Amico PSF16 User manual

Installation Guide
1
Important Safety Instructions
When using electrical equipment, basic safety precautions should always
be followed including the following:
Read And Follow All Safety Instructions
PSF16 Channel Power Supply and Filter Pack
0-10V Dimming
1. Warning: This product must be installed in accordance with the NEC or your local
electrical code. If you are not familiar with these codes and requirements, consult a
qualied electrician. Averssement: Ce produit doit être installé conformément au NEC
ou à votre code électrique local. Si vous n’êtes pas familier avec ces codes et exigences,
consultez un électricien qualié.
2. Warning: This equipment is not for use in hazardous combusble atmospheres as
dened by the Naonal Electrical Code. Averssement: Cet équipement ne doit pas être
ulisé dans des atmosphères combusbles dangereuses telles que dénies par le Code naonal de l’électricité.
3. Warning: This equipment must be installed, operated and serviced only by trained, qualied individuals. Averssement: Cet équipement
doit être installé, ulisé et réparé uniquement par des personnes formées et qualiées.
4. These products are recommended for installaon in MRI rooms with access from both sides of the wall with a minimum distance of twelve
inches around the power unit for any building surface. Ces produits sont recommandés pour l’installaon dans des salles d’IRM avec accès
des deux côtés du mur avec une distance minimale de douze pouces autour de l’unité d’alimentaon pour toute surface de bâment
5. Cauon - Risk of shock. DIsconnect all power sources. Aenon - Risque de choc. Déconnecter toutes les sources d’alimentaon.
6. This equipment is not suitable for use in locaons where children are likely to be present. Cet équipement ne convient pas pour une ulisa-
on dans des endroits où des enfants sont suscepbles d’être présents.
Save These Instructions For Future Reference
1-05-000184
14"
10
1
2
"
8"
CUT OUT
11 1
2
"
CUT OUT
1
8
"
3
1
2
"
1"
EQUIPMENT ROOM SIDE
SCAN ROOM SIDE

2
Diagram 2
NOTE: The PSF 16 Channel Power Supply and Filter Pack must be orientated so the AC power Connections are in the equipment room. The
product will be labeled SCAN ROOM SIDE.
Diagram 1 - Mounting
Installation:
Shielding Facing
Equipment Room
Shielding Facing
MRI Room
Step 1:
Cut a rough opening in the intended mounting surface measuring
11.25” x 8”. This Step should be performed by a trained RF Vendor/
Installer.
Step 2:
Note whether the Shielding Material of the wall is facing the
Equipment Room or the MRI Room. This will determine how to
secure the PSF 16 Channel Power Supply and Filter Pack in place.
The flange must be mounted against the shielding material with
the supplied gasket in between. Reference Diagram 1.
Step 3:
Place the provided gasket along the inner edge of the flange so it
is held in place between the flange and the shielding surface. See
Diagram 2. Be sure the shielding and power supply plate are clean
before applying the RF Gasket.
Step 4:
Secure the PSF 16 Channel Power Supply and Filter Pack and gasket in place with the supplied screws using the 20 screw holes located
around the perimeter of the flange.
Step 5:
Reference the project specific plans for complete wiring instruction to make the appropriate Electrical Connections. Reference Diagram 4
for instruction on how to open the AC wiring compartment.
Note: Knockouts are provided. Use an appropriately sized connector clamp to secure the wiring entering and leaving the Filter Pack.
Additional knockouts may be added if necessary.
Note: A divider will be provided from the factory to separate Class 1 and Class 2 wiring. If using Class 1 wiring, the divider can be removed as
shown in Diagram 3.
RF GASKET
RF GASKET
RF GASKET
RF GASKET
CLASS 1
WIRING
CLASS 2
WIRING
DIVIDER
Diagram 3
Diagram 4

