Aqua Guard BS9251 Guide

Page | 1
AquaGuard BS9251 Fire Pump Controller
User & Installation Manual

Page | 2
Table of Contents
1. Product Description Page 3
2. User Interface Page 4
3. Installation Guide Page 5
4. Controller Set Up Page 6 - 7
5. Commissioning Page 8
6. Annual Maintenance Page 9
7. NFC Connectivity Page 10
8. Fault Alarm Table Page 11
9. Troubleshooting Page 12
If additional assistance or information is required, please contact
AquaGuard Pumps Technical on 0800 040 7738.

Page | 3
1. Product Description
The AquaGuard fire pump controller has been designed as an easy to install, all in one
solution to control the operation, monitoring and automatic testing of the fire pump in
accordance with BS9251:2014.
Incorporating an informative LCD display and optional Mobile App to assist programming
and view/save event logs making the AquaGuard fire pump controller the most
advanced on the market.
Features
Jockey Mode - Upon pressure loss the pump will operate, if no flow is detected then
pump will shut off after 2 minutes.
Fire Mode - If pressure loss and flow are detected pump will operate in fire mode until
manually shut down.
Test Mode –Each Monday at 10am the controller will open the solenoid valve until the
pressure switch is activated and run the pump checking voltage/current and power are
within set parameters. Current check only version will test at the same time running the
pump checking voltage/current and power are within set parameters.
Maintenance - Maintenance interval is pre-set to every 12 Months but can be adjusted
to suit specific interval requirements. Maintenance due indicator will require a physical
flow test to reset.
Event Log - Event log up to 128 entries can be accessed on the control panel or
downloaded from the Mobile App via the IR dongle*.
Setup Mode - All settings can be changed if required with the use of an advanced user
password to prevent unauthorised access to settings.

Page | 4
2. User Interface
2.1 –AquaGuard fire pump controller button and LED description.
2.2 –AquaGuard fire pump controller LCD Display ‘Home Screen’ description.
Controller
Home Screen

Page | 5
3. Installation Guide
General
3.1 - This product must be installed by a suitably qualified electrician.
3.2 - This controller must be earthed.
3.3 –This controller should be wired to a suitable isolator, fed directly from the electrical
distribution board protected by a dedicated RCD/RCBO suitably sized for the fire pump
installed.
Installation
3.4 –AquaGuard Fire Pump Controller must be connected as per diagram below. The
current check only version will not have the solenoid cable present. Take care with
solenoid connection as 230v will be present to solenoid when requested.
Fig.1

Page | 6
4. Controller Set Up
4.1 –Once controller has been wired as per diagram (Fig.1) the controller power supply
can be switched on, please note that on initial power up the pump will run to reach
system pressure, please ensure that all suction valves are open and pump has been fully
primed and free of any air before switching on for the first time.
4.2 –Shortly after switching the controller on for the first time, once system pressure
(Pmax) has been made the controller will start a 2 minute countdown indicating ‘Jockey
Mode’ press the ‘Stop’ button and the home screen and green power led should be
visible as image below. If the ‘Sprinkler activated’ is displayed press the ‘Reset’ button to
reset.
If pump current/power differs from the pre-set current/power of 5 amps and 1.1KW
then the installed pump current will need to be entered into the controller following the
steps below.
4.3 –Setting Pump Current and Power
1. To set the pump current and power, press the ok (tick) button to enter ‘Main
Menu’.

