APsmart RSD-S-PLC Instruction Manual

smart
Installation / User Manual
TRANSMITTER-PLC/TRANSMITTER-PLC
ALTENERGY POWER SYSTEM INC. www.APsmartGlobal.com
© All Rights Reserved
APsmart rapid shutdown system
RSD-S-PLC
Rev1.0 2020/03/18

IMPORTANT SAFETY INSTRUCTIONS
This manual contains important instructions to be followed during installation and maintenance of the
APsmart RSD and Transmitter. To reduce the risk of electrical shock and ensure the safe installation
and operation of the APsmart RSD and Transmitter, the following symbols appear throughout this
document to indicate dangerous conditions and important safety instructions.
Safety Instructions
· Do NOT disconnect the PV module from the RSD-S-PLC without first disconnecting the AC power.
· Only qualified professionals should install and/or replace the APsmart RSD-S-PLC.
· Perform all electrical installations in accordance with local codes.
· Before installing or using the RSD-S-PLC, please read all instructions and cautionary markings in the
technical documents.
· Be aware that the body of the running RSD-S-PLC is the heat sink and can reach high temperatures.
To reduce risk of burns, do not touch the body of the RSD-S-PLC.
· Do NOT attempt to repair the RSD-S-PLC. If it fails, contact APmart Customer Support to obtain an
RMA number and start the replacement process. Damaging or opening the RSD-S-PLC will void the
warranty.
The Transmitter-PLC control power supply MUST be on the same AC branch circuit as the inverter to
meet rapid shutdown requirements.
Symbols replace words on the equipment, on a display, or in
manuals
Qualified personnel:
1
Person adequately advised or supervised by an electrically skilled person to enable him or her to per-
ceive risks and to avoid hazards which electricity can create. For the purpose of the safety information
of this manual, a "qualified person" is someone who is familiar with requirements for safety, refrigera-
tion system and EMC and is authorized to energize, ground, and tag equipment, systems, and ircuits
in accordance with established safety procedures. The inverter and endues system may only be com-
missioned and operated by qualified personnel.

RSD PRODUCTS
RSD-S-PLC
· Meets NEC 2017 (690.12) requirements
· Executes rapid shutdown of system
· Meets SunSpec requirements
2
when Transmitter-PLC signal is absent
RSD-S-PLC meets SunSpec requirements,maintaining normal function by continually receiving a
heart-beat signal from the APsmart Transmitter. The RSD executes rapid system shutdown when
Transmitter signal is absent. Users can manually execute rapid shutdown using Transmitter breaker
switch.

SYSTEM WIRING DIAGRAM
①RSD-S-PLC
②Transmitter-PLC (integrated in CPS 25/50/60kW inverter APS RSD wire-boxes)
③Inverter
The APsmart Rapid Shutdown System Transmitter-PLC is part of a rapid shutdown solution when
paired with APsmart RSD-S-PLC, a PV module rapid shutdown unit. While powered on, the
Transmitter-PLC sends a signal to the RSD-S-PLC units to keep their PV modules connected and
supplying energy.
RSD-S-PLC units automatically enter rapid shutdown mode when the Transmitter-PLC is switched
complies with NEC 690.12 specifications for 2017 and supports the SunSpec signaling for rapid shut-
down.
The Transmitter-PLC includes one or two cores and an optional power supply: 85-264VAC for
residential, 180-550VAC for commercial.
-
+
-
+
-
+
-
+
-
+
-
+
- +
- +
- +
- +
- +
- +
- +
- +
2
3
1
4

RSD-S-PLC INSTALLATION
INSTALLATION NOTES
Installation MUST comply with local regulations and technical rules:
①Perform all electrical installations in accordance with local codes.
②Be aware that only qualified professionals should install and/or replace the RSD-S-PLC.
③Before installing or using an RSD-S-PLC, please read all instructions and warnings in the technical
documents and on the inverter system itself as well as on the PV array.
④Be aware that installation of this equipment includes the risk of electric shock.
⑤Do not touch any live parts in the system, including the PV array, when the system has been
connected to the electrical grid.
⑥Ensure the solar module and inverter has been disconnected before installing an RSD-S-PLC.
Additional installation components from APsystems
Required parts and tools to complete the installation
· DC extension cable (sold separately)
In addition to your PV array and its associated hardware, you will need the following items:
· Rapid shutdown device installation kit (screw, nut)
· A torque wrench and a Phillips screwdriver
①Be sure to verify the voltage and current specifications of your PV module match with those of
the RSD-S-PLC.
②You must match the DC operating voltage range of the PV module with the allowable inpust
voltage range of the RSD-S-PLC.
③The maximum open circuit voltage of the PV module must not exceed the specified maximum
input voltage of the APsystem RSD-S-PLC.
6

