MODEL - H
Mounting: Simple Mounting - All Models
Mounting: Simple Mounting - All Models
7/8”
(22 mm)
Mounting Bracket
2-5/8”
(67 mm)
1-1/8”
(28 mm)
1/2”
(13 mm) All Mounting Holes (Dia.)
7/32” 5/16” 7/32”
(5.5 mm) (8 mm) (5.5 mm)
1/2”
(13 mm)
Model: LGP-H
NC
NO
C
By Others
Model: HGP-H
Duty: High Gas Reset Switch
Elec. Rating: 10A, 1/8HP, 125 VAC
5A, 1/4HP, 250 VAC
Pilot Duty: 125VA, 125-250 VAC
Indicator On
Field wiring to be rated @75ºC for max 120ºF Ambient
Field wiring to be rated @90ºC for max 140ºF Ambient
Max Surge Pressure: 35 PSIG
Reset lever will latch
when gas pressure is
below setting contact
C & NC make
NC
NO
C
By Others
Reset
HGP-H
Model: HGP-H
Duty: High Gas Reset Switch
Elec. Rating: 10A, 1/8HP, 125 VAC
5A, 1/4HP, 250 VAC
Pilot Duty: 125VA, 125-250 VAC
Indicator On
Field wiring to be rated @75ºC for max 120ºF Ambient
Field wiring to be rated @90ºC for max 140ºF Ambient
Max Surge Pressure: 35 PSIG
Contacts C & NC
break when pressure
rises above setting
NC
NO
C
By Others
Recycle
RHGP-H
Reset lever will latch
when gas pressure is
above setting contact
C & NO make
Reset
LGP-H
Duty: Low Gas Reset Switch
Elec. Rating: 10A, 1/8HP, 125 VAC
5A, 1/4HP, 250 VAC
Pilot Duty: 125VA, 125-250 VAC
Field wiring to be rated @75ºC for max 120ºF Ambient
Field wiring to be rated @90ºC for max 140ºF Ambient
Max Surge Pressure: 35 PSIG
Indicator Off
Model: RLGP-H
NC
NO
C
By Others
Contacts C & NO
make when pressure
rises above setting
Recycle
LGP-H
Duty: Low Gas Reset Switch
Elec. Rating: 10A, 1/8HP, 125 VAC
5A, 1/4HP, 250 VAC
Pilot Duty: 125VA, 125-250 VAC
Field wiring to be rated @75ºC for max 120ºF Ambient
Field wiring to be rated @90ºC for max 140ºF Ambient
Max Surge Pressure: 35 PSIG
Indicator Off
Electrical Information
All gas pressure switches must be mounted in a horizontal
position, with the inlet stem down. Switches should be
reasonably leveled but do not require accurate leveling.
Single gas switch models have a NPT gas inlet.
Gas vent outlets are 1/8 NPT on all models.
Piping can be either standard black pipe or aluminum tubing.
All switches can be supported by the inlet pipe, but optional
mounting brackets are available if needed.
All switches have been factory calibrated and tested for leaks.
However, it is recommended that after the installation is
completed, switch, gas pipe inlets, and connections be tested
for leaks with a soap bubble test.
Maximum surge pressure: 35 PSIG
Maximum ambient operating temperature: 140°F (60°C)
Minimum ambient operating temperature: -40°F (-40°C)
Models Available Each Switch is adjustable within the ranges shown
Reset Recycle
LGP-H Single Unit, Low Pressure RLGP-H
HGP-H Single Unit, Hi - Pressure RHGP-H
Ranges Available
High Gas Pressure Low Gas Pressure
HGP-H, RHGP-H LGP-H, RLGP-H
1 to 7 PSI 1 to 7 PSI
6 to 15 PSI 6 to 15 PSI