Page | 7
2. Navigate to ‘Enter Password’ (key icon), enter code 2000, press right to key
symbol then press ok (tick).
3. Enter main menu, navigate to ‘Setup’. To enter setup you must first hold the
‘Manual Mode’ button located on the underside of the controller (Fig 4) and press
ok on the keypad (once into setup the manual mode button can be released).
4. Once in ’Setup’, go to ‘M02 General’, navigate down to ‘Nominal Current’ press
ok. Using the left and right arrows adjust the current to match the pump current
indicated on the pump data plate. Once entered press ok.
5. Press the ‘Stop’ button to navigate back to ‘M02 General’ then navigate down to
‘Nominal Power’ press ok. Using the left and right arrows adjust the power (KW)
to match the pump power (KW) indicated on the pump data plate. Once entered
press ok. Then press the ‘Stop’ button three times to exit to home screen this will
prompt a system reset to update values entered.
Warning: All controllers are pre-programed and tested to comply with BS9251, only
change the current and power parameters to suit installed pump, changes to any other
parameters may prevent the controller from operating correctly and will invalidate the
warranty.
4.4 –Setting Time and Date
From the home screen display, press the up key until the time and date are visible on
display, then press the left and right keys at the same time to edit. Use the up, down,
left, right keys to set time and date then press ok (tick) button to set. Press the down key
until the home screen is displayed. Note: date is in the format of MM/DD/YYYY.

Page | 8
5. Commissioning
5.1 –Filling the system
If the sprinkler system was not filled upon initial power up in step 4.1, please proceed to
filling the system, this may activate the alarm output therefore it may be required to
temporarily isolate the alarm. Once system pressure (Pmax) has been made the
controller will start a 2 minute countdown indicating ‘Jockey Mode’ press the ‘Stop’
button and the home screen and green power led should be visible as image below. If
the ‘Sprinkler activated’ is displayed press the ‘Reset’ button to reset.
5.2 –Setting of Pressure Switch
The installed pressure switch may need adjusting from factory default settings, it is
recommended that the system pressure switch be set approximately 0.5 bar above
pressure required in the ‘most unfavourable hydraulic calculations’. Refer to pressure
switch instruction manual for setting instructions, this should be undertaken with the
Aquaguard pump controller switched off.
5.2 –Flow Test
From the pump test valve a flow test should be undertaken to check pump satisfies the
flow and pressure requirements set out in the system Hydraulic Calculations, after 15
seconds of the system flowing the ‘Sprinkler Activated’ will appear triggering the alarm
output. Once flow test has been completed and system repressurised press the ‘Stop’
button then ‘Reset’ button to return to home screen.
5.3 –Weekly Test
To force a weekly test to ensure correct operation of solenoid etc, using the instructions
set out in ‘4.4 – Setting Time and Date’ adjust the time to a Monday at 09.58, press ok,
then press the down key until the home screen is displayed.
Within two minutes the weekly test will start, opening the solenoid valve until the
pressure switch is activated and run the pump for 60 seconds checking voltage/current
and power are within set parameters. Current check only version will run the pump for
60 seconds checking voltage/current and power are within set parameters.
Once test is completed, repeat the steps in 4.4 to reset to correct time and date.

Page | 9
6. Annual Maintenance
6.1 –Annual Maintenance Reset
12 Months from system commissioning the ‘Maintenance 1 Requested’ fault will be
displayed; this will not trigger the fault output unless requested. This maintenance fault
can only be reset by undertaking an annual flow test.
To reset annual maintenance undertake the following procedure.
1. Undertake a flow test as per section 5.2, please note if flow detected for more
than 15 seconds the alarm output will be triggered. Once finished press the ‘Stop’
button followed by the ‘Reset’ button.
2. Following the same password and button entry procedure in section 4.3, enter
main menu, navigate to the ‘Enter password’ section, enter code ‘2000’ then press
ok on the key symbol.
3. Enter main menu, navigate to the ‘Commands’ menu, while holding the ‘Manual
mode’ button press ok.
4. Once in ‘Commands’ menu, navigate down to ‘C01 Reset Maintenance Interval 1’
press ok to execute it, the device will prompt for a confirmation, press ok again,
this will reset the maintenance to a further 12 months. Press the ‘Stop’ button
several times to exit to home screen.
6.2 –Event Log
The Aquaguard controller has a 128 entry event log incorporated, this indicates in detail
with a date and time every event that has occurred. To view, from the controller home
screen press the up key until the ‘Event Log’ screen is displayed, then use the left and
right keys to navigate through the log.

