AP O3TH User manual

Ozone Detector c/w O3TH Dec.11
Automatikprodukter
Indicator for Temperature/Humidity
Technical Data
Gas Ozone O3
Detectionprinciple Semiconductor ozone gas senso
Warm up time
First time 96 hours
Operational 1 hour
Mountingheight 300mm above floor
O3 Measuring range 10 - 1000ppb
Relayoutput One dry contact output
Current 2A switching (resistance load)
Ranges Four to be selected to control
the relay turn-on/ turn-off
Analogueoutput 0-10Vdc linearzed
Outputresolution 10Bit
Temperaturemeasurement 0-+50C
settings 5-+45C
Humidity measurement 0-99% RH
settings 5-+95%RH
Serial Interface RS485
Rate 9600/14400/19200 (default)
28800, 38400bps programmable
selection¨
Base address3 indepedent
Nodes Max 31 in a network
Powersupply 24Vac/dc
Displayresolution 1 ppb
Accuracy +/- 10 ppb + 20% of reading
Expected lifetime More than 5 years normal opera
ting environmontal
Humidityrange 5-95% rH non-condensing
Operating range 5 up to +45C
Protection Class IP30 Fire proof ABS material
Features
- Real time detection of ambient ozone gas level
- Full time indicate O3 level
- Wall mount with LCD display
- Temperature & humidity detection
- The on/off output for control a fan, O3 generator or
an alarm
- Provide an analogue output with linearover full
range output
- Adressing for RS485 mode. eg. Modbus
Description
O3 detector including digital measurement value processing
and temperature compensation for the continuous
monotoring of ozone concentration in the ambient air.
For the detection of ozone within a wide range of industrial
and commercial applications.
O3TH
Ordering Codes
O3TH 2 Ozone Detector 10 - 1000ppb (0,01 -- 1ppm)
c/w one relay output
O3TH 2M Ozone Detector 10 - 1000ppb (0,01 -- 1ppm)
c/w one relay output and Modbus
O3TH 12 Ozone Detector 10 - 1000ppb (0,01 -- 1ppm)
c/w one relay and analogue output
O3TH 12M Ozone Detector 10 - 1000ppb (0,01 -- 1ppm)
c/w one relay and analogue output, Modbus
AlarmUnits
AAW 24 Warning Siren 24Vdc 98-108dB
AAW 230 Warning Siren 230Vac 98-108dB
OA 24 Flash Light 24Vdc red
OAW 24 Combined Warning Siren and Flash Light 24Vdc
OAW 230 Combined Warning Siren and Flash Light 230V
WarningSign
Gasalarm Warning Sign ¨GASALARM¨ 24Vac/dc

Automatikprodukter
Ozone Detector c/w
Indicator for Temperature/Humidity O3TH Dec.11
We reserve the right to make changes and improvements in our
products which may effect the accuracy of the information contained
in this leaflet.
Important information
1. Always cut off power before mounting, removing and
cleaning the monitor.
2. Read all of the information in this datasheet before
mounting the detector.
3. Notice the supply power voltage of the transmitter:
24Vac/dc.
Do not install the transmitter on voltages higher than
marked on the transmitter
Mounting and Wire Connection
1. Cut off power first. Simualtaneously depress the 2
clips on either of the sides of the detector gently with
your nails or other unsharp tools, then move off the
face part.
2. Mount the detector on the place where you want to
detect O3 level 0,3m above floor.
Do not behind a door, in a corner, in direct sunlight and
near any heat or steam sources.
Do not mount the detector in the direction of the outlet
of the Ozone generator or in places where wind pass
through.
3. Mount the wall plate first.
Place the detector against the wall at desired
location;
make sure wires can be passed through the
holes of the wall plate.
4. Connect wires to terminal strips, (see the label
attached on the wall plate and fig.3).
Make sure wiring connection correct and scure.
5. Cover the face part to the wall plate