Step 1: Install the RSD-S-PLC.
Buckle RSD-S-PLC on the PV module frame.
DC input - DC input +
DC output - DC output +
Mounting brackets
A. Front buckle
B. Back buckle
Note: Both installations can be installed anywhere on the PV module frame.
7

Step 2: According to the component arrangement, connect the
output port of the RSD-S-PLC and connect the input port to the
junction box.
Step 3: Connect the RSD-S-PLC serially connected output to the
inverter with a self-made DC extension cable.
self-made DC extension cable
GRID
DC 1
DC 2
DC 1 DC 2 DC Switch COM GRID
Input-
Output-
Input +
Output +
Input-
Output-
Input +
Output +
7

TRANSMITTER-PLC INSTALLATION
• Mount Transmitter-PLC and power supply on DIN rail
• Connect DC leads from power supply to Transmitter-PLC
• Connect single/dual core(Core 1 and Core 2) to Transmitter-PLC
No
Note: If there is only one core need to connect, please connect Core 1 first.
te: Install RSD-S-PLC before powering on Transmitter.
Place rapid shutdown system label no more than 1m (3ft) from Transmitter or AC
disconnect if not at same location.
T
During operation, the Power LED should be lit and the Signal LED should be blinking.
When Transmitter fails to work, the Signal LED will not be blinking. If the Power
LED is also not lit, check the power supply first.
ransmitter power supply must be on same AC branch circuit as inverter to meet
rapid shutdown requirements.
9
V-V+
N L
V -
CUS
25 907 7
sm ar t
Power Supply
Transmitter-PLC
Core 1
1
2
3
1
3
Power LED
V+
V -
Signal LED
Core 1
2

Note: Install RSD-S-PLC before powering on Transmitter.
s30 modules
C150A
v v 3300ft (1000m)
V-V+
N L
V -
CUS
25 907 7
smart

TECHNICAL DATA LC
Model RSD-S-PLC
Input Data (DC)
Input Operating Voltage Range
Output Operating Voltage Range
8-80V
8-80V
Maximum Cont. Input Current (Imax) 15A
Maximum Input Power 800W
Output Data (DC)
Output Power Range 0-800W
st VyMaximum S em oltage 1000V/1500V
Mechanical Data
Operating Ambient Temperatu
r
e Range -40 °C to + 85 °C (-40 °F to +185 °F )
Dimensions (without cable & connectors) 5" x 1.2" x 0.6" (129 mm x 30 mm x 16 mm)
Cable Length Input 250mm/ Output 1200mm or Customize
Module Connector MC4 or MC4 Compatible
Enclosure Rating Type 6P/ IP68
Overtemperature Protection Yes
Features & Compliance
Communication PLC
Safety Compliance
NEC 2017 (690.12); UL1741; CSA C22.2 No. 330-17;
IEC/EN62109-1; 2PFG2305
EMC Compliance FCC Part15; ICES-003; IEC/EN62109-1/-2/-3/-4
12
—RSD-S-P

TECHNICAL DATA—TRANSMITTER-PLC
Model Transmitter-PLC
Main Electrical Data
Input Voltage 12 VDC
Input Current 0.5A
Communication P LC
Power Supply
Residential(optional)85-264VAC Input, 12VDC Output,
90 mm x 17.5 mm x 58.4 mm
Commercial(optional)180-550 VAC Input, 12VDC Output,
125.2 mm x 32 mm x 102 mm
Core Data
Max.Current 300A (150AX2)
Max. System Voltage 1500VDC
Inner Hole Size Of Core
Inner Diameter 29mm
Max. Supported PV Modules per String 30 modules
DC Cable Diameter Φ5.94mm Φ6.35mm Φ6.97mm Φ8.57mm
DC Cable Size 2.5mm² 4mm² 6mm² 10mm²
Number Of Strings Per Core(without connector) ≤15 ≤15 ≤14 ≤10
Environmental
Max. Number Of Strings per core
Temperature -40°C~+100°C
Structure Data
Dimensions (W x H x D) 90 mm x 35 mm x 40 mm
Enclosure Environmental Rating IP30
Features & Compliance
Safety Compliance NEC 2017 (690.12); UL1741; CSA C22.2 No. 330-17
EMC Compliance FCC Part15; ICES-003
13
Number Of Strings Per Core(with connector) ≤12 ≤10 ≤7 ≤5
Other manuals for RSD-S-PLC
9
Table of contents
Other APsmart Control Unit manuals
Popular Control Unit manuals by other brands

Parker
Parker PA Series Installation, operating, & maintenance instructions

SMC Networks
SMC Networks VM1000 Series instruction manual

Siemens
Siemens Simatic S7-1500/ET 200MP manual

Aventics
Aventics RV2 operating instructions

Parker
Parker SS1500 Series Installation & service instructions

Mitsubishi Electric
Mitsubishi Electric FX-USB-AW user manual