Page | 10
7. NFC Connectivity
The Aquaguard fire pump controller has incorporated NFC mobile connectivity. This
allows the user to easily change parameters and download the event log via an app (Only
available on Android devices). To use this feature, complete the following.
1. Go to the Google ‘Play Store’ and download the ‘Lovato NFC’ app. Ensure NFC is
activated in your device settings.
2. Once downloaded, open the app and select ‘Download Driver’, once complete will
display ‘Driver downloaded successfully’.
3. Hold the mobile device to the NFC symbol on the Aquaguard controller, may have
to move phone around slightly to achieve a connection. The NFC works when the
controller is off, if the controller is powered on then the ‘Manual mode’ button
must be pressed when connecting.
4. Once connected, you will be prompted to input the advanced user passcode which
is 2000.
5. Once connected, navigate the menu to change the current/power parameters,
reset maintenance or view event logs.
6. To execute a current/power parameter change or command follow the on screen
prompt to place mobile device against the NFC symbol on the controller, as above
if powered on the ‘Manual mode’ button must be pressed when connecting. The
mobile device will state a successful upload and the controller will reset.
Warning: All controllers are pre-programed and tested to comply with BS9251, only
change the current and power parameters to suit installed pump, changes to any other
parameters may prevent the controller from operating correctly and will invalidate the
warranty.

Page | 11
8. Fault Alarm Table
If any faults are present on the controller then these will be displayed on the LCD display
with a code A01 –A38, see alarm table below for description.

Page | 12
9. Troubleshooting
Issue
Possible Cause
Action
Controller not powering on
Power supply to controller not
on or wired incorrectly.
Check all connections, fuses and
MCB/RCBO.
Controller powers on, then goes
off when pump start requested.
Pump wired incorrectly
Fuse or MCB/RCBO not sized
correctly for pump.
Check pump motor wiring
Replace fuse, MCB/RCBO for an
adequately sized C rated type.
Pump running not pressurising
system
Suction/delivery valves closed
Pump not primed
Check all suction and delivery
valves are open.
Open all pump bleed screws
until water flows freely.
Pump not generating design
flow/pressure
Pump not adequately primed
Obstruction in suction or
delivery pipe work.
Suction pipe diameter too small
or pipe run too long
Open all pump bleed screws
until water flows freely.
Check pipe work and clear if
necessary.
Pump suction must never be
smaller than pump inlet
diameter. If long suction pipe
run then increased pipe size
should be used.
Pump not running when
pressure low or at zero
Pressure switch not wired
correctly
Pressure switch cable wired to
flow switch
Wire pressure switch between
COM and NC (normally closed)
Wire pressure switch cable to
pressure switch as above.
230v Solenoid valve fails to
operate on weekly test followed
by voltage fault on controller
Incorrect wiring to solenoid
Check wiring –may have blown
1.6A fast blow fuse in controller,
replace if necessary.
External Fire Panel in fault when
pump controller displays no
fault on the LCD Display.
Incorrect wiring of fault output
Pump controller switched off
Fault output must be wired
normally closed (NC)
Turn pump controller on
Faults - A11 Current too low,
A12 Current too high, Power too
high, Power too low.
Correct pump current and
power not input correctly
Possible pump fault
Follow the steps in section 4.3.
Check current/power reading if
vastly different to pump data
plate call pump manufacturer.
Fault present on pump
controller
Refer to fault alarm table in
section 8 to identify fault and
possible action required.
Undertaken action if possible.
Call Aquaguard if problem
persists.
If the controller is suspected to be faulty call Aquaguard on 0800 040 7738 for advice.
Table of contents
Other Aqua Guard Controllers manuals
Popular Controllers manuals by other brands

Hoffman
Hoffman 709D-VmA Series Installation and operating instructions

Sentera Controls
Sentera Controls SD Mounting and operating instructions

Supermicro
Supermicro AOC-S3616L-L16iT user manual

Fisher
Fisher EMERSON VSX4 Series instruction manual

NRI
NRI G-26.4000 Series manual

Mitsubishi Electric
Mitsubishi Electric MELSEC iQ-R Series user manual