-0700
L1
G
R
Relay
S-0755
Black Bulb
Sensor
Outside
Sensor
(where applicable)
(COMMON)
eg E.M.S.
(REMOTE ON)
(REMOTE OFF)
L2
(n.c.)
Modulation
Damper

5 Modulating Split Zone System.
SmartCom Mulitizone
NEUT
LIVE
(COMMON)
eg
E.M.S.
(REMOTE ON)
(REMOTE OFF)
1/L 2/N 10 S/R0S/R1D0 D1 O0 O1 B1 B0 B2 C2 C0 C1 66 64 20
41 40 7 8 9 25 14 5 6
To other slave
controllers
SmartCom Mulitizone
NEUT
LIVE
(COMMON)
(REMOTE ON)
(REMOTE OFF)
1/L 2/N 10 S/R0S/R1D0 D1 O0 O1 B1 B0 B2 C2 C0 C1 66 64 20
41 40 7 8 9 25 14 5 6
To other slave
controllers
eg E.M.S.
(Slave 1)
(Master)
Drawing No. :
900290 R6 USA
NOTES:
NETWORK. Master-slave (Network)
communication is by shielded
twisted pair cable, RS485
compatible such as Belden 9841.
Maximum overall system length of
1650ft Connect screen to C0.
NOTE: Diagram shows a master
and ONE slave configuration**.
Wire further slaves in parallel.
REMOTE SWITCH INPUTS should
be connected by 18 Awg cable.
Max length is 325ft.
Low voltage switching inputs to be
normally open (closed circuit to
enable).
Connect to B0 & B1 for remote ON
(ie BMS time control).
REMOTE SENSOR(s) may be
placed at a max distance of 325ft
from the control unit, using shielded
18 Awg cable.
Wiring should be kept separate
from mains wiring to minimize noise
pick up. Set within Engineers
functions for all remote sensors.
Burners
Zone A
Burners
Zone B
20 amp Supply
120V 60Hz 1 Ph
C
Relay
S-0755 W1
S-0700
Exhaust
Fan
L2
L1 (HOT)
GND
Black Bulb
Sensor
Black Bulb
Sensor
Outside
Sensor
(where applicable)
Black Bulb
Sensor
L2
L1 (HOT)
GND 15 amp Supply
120V 60Hz 1 Ph
C
40VA
Trans
Relay
S-0700
L1
G
R
L2
C
40VA
Trans
Relay
L1
G
R
L2
L2
L1 (HOT)
GND
(n.c.)

6 Independently Modulating Split Zone System
SmartCom Mulitizone
NEUT
LIVE
(COMMON)
(REMOTE ON)
(REMOTE OFF)
1/L 2/N 10 S/R0S/R1D0 D1 O0 O1 B1 B0 B2 C2 C0 C1 66 64 20
41 40 7 8 9 25 14 5 6
To other slave
controllers
SmartCom Mulitizone
NEUT
LIVE
(COMMON)
(REMOTE ON)
(REMOTE OFF)
1/L 2/N 10 S/R0S/R1D0 D1 O0 O1 B1 B0 B2 C2 C0 C1 66 64 20
41 40 7 8 9 25 14 5 6
To other slave
controllers
eg E.M.S.
(Slave 1)
(Master)
Drawing No. :
900290R6 ID USA
NOTES:
NETWORK. Master-slave (Network) communication is by
shielded twisted pair cable, RS485 compatible such as
Belden 9841. Maximum overall system length of 1650ft
Connect screen to C0. NOTE: Diagram shows a master and
ONE slave configuration**. Wire further slaves in parallel.
REMOTE SWITCH INPUTS should be connected by 18 Awg
cable. Max length is 325ft.
Low voltage switching inputs to be normally open (closed
circuit to enable).
Connect to B0 & B1 for remote ON (ie BMS time control).
REMOTE SENSOR(s) may be placed at a max distance of
325ft from the control unit, using shielded 18 Awg cable.
Wiring should be kept separate from mains wiring to
minimise noise pick up. Set within Engineers functions any
for remote sensors.
Burners
Zone A
Burners
Zone B
L2
L1 (HOT)
GND
Modulation
Damper
eg
E.M.S.
(REMOTE ON)
Black Bulb
Sensor
Black Bulb
Sensor
Outside
Sensor
(where applicable)
15 amp Supply
120V 60Hz 1 Ph
20 amp Supply
120V 60Hz 1 Ph
C
Relay
S-0755 W1
S-0700
C
40VA
Trans
Relay
L1
G
R
L2
L2
L1 (HOT)
GND
C
40VA
Trans
Relay
L1
G
R
L2
L2
L1 (HOT)
GND
(n.c.)