Ozone Detector c/w O3TH Dec.11
Automatikprodukter
Indicator for Temperature/Humidity
LCD and Buttons
O3 value
Locked
temperaturehumidity
Relay on
Operation
1.If you use the monitor for the first time or it hasn’t been used for a long time, then it should be energized for more
than 48 hours before it come into normal use.
If you have placed it in the direction of the outlet of the Ozone monitor or in places where wind pass through, then the
measurement of the Ozone monitor will be incorrect.
In this situation, please place the Ozone monitor in normal environment and keep it energized for at least 24 hours,
and then calibrate its zero point following step 10.
Then the monitor will return to normal use again.
When the ozone measurement range overstep the maximum measurement, the ozone sensor can be resumed after
a long time rest, and then it will return to normal use again.
2.Temperature measurement range is 0~50!, accuracy 0.5!, temperature setting range is 5~45!.
Humidity measurement range is 5~99%RH, accuracy 1%RH, humidity setting range is 5~95%RH.
Ozone measurement range is 10~1000ppb, accuracy 1ppb and setting range is 40~1000ppb, its maximum
measurement limited is 2000ppb.
3.Turn on: Turn on the monitor by press power for 2 seconds.
Temperature measurement displays on the right of upper line of LCD, the humidity measurement displays on the
left of upper line of LCD.
The preheating time of ozone sensor displays on the below line and the time is set to 300 seconds(default).
The preheating time can be changed in parameter setup.
After it is counted down to 0, ozone level will be displayed.
4.Switch setting value: press switch key to exchange setting value from between ozone and temperature/humidity.
But for the model, temperature setting is un-effective.
5.Setting O3 value: Once switching to ozone setting, the ozone number is blinking, it indicates that the O3 value can be
set by (tangent down) and (tangent up)key .
Increase or decrease 1ppb each time by pressing and rapid increase or decrease by pressing key for more than 2
seconds.
6.Lock setting value: Simultaneously depress the (tangent down and tangent up)key more than 5 seconds up to the
symbol (lock) appearing on the LCD.
Then the setting value is locked to avoid wrong operation.
7.Unlock: Under the locked mode, simultaneously depress (tangent down) and (tangent up) up to (lock) disappear.

Automatikprodukter
Ozone Detector c/w
Indicator for Temperature/Humidity O3TH Dec.11
8.When DIP4 is set to OFF(details see below Parameter Setup):
The relay will turn on when O3 measurement < O3 setting with ON symbol appearing on the right of LCD.
When O3 measurement <O3 setting , the relay will turn off with ON disappearing.
When DIP4 is set to ON(details see below Parameter Setup):
The relay will turn on when O3 measurement > O3 setting with ON symbol appearing on the right of LCD. When O3
measurement < O3 setting , the relay will turn off with ON disappearing.
The differential of ozone setting, please refer to Parameter Setup.
9.The scale bards on the right of LCD indicates the analog output. It is un-effective to this model.
10.Calibration of the zero of ozone sensor: after using the ozone sensor for more than one year, the sensor need to be
calibrated again.
Put the monitor into the space of zero ozone and preheating it, press switch key for about 20 seconds until X10
symbol appearing on the right of ozone number, then loosen switch key, the monitor starts auto zero calibration.
After 210 seconds until X10 symbol disappearing, it indicates the zero calibration finished.
Cancel the zero calibration: press switch key for about 20 seconds until X10 symbol appearing and then keep on
press switch key for about 20 seconds until X10 symbol disappearing.
It indicates the zero has no any calibration, it’s still 0.
Note: Auto zero calibration can be done only when ozone measurement is above 5ppb.
And keep the controller in the zero ozone environment before X10 symbol disappears.
Parameter Setup ( Service Manual V.O3_210)
Cut off power and simultaneously depress the 2 clips on either of the sides of the monitor gently with your nails or other
unship tools.
Move the face cover, there is a set of 4 Dipswitches on the right of the circuit board.
DIP1 ON - set parameter OFF- normal use Leaving factory: OFF
DIP2 ON - Fahrenheit OFF- Celsius Leaving factory: OFF
DIP3 Un-effective for the model Leaving factory: OFF
DIP4 ON- For decrease ozone (to control ventilation system)
OFF- For increase ozone (to control an ozone generator) Leaving factory: OFF
__________________________________________________________________________________________________
Please put DIP1 to ON, press power key to turn it on, and set the following parameters.
Press switch for switching parameters, ( tangent down,tangent up) for adjusting values.
LCD Display Parameter Setting Range Default
-00 Temperature modification +/-3.0C 0.0C
-01 Humidity modification +/-9%RH 0
-02 Ozone value correction +/-30ppb 0.0
-03 Warm up time of the ozone detector 1 - 900sec 300
( no output use, neither 0-10vdc nor
on/off, is recommended before ozone
measurement becomes stable or
warm up is finished)
-04 Un-effective for the model 0.0