3
Wiring For 1 Light Control Zones (Maximum Fixtures Per Zone)
Control Zone #1 Wiring
(16) - Down Lights [LP6] Diagram #1
Wiring For 2 Independent Light Control Zones (Maximum Fixtures Per Zone)
Control Zone #1 Control Zone #2 Wiring
(4) - LP6 (9) - 2'x2' Ceiling Image [IDP] Diagram #3
(2) - Directionals [LPD] (9) - 2'x2' Ceiling Image [IDP] Diagram #3
(8) - Directionals [LPD] (12) - Down Lights [LP6] Diagram #3
(4) - Down Lights [LP6] (12) - Down Lights [LP6] Diagram #3
(4) - 2'x2' Ceiling Image [IDP] (12) - Down Lights [LP6] Diagram #3
(8) - 2'x2' Ceiling Image [IDP] (8) - Down Lights [LP6] Diagram #2
(8) - Down Lights [LP6] (8) - Down Lights [LP6] Diagram #2
Wiring For 3 Independent Light Control Zones (Maximum Fixtures Per Zone)
Control Zone #1 Control Zone #2 Control Zone #3 Wiring
(4) - 2'x2' Ceiling Image (IDP) (4) - Down Lights [LP6] (8) - Down Lights [LP6] Diagram #4
(4) - 2'x2' Ceiling Image (IDP) (2) - Directionals [LPD] (8) - Down Lights [LP6] Diagram #4
(4) - Down Lights [LP6] (4) - Down Lights [LP6] (6) - 2'x2' Ceiling Image [IDP] Diagram #4
(2) - Directionals [LPD] (4) - Down Lights [LP6] (8) - 2'x2' Ceiling Image [IDP] Diagram #4
(8) - Directionals [LPD] (4) - Down Lights [LP6] (8) - Down Lights [LP6] Diagram #4
(4) - Down Lights [LP6] (4) - Down Lights [LP6] (8) - Down Lights [LP6] Diagram #4
Wiring For 4 Independent Light Control Zones (Maximum Fixtures Per Zone)
Control Zone #1 Control Zone #2 Control Zone #3 Control Zone #4 Wiring
(4) - 2'x2' Ceiling Image [IDP] (2) - Directionals [LPD] (4) - Down Lights [LP6] (4) - Down Lights [LP6] Diagram #5
(4) - Down Lights [LP6] (4) - Down Lights [LP6] (4) - Down Lights [LP6] (4) - Down Lights [LP6] Diagram #5
(8) - Directionals [LPD] (4) - Down Lights [LP6] (4) - Down Lights [LP6] (4) - Down Lights [LP6] Diagram #5
(4) - 2'x2' Ceiling Image [IDP] (4) - Down Lights [LP6] (4) - Down Lights [LP6] (4) - Down Lights [LP6] Diagram #5
Wiring For 1 Light Control Zones (Maximum Fixtures Per Zone)
Control Zone #1 Wiring
(12) - 2’x2’ Ceiling Image [IDP] Diagram #6
(24) - 2’x2’ Ceiling Image [IDP] Diagram #7
This supply can be used to remotely power any of PDC “ethernet wiring” fixtures. The power supply can be wired to control up to 4
independent controlled light zones. Use the table below to determine the correct wire diagram (wire diagram 1-5) for the number of zones
and types of luminaires on each zone
Any standard 3-way 0-10V dimmer can be used. PDC recommends using Lutron Diva (DVSTV) or Leviton IllumaTech (IPX12) . When the
0-10V wires are shorted together that zone will shut off. If another 0-10V dimmer is used it must be wired so the common of the switch is
connected to the gray dimming wire and the normally open wire is connected to the violet wire of the switch.
Electrical Connections:
Emergency backup:
The PSF16 power supply is capable of connection directly to an IOTA
125W battery backup. This unit can be purchased directly from
PDC (part number 3-23-000203). Refer to Wiring Diagram #8 for
electrical connections
Note:
Emergency operation when wired per Wiring Diagram #8 the fixture
will operate as normal when normal AC is present. During the loss
of AC the unit will turn on luminaires #1 - #4 to full level. All of the
other luminaires in the room will go to a full dim level

