
5
10 8
φ3.2mm 3.2mm
58mm
or less
.
DANGER
WARNING
NOTICE
TC100
LOCKOUTAT AL
1
2
3
46
7
9
K
INPUT TYPE CODE
Pt100
RANGE ()℃RANGE ()℉
TC100
LOCKOUTAT AL MD
MD
MD
LOCK
OUT
AT
AL
LOCKOUTAT AL
123
123
ON
DIP Switch
Description
DIP Switch Number
K Type Thermocouple (Default,)
Pt100 Type RTD
SSR Output
Relay Output
0.5% of F.S.
K Pt100,
PID ON/OFF,
35 ~ 85%RH
-10 ~ +50℃
TC210 TC300 TC400
48Hx48W 96Hx48W 48Hx96W 72Hx72W 96Hx96W
TC100
TC110-10
TC110-11
TC110-20
TC110-21
1
PV
SV
MD
LOCK
AL
OUT
AT
2
3
4
5
6
7
8
9
10
1
2
3
4
-50.0 ~ 400.0℃
-50 ~ 600℃
0 ~ 1200℃
0.0 ~ 400.0℃
-58.0 ~ 752.0℉
-58 ~ 1112℉
0 ~ 2192℉
0.0 ~ 752.0℉
TC200
TC100
TC110 TC210
TC300
TC400
TC200
ANV ELECTRIC
PID TEMPERATURE CONTROLLER
MANUAL
Please confirm the specification of controllers is to totally with
your requirement before using it, also read this user's manual
in detail.
D
D
anger! Electric Shock!
on't touch AC power wiring terminal when controller has been
powered!
Keep the power off until all of the wiring are completed!
1. Please confirm the AC power wiring to controller is correc
otherwise it would be caused aggravated damage on
controller
2. Be sure to use the rated power supply(100~240VAC or 24VDC)
otherwise it would be caused aggravated damage on
controller.
3. Please confirm wires are connected with correct terminal
(Input, Output, Alarm).
4. Use M3 screw-compatible crimp-on terminals with an
insulation sleeve, as shown below.
t
TC100/200/210/300/400 with Pin 1,2; TC110 with Pin 7,8). (
5. Avoid to install controller in following places:
a. A place where the ambient temperature may reach beyond
the range -10 to 50 .
b. A place where the ambient humidity may reach beyond the
range from 35 to 85% RH.
c. A place where the controller likely to come into contact with
water, oil, chemicals, steam and vapor.
d. A place where the controller is subject to interface with static
electricity, magnetism and noise.
6. For thermocouple(TC) input, use shield compensating lead wire.
7. For RTD input, use shield wires which have low resistance and no
resistance difference between the 3 wires.
8. DIP switch mounts on the PCB, inside the unit. Power off and
detach the case before change setting.
℃
Torque : 0.4 N.m(4kgf.cm)
58mm
or less
.
SPECIFICATIONS
INPUT TYPE TABLE
Weight
Ambient Temperature
Ambient Humidity
Power Consumption
Dielectric Strength
Isolated Resistance
Control Algorithms
Electrical Life
Output
Input
Accuracy
Rated Voltage
Dimension(mm)
Model
Voltage Range
100 ~240VAC 50/60Hz or 24VDC
Rated 90~110%
Relay NO 5A / NC 3A 250VAC
and Voltage DC24V (for SSR drive)
100000 times or more (Under the rated load)
Approx.130g
10M or more between input terminals
and case(ground) at DC 500V
Ω
1000V AC for 1 minute between input terminals and case(ground)
1500V AC for 1 minute between output terminals and case(ground)
Approx.3VA Approx.3VAApprox.4VA Approx.4VA Approx.4VA
Approx.200g Approx.200g Approx.200g Approx.260g
PARTS DESCRIPTION
SWITCH FUNCTIONS
OPERATIONS
Present Value
Setting Value
Shift Key
SYMBOL NAME FUNCTION
Down Key /
Lock Key
Up Key
Mode Key /
Save and Exit Key
Decrease numerals / Press more then
3 seconds to lock key or unlock key
Increase numerals
Shift digits when settings are changed
Use for parameter calling up and
set value registration
Lock Indicator
Alarm Indicator
Output Indicator
Autotuning Indicator
Lights when lock is activated
Lights when alarm is activated
Lights when output is activated
Lights when autotuning is activated
Displays PV
Displays SV
ON OFF
ON OFF
ON
ON
OFF
OFF
Select the sensor input
type & control output by
DIP switch on the PCB.
PARAMETER CONFIGURATION (LEVEL 1)
Light all LEDs and all
7 segment displays
Display input type Display range (0~400.0) Ready for use
SETTING SV : Ex: Change SV from 100.0 to 200.0
(Setting without pressing any key over 30 seconds will no save and return to RUN mode)
POWER ON :Controller will display as following
Press key the SV
number started to
flash
Press key to select
the digits.
Cyclic selection.
Press key Increase
or Press key
Decrease value
Press key save
value and return
to RUN mode
Press key into the LEVEL 1 parameter configuration.
(Setting without pressing any key over 30 seconds will no save and return to RUN mode)
UPPER LIMIT ALARM :
Press key to select the digits. Press key Increase or Press key Decrease value.
then press key save value and change to mode or press key
3 seconds save value and return to mode.
LOWER LIMIT ALARM
RUN
Setting range : 0.0 ~ 200.0
Default : 0.0
LOWER LIMIT ALARM :
Setting range : 0.0 ~ 200.0
Default : 0.0
Press key to select the digits. Press key Increase or Press key Decrease value.
then press key save value and change to mode or press key
3 seconds save value and return to mode.
UPPER ALARM SENSITIVITY
RUN
UPPER ALARM SENSITIVITY :
Setting range : 0.0 ~ 200.0
Default : 0.0
Press key to select the digits. Press key Increase or Press key Decrease value.
then press key save value and change to mode or press key
3 seconds save value and return to mode.
LOWER ALARM SENSITIVITY
RUN
Setting range : 0.0 ~ 200.0
Default : 0.0
Press key to select the digits. Press key Increase or Press key Decrease value.
then press key save value and change to mode
or press key 3 seconds save value and return to mode.
INCREASE ON/OFF CONTROL SENSITIVITY
RUN
LOWER ALARM SENSITIVITY :
INCREASE (PID control mode without this option)ON/OFF CONTROL SENSITIVITY :
Setting range : 0.0 ~ 200.0
Default : 0.0
Press key to select the digits. Press key Increase or Press key Decrease value.
then press key save value and change to mode
or press key 3 seconds save value and return to mode.
DECREASE ON/OFF CONTROL SENSITIVITY
RUN
DECREASE ON/OFF CONTROL SENSITIVITY : (PID control mode without this option)
Setting range : 0.0 ~ 200.0
Default : 0.0
Press key to select the digits. Press key Increase or Press key Decrease value.
then press key save value and change to mode or press key 3 seconds
save value and return to mode.
AUTO TUNING
RUN