Ozone Detector c/w O3TH Dec.11
Automatikprodukter
Indicator for Temperature/Humidity
LCD Display Parameter Setting Range Default
-05 Un-effective for the model 0
- 06 Minus differential of ozone 5 -30 20
of control the delay e.g. the
setting value is 10 and O3 is
50ppb, if measured O3<50-10ppb,
the relay will be on (DIP4=OFF)
or will be off (DIP4=ON).
-07 Positive differential of ozone of 5 - 100 50
’ control the delay e.g. the setting
value is 20 and O3 setting is 50ppb,
if measured O3>50+20ppb, the relay
will be off (DIP4=OFF) or will be on
(DIP4=ON).
-08 The state of the detector electrify 0: turn off after electrify 2
after power broken 1: turn on after electrify
2: keep on the last state
-09 Setting RS485 address 0-250 0
-10 RS485 communication rate selection 1: 9600bps 2: 14400bps 3
3: 19200bps 4: 28800bps
5: 38400bps
RESET: Put the DIP1 to ON and press switch key for about 25 seconds until the detector is off, then all the setting return to the
default.
Annex: Ozone Measurement Emendation
Put the four DIPs to the upper position to be ON and then start ozone emendation.
1) The digit displayed on the upper left of the LCD indicates the demarcation point that is right now being
emended.
Display range: 01, 02, 03, 04, 05, 06, 07, 08, 09, 10
2) The digit displayed on the upper right of the LCD indicates the ozone measurement at the current demarcation point.
Display range: Y1, Y2, Y3, Y4, Y5, Y6, Y7, Y8, Y9, Y10
3) The digit displayed on the bottom line corresponds to the A/D transition level of X axial.
4) The non-twinkling figure indicates the real-time ozone measurement detected by the sensor.
5) The twinkling figure indicates the demarcation point that needs to be set
Display range: X1, X2, X3, X4, X5, X6, X7, X8, X9, X10

Automatikprodukter
Ozone Detector c/w
Indicator for Temperature/Humidity O3TH Dec.11
Steps:
1) Energize the controller
2) Put the four DIPs to the upper position to be ON and wait until the digits displayed on the LCD to be stable
3) Demarcate demarcation point 1 (0), write down the un-twinkling point of X1
4) Press switch to the first demarcation point (N=1)
5) Press (tangent down) or (tangent up) to adjust the twinkling figure until it equals to X1.
Then the demarcation of X1 is finished
6) Now go to demarcation point 2, put the controller in sample gas
7) Write down the un-twinkling point of X2 and Y2
8) Press switch to the second demarcation point (N=2)
9) Press (tangent down) or to (tangent up) adjust the twinkling figure until it equals to Y2
10) Press switch, then the following figure starts twinkling
11) Press (tangent down) or (tangent up) to adjust the twinkling figure until it equals to X2.
Then the demarcation of X2 is finished
12) Repeat steps 6-11 to finish the emendation of demarcation point 3 to 10
13) After the emendation to all demarcation points, put the four DIPs to OFF.
6
1000PPB 7
5
4
3
2
1 1023 X (A/D transition)
Y ( ozone measurement)

Ozone Detector c/w O3TH Dec.11
Automatikprodukter
Indicator for Temperature/Humidity
Table:
Ozone measurement in normal air Y1=0 Sensor output in normal air X1 (zero point)
Ozone measurement in sample gas1 Y2 Sensor output in gas1 X2
Ozone measurement in sample gas2 Y3 Sensor output in gas2 X3
Ozone measurement in sample gas3 Y4 Sensor output in gas3 X4
Ozone measurement in sample gas4 Y5 Sensor output in gas4 X5
Press switch key for about 25 seconds until the monitor is off, then all the settings return to the default.
If warm-up time is less than 3 months before leaving factory, then do emendation as the second row of the following table.
If warm-up time is more than 3 months before leaving factory, then put four DIPs to ON and press switch key for about 25
seconds until the detector is off, then do emendation as the third row of the following table.
Warm-up time 0ppb 40ppb 80ppb 200ppb 300ppb 500ppb 600ppb 700ppb 900ppb 999ppb
Less than 3 months 1000 847 717 500 420 338 315 291 264 254
More than 3 months 870 720 580 500 420 338 315 291 264 254

Automatikprodukter
Ozone Detector c/w
Indicator for Temperature/Humidity O3TH Dec.11
Guidelines on How to Measure Ozone
The following information is presented to help users operate their
Ozone Detector in the most effective and efficient manner.
General
• Ozone is heavier than air and tends to sink.
Thus detection of leaks from ozone generating equipment should be performed at
the most appropriate position.
• Ozone will react and decompose on surfaces such as walls,
furniture etc.
• Smell is not a reliable test for the presence or concentration of
ozone as the odour threshold varies widely between people and
is affected by local ambient conditions.
Permanent Controller Placement
• The Ozone Detector has been designed to measure
the ambient concentration of ozone.
The controller must not be placed directly in an ozone stream.
• For indoor local area monitoring attach the controller to an inert
surface with the inlet unobstructed.
• For leak detection mount the unit near the ozone equipment.
• Ensure that the controller is protected from excessive water
splashing, dust, vibration, excessive heat or cold, high
concentrations of ozone and excessive swings in humidity.
False Readings
• The Ozone Detector has been designed to respond
selectively to ozone, however other oxidizing gases such as
chlorine and nitrogen dioxide can generate false readings if they
are at high concentrations.
High concentrations of hydrocarbon gases such as vapours of alcohol,
oils and solvents can reduce and mask the concentration of ozone.