4
BROWN
LIGHT BLUE
GREEN
110 - 240 VAC
Customer Supplied
RED
BLACK
VIOLET (+)
VIOLET
VIOLET
VIOLET
VIOLET
GRAY
GRAY (-)
RED/WHITE
DIM (+)
GREEN
YELLOW
ORANGE
DIM (-)
DIM (+)
DIM (-)
1 ZONE
MAXIMUM 16 FIXTURES
1 DIMMER SWITCH
OUT IN
FIXTURE
#1 - #4
FIXTURE
#13 - #16
FIXTURE
#5 - #8
FIXTURE
#9 - #12
PSF16
Located In Equipment Room Near Penetra�on Panel
OUT IN OUT INOUT IN
OUT IN OUT IN OUT IN
OUT IN OUT IN OUT IN OUT IN
OUT INOUT INOUT INOUT IN
OUT IN
PSF16
Located In Scan Room Near Penetra�on Panel
Located Near
Technologist Desk
Equipment Room Side
Scan Room Side
ZONE 1
FIXTURE #4 FIXTURE #3 FIXTURE #2 FIXTURE #1
FIXTURE #8 FIXTURE #7 FIXTURE #6 FIXTURE #5
FIXTURE #12 FIXTURE #11 FIXTURE #10 FIXTURE #9
FIXTURE #16 FIXTURE #15 FIXTURE #14 FIXTURE #13
Wiring Diagram 1
Electrical Connections:

5
ZONE 1
MAXIMUM 8 FIXTURES
1 DIMMER SWITCH
ZONE 2
MAXIMUM 8 FIXTURES
1 DIMMER SWITCH
FIXTURE
#1 - #4
FIXTURE
#13 - #16
FIXTURE
#5 - #8
FIXTURE
#9 - #12
OUT IN OUT IN OUT INOUT IN
OUT IN OUT IN OUT INOUT IN
OUT IN OUT IN OUT INOUT IN
OUT IN OUT IN OUT INOUT IN
PSF16
Located In Scan Room Near Penetra�on Panel
Located Near
Technologist Desk
Equipment Room Side
Scan Room Side
BROWN
LIGHT BLUE
GREEN
110 - 240 VAC
Customer Supplied
RED
ZONE 1
GRAY
DIM (+)
GREEN
YELLOW
ORANGE
DIM (-)
RED
DIM (-)
ZONE 2
ZONE 3
ZONE 4
DIM (+)
BLACK
GRAY (-)
VIOLET (+)
RED/WHITE
DIM (+)
DIM (-)
DIM (+)
DIM (-)
BLACK
GRAY (-)
VIOLET (+)
RED/WHITE
ZONE 1
PSF16
Located In Equipment Room Near Penetra�on Panel
FIXTURE #4 FIXTURE #3 FIXTURE #2 FIXTURE #1
FIXTURE #8 FIXTURE #7 FIXTURE #6 FIXTURE #5
FIXTURE #12 FIXTURE #11 FIXTURE #10 FIXTURE #9
FIXTURE #16 FIXTURE #15 FIXTURE #14 FIXTURE #13
ZONE 2
Wiring Diagram 2