7 Multizone Modulating System
SmartCom Mulitizone
NEUT
LIVE
(COMMON)
(REMOTE ON)
(REMOTE OFF)
1/L 2/N 10 S/R0S/R1D0 D1 O0 O1 B1 B0 B2 C2 C0 C1 66 64 20
41407 8 925 145 6
To other slave
controllers
To other slave
controllers
(Master)
Drawing No. :
900454 R1 USA
NOTES:
NETWORK. Master-slave (Network)
communication is by shielded
twisted pair cable, RS485
compatible such as Belden 9841.
Maximum overall system length of
1650ft Connect screen to C0.
NOTE: Diagram shows a master
and ONE slave configuration**.
Wire further slaves in parallel.
REMOTE SWITCH INPUTS should
be connected by 18 Awg cable.
Max length is 325ft.
Low voltage switching inputs to be
normally open (closed circuit to
enable).
Connect to B0 & B1 for remote ON
(ie BMS time control).
REMOTE SENSOR(s) may be
placed at a max distance of 325ft
from the control unit, using shielded
18 Awg cable.
Wiring should be kept separate
from mains wiring to minimize noise
pick up. Set within Engineers
functions for any remote sensors.
Burners
Zone A
Exhaust
Fan
SmartCom Mulitizone
NEUT
LIVE
(COMMON)
(REMOTE ON)
(REMOTE OFF)
1/L 2/N 10 S/R0S/R1D0 D1 O0 O1 B1 B0 B2 C2 C0 C1 66 64 20
41407 8 925 145 6
Exhaust
Fan
(Slave 1)
Burners
Zone B
eg
E.M.S.
Black Bulb
Sensor
Black Bulb
Sensor
Outside
Sensor
(where applicable)
eg
E.M.S.
Black Bulb
Sensor
Black Bulb
Sensor
Outside
Sensor
(where applicable)
20 amp Supply
120V 60Hz 1 Ph
C
Relay
W1
S-0700
C
40VA
Trans
Relay
L1
G
R
L2
L2
L1 (HOT)
GND
L2
L1 (HOT)
GND
20 amp Supply
120V 60Hz 1 Ph
C
Relay
W1
S-0700
C
40VA
Trans
Relay
L1
G
R
L2
L2
L1 (HOT)
GND
L2
L1 (HOT)
GND
(n.c.)

1 3
The pressure switch is attached to the damper
assembly
Release the plastic cap via two screws.
Connect the incoming cable to terminals:
1 - normally closed contact
3 - common contact
Refer to low voltage external wiring diagram for
control panel terminations.
Replace the plastic cap via two screws.
The fan damper is wired via a plug and socket arrangement. The socket is connected to the
assembly via a bracket.
Release the loose plug and
remove the cap via two screws.
Connect the incoming 24V
cable from the Control panel
onto terminals L3 and GND,
ensuring correct orientation.
Connect the incoming 4-20mA
cable from the modulation
thermostat onto terminals L1
and GND, ensuring correct
orientation.
Refer to low voltage external
wiring diagram for control panel
and modulation thermostat
terminations.
Replace the cap and plug into
socket.
CONTRACTORS
CONNECTION PLUG
FIXED CONNECTION
SOCKET
24V AC LINE
VOLTAGE
FROM PANEL
L3
L1
G
4 - 20mA
FROM
THERMOSTAT
PRESSURE
SWITCH
SCHEMATIC DIAGRAM
8 Modulation Damper and Pressure Switches
PRESSURE SWITCH CONNECTIONS

9 Schematic Two Zone One Fan ARC System.
Tail Pipe
1st Branch Zone 1
In-line Burner
To 'Mains In' on
End Vent Burner
End Vent
Module
SmartCom³ no.2
'SLAVE' (SC3-MZ)
115V 60Hz
Mains Supply
Networking Cable
Shielded pair Beldon
9841 or equiv
Isolator
End Vent
Module
In-line Burner
Branch Zone 2
18 Awg
Shielded
Cable
Sensor
Zone 2
In-line Burner
In-line Burner
In-line Burner
2nd Branch Zone 1
End Vent
Module
End Vent
Burner
1 phase
115V Pump
115V 60Hz
Mains Supply SmartCom³
no.1 'MASTER'
(SC3-MZ)
Fan Centre
Relay
Sensor
Zone A
Heater
Relay
18 Awg
Shielded
Cable
Fan Switch
End Vent
Burner
End Vent
Burner
Isolator
Isolator
Isolator
Isolator
Isolator
Isolator
Isolator
Isolator
Outside Air
Sensor
(optional)

