4.4 Connecting Cable
The APM 3DLinkPro po er supply is connected ith standard cable
according to national installation standards. An outer cable
diameter of 5…9 mm ensures the seal effect of the cable entry. If
electromagnetic interference is expected, e recommend the use of
screened cable for the signal lines.
Proceed as follo s to connect cable to the po er supply:
1. Loosen the four scre s of the housing ith a scre driver
2. Remove the housing cover
3. Unscre the po er supply lines from the left green connector
of the 3DLevelScnner
4. Remove the cable from the 3DLeveScanner through the gland
5. Insert the cable through the left gland of the 3DLinkPro
6. Open the terminals ith a scre driver
7. Connect the ires to sockets "1" and "2" according to the
diagram. Take note of the polarity.
8. Close the terminals
9. Tighten the compression nut of the cable entry. The seal ring
must completely encircle the cable
10. Scre the housing cover back on
11. If the cable is screened please follo the procedure in the
"cable screening and grounding" paragraph
12. Tighten the compression nut of the cable entry. The seal ring
must completely encircle the cable
The electrical connection is finished.
4.5 Connecting the Communication
(4…20mA/HART) to the APM 3DLinkPro
1. Unscre the communication lines (2W of 4…20mA/HART) from
the left green connector of the 3DLevelScnner.
2. Remove the cable from the 3DLeveScanner through the gland
3. Insert the cable through the left gland of the APM 3DLinkPro
4. Connect the ires to sockets "3" and "4" according to the
iring diagram, above.
4.6 Connecting the RS-485 wires to the APM
3DLinkPro
Connect t o ires to sockets "11" and "12" according to the
diagram belo .