6
ZONE 1
MAXIMUM 4 FIXTURES
1 DIMMER SWITCH
ZONE 2
MAXIMUM 12 FIXTURES
1 DIMMER SWITCH
FIXTURE
#1 - #4
FIXTURE
#13 - #16
FIXTURE
#5 - #8
FIXTURE
#9 - #12
OUT IN OUT IN OUT INOUT IN
OUT IN OUT IN OUT INOUT IN
OUT IN OUT IN OUT INOUT IN
OUT IN OUT IN OUT INOUT IN
PSF16
Located In Scan Room Near Penetra�on Panel
PSF16
Located In Equipment Room Near Penetra�on PanelLocated Near
Technologist Desk
Equipment Room Side
Scan Room Side
BROWN
LIGHT BLUE
GREEN
110 - 240 VAC
Customer Supplied
RED
ZONE 1
GRAY
DIM (+)
GREEN
YELLOW
ORANGE
DIM (-)
RED
DIM (-)
ZONE 2
ZONE 3
ZONE 4
DIM (+)
BLACK
GRAY (-)
VIOLET (+)
RED/WHITE
BLACK
GRAY (-)
VIOLET (+)
RED/WHITE
DIM (+)
DIM (-)
DIM (+)
DIM (-)
ZONE 1 ZONE 2
FIXTURE #4 FIXTURE #3 FIXTURE #2 FIXTURE #1
FIXTURE #8 FIXTURE #7 FIXTURE #6 FIXTURE #5
FIXTURE #12 FIXTURE #11 FIXTURE #10 FIXTURE #9
FIXTURE #16 FIXTURE #15 FIXTURE #14 FIXTURE #13
Wiring Diagram 3

7
ZONE 1
MAXIMUM 4 FIXTURES
1 DIMMER SWITCH
ZONE 2
MAXIMUM 4 FIXTURES
1 DIMMER SWITCH
ZONE 3
MAXIMUM 8 FIXTURES
1 DIMMER SWITCH
FIXTURE
#1 - #4
FIXTURE
#13 - #16
FIXTURE
#5 - #8
FIXTURE
#9 - #12
OUT IN OUT IN OUT INOUT IN
OUT IN OUT IN OUT INOUT IN
OUT IN OUT IN OUT INOUT IN
OUT IN OUT IN OUT INOUT IN
PSF16
Located In Scan Room Near Penetra�on Panel
PSF16
Located In Equipment Room Near Penetra�on Panel
Located Near
Technologist Desk
Equipment Room Side
Scan Room Side
BROWN
LIGHT BLUE
GREEN
110 - 240 VAC
Customer Supplied
ZONE 1
GRAY
DIM (+)
GREEN
YELLOW
ORANGE
DIM (-)
DIM (-)
DIM (-)
ZONE 2
ZONE 3
ZONE 4
DIM (+)
DIM (+)
RED
RED
RED
BLACK
GRAY (-)
VIOLET (+)
RED/WHITE
BLACK
GRAY (-)
VIOLET (+)
RED/WHITE
BLACK
GRAY (-)
VIOLET (+)
RED/WHITE
DIM (+)
DIM (-)
DIM (+)
DIM (-)
DIM (+)
DIM (-)
ZONE 1 ZONE 3
FIXTURE #4 FIXTURE #3 FIXTURE #2 FIXTURE #1
FIXTURE #8 FIXTURE #7 FIXTURE #6 FIXTURE #5
FIXTURE #12 FIXTURE #11 FIXTURE #10 FIXTURE #9
FIXTURE #16 FIXTURE #15 FIXTURE #14 FIXTURE #13
ZONE 2
Wiring Diagram 4