button (C) — damper can now be
adjusted manually.
3. Rotate damper spindle until low fire end
vent suction of between 0.5” to 1” WG is
achieved. Release the manual override
button (C).
4. Using a phillips screwdriver, reposition
the mechanical end stop (A) to final
bracket position.
5. Reconnect power to damper. Recheck
correct direction of rotation (i.e. when
4mA from controller = damper fully open.)
If this is not correct, use a flat head
screwdriver and change the direction
switch (B).
C
A
B
The high/low fire end vent suction adjustment is
made using the fan damper.
Setting Maximum Fire End Vent Suction.
1. Isolate supply from the motorised
damper.
2. Press and hold the manual override
button (C) — damper can now be
adjusted manually.
3. Rotate damper spindle until end vent suc-
tion of between 2.5” to 3” WG is
achieved. Release the manual override
button.
4. Using a phillips screwdriver, reposition
the mechanical end stop (A) to final
bracket position.
5. Reconnect power to damper. Recheck
correct direction of rotation (i.e. when
4mA from controller = damper fully open.)
If this is not correct, use a flat head
screwdriver and change the direction
switch (B).
Setting Minimum Fire End Vent Suction.
1. Isolate supply from the motorised
damper.
2. Press and hold the manual override
10 Modulation End Vent Suction Setting Procedure.
Nb
Please contact an AmbiRad representative for installations over 4000’ elevation
11 Modulation Technical Information.
Heater Model
ARC18LR(M) ARC24LR(M) ARC32LR(M) ARC38LR(M)
Minimum Fire BTU 30,000 39,000 52,000 63,000
Maximum Fire BTU 74,000 98,000 130,000 155,000
Jet Size LPG L100535
(3.5mm) L100540
(4.0mm) L100544
(4.4mm) L100548
(4.8mm)
Nat Gas L100544
(4.4mm) L100549
(4.9mm) L100554
(5.4mm) L100558
(5.8mm)
Shutter Plate L100321
(17mm) L100320
(19.5mm) L100314
(22mm) L100316
(24mm)
End Vent
Orifice Plate L104102
(16mm) L104101
(24mm) L104100
(27mm) L104103
(28mm)
End Vent Suction (All Models)
Minimum Fire 0.5” to 1” WG
Maximum Fire 2.5” to 3” WG

12 SmartCom³ ARC Commissioning.
For ease and swiftness of initial start-up, the
SmartCom³ range of electronic controllers is
supplied factory pre-set to default settings as
described in the SmartCom³ Installation and
User Manual ref US/SCOM/29.
The controllers will therefore operate
immediately with standard Infrared Radiant
heaters.
To alter the control system to a single or
multi-zone ARC systems and operated along
with a Black Bulb Sensor, then the engineers’
settings will have to be modified.

Notes:
MASTER & SLAVE (NETWORK)
When setting up a SmartCom³ Master and
Slave (Network) system, the master controller
will display an error message during
commissioning. This will clear once the
commissioning is complete.
REMOTE SWITCHED INPUTS
SmartCom³ controllers can be operated
remotely via a remote ON or a remote OFF
signal in the following ways:
A. Building Management System Control
(BMS).
SmartCom³ controllers can be operated via a
BMS system, by applying a volt free
connection (ie closed circuit to enable) across
terminals B1 and B0 turns the system on.
Making this connection on a master controller
will turn the entire system on whereas making
this connection on a slave unit will only bring
on that zone.
1. BMS Controlling Time only.
Ensure all the programmed ON times in the
SmartCom³ are turned off
(i.e. They read “- -:- -”).
2. BMS Controlling Time and Temperature.
Ensure all the programmed ON times in the
SmartCom² are turned off
(i.e. They read “- -:- -”). Set all the required
day temperatures to 30°C.
B. Remote Door Interlock
SmartCom³ controllers can be connect to a
door interlock, remote frost stat or permanent
off switch via terminals B2 and B0. When a
volt free connection is provided (ie closed cir-
cuit to enable) at these terminals, the con-
troller reverts to a FROST ONLY mode.
Refer to the individual wiring diagrams for
wiring configurations and type.
Th 09 : 30 Zone 1
COMMS ERR Zone 6
FROST ONLY
EXTERNAL / DOOR
AUTO
EXTERNAL / BMS

Document reference number GB/CON/31/0311
Ambi-Rad Limited P.O. Box 617
Fishers, Indiana 46038
Telephone 317-577-0337
Facsimile 317-842-3989
Website www.ambirad.com/us