8
ZONE 1
MAXIMUM 4 FIXTURES
1 DIMMER SWITCH
ZONE 2
MAXIMUM 4 FIXTURES
1 DIMMER SWITCH
ZONE 3
MAXIMUM 4 FIXTURES
1 DIMMER SWITCH
ZONE 4
MAXIMUM 4 FIXTURES
1 DIMMER SWITCH
FIXTURE
#1 - #4
FIXTURE
#13 - #16
FIXTURE
#5 - #8
FIXTURE
#9 - #12
OUT IN OUT IN OUT INOUT IN
OUT IN OUT IN OUT INOUT IN
OUT IN OUT IN OUT INOUT IN
OUT IN OUT IN OUT INOUT IN
PSF16
Located In Scan Room Near Penetra�on Panel
PSF16
Located In Equipment Room Near Penetra�on Panel
Located Near
Technologist Desk
Equipment Room Side
Scan Room Side
RED
ZONE 1
DIM (+)
ZONE 2
ZONE 3
ZONE 4
DIM (+)
DIM (+)
DIM (+)
ZONE 1
BLACK
GRAY (-)
VIOLET (+)
RED/WHITE
DIM (+)
DIM (-)
BROWN
LIGHT BLUE
GREEN
GRAY
GREEN
YELLOW
ORANGE
DIM (-)
110 - 240 VAC
Customer Supplied
DIM (-)
DIM (-)
DIM (-)
RED
BLACK
GRAY (-)
VIOLET (+)
RED/WHITE
DIM (+)
DIM (-)
RED
BLACK
GRAY (-)
VIOLET (+)
RED/WHITE
DIM (+)
DIM (-)
RED
BLACK
GRAY (-)
VIOLET (+)
RED/WHITE
DIM (+)
DIM (-)
ZONE ZONE 3 ZONE 4
FIXTURE #4 FIXTURE #3 FIXTURE #2 FIXTURE #1
FIXTURE #8 FIXTURE #7 FIXTURE #6 FIXTURE #5
FIXTURE #12 FIXTURE #11 FIXTURE #10 FIXTURE #9
FIXTURE #16 FIXTURE #15 FIXTURE #14 FIXTURE #13
Wiring Diagram 5

9
Wiring Diagram 6

10
Wiring Diagram 7

11
Directive 2012/19/EU (WEEE - Waste Electrical and Electronic Equipment): Information for Users
This product complies with EU Directive 2012/19/EU. The crossed out wheeled bin symbol on the article means that at the end of its useful lifespan, this product must not be disposed
of with your other household or municipal waste. This product has required the extraction and use of natural resources for its production. It may contain hazardous substances that
could impact health and the environment if not properly disposed. In order to avoid dissemination of those substances in our environment and to diminish the pressure on the natural
resources, the user is responsible for delivering the appliance to an appropriate collection facility at the end of its useful lifespan. The separate collection and recycling of your waste
equipment at the time of disposal will help conserve natural resources and ensure that it is recycled in a manner that protects human health and the environment. For more information
on available collection facilities contact your local waste collection service or the place of purchase.
Amico Lights Corporation | 122-B East Beaver Creek Road, Richmond Hill, ON L4B 1G6, Canada | www.amico.com
Toll Free Tel: 1.877.462.6426 | Toll Free Fax:1.866.440.4986 | Tel: 905.764.0800 | Fax: 905.764.0862
For informational purposes only. Content is subject to change.
ALTINSTALLMRIPSF16CHANNELPOWER 01.18.2021
Electrical Connec�ons
Power Supply
Located in Equipment Room Near Penetra�on Panel
ORANGE
YELLOW
LT BLUE
BROWN
GREEN
GREEN
Neutral
SW1
Ground
Normally Closed
Common
WHITE (Neutral)
INPUT WIRES
FLYING LEADS
OUTPUT WIRES
DIMMING WIRES
AC (Neutral)
WHITE (Neutral)
AC (Line)
BLACK (120V)
ORANGE (277V)
ORANGE (277V)
Neutral
GRAY (NEU)
YELLOW (277V)
SW1
VIOLET (120V)
Common
RED (Common)
BLUE (Normally Open)
Normally Closed
BROWN (Normally Closed)
3-23-000203 IOTA INVERTER
Located in Equipment Room Near Penetra�on Panel
SOPGENSOPGEN
Ground
Green
BLACK (120V)
Ground
120 VAC 20 amp
Customer Supplied
NEUTRAL
LINE
GROUND
CAUTION: Do not connect OutPut Wires (Neutral) to Input Wires AC (Neutral).
Wiring Diagram 8
Table of contents
Popular Power Supply manuals by other brands

ASL INTERCOM
ASL INTERCOM BS 181 user manual

mini-box
mini-box picoPSU-80-WI-32 Quick installation guide

Patton electronics
Patton electronics 000CU2 Specification sheet

NGI
NGI N36100 Series user manual

Intec Controls
Intec Controls I-PS24 Installation & operation instructions

Ubiquiti
Ubiquiti USP-RPS quick start guide