AquatiControl Technology ELC-810 Series User manual

OPERATION AND MAINTENANCE MANUAL
ELC-810
AUTOMATIC WATER LEVEL CONTROLLER
AquatiControl Technology
3820 South Federal Blvd
Sheridan, Colorado 80110
Toll Free: 877.755.8817
Fax: 303.761.1499
www.aquaticontrol.com
Serial No. _____________________ Model No. _______________________

ACT 2009
- 2 -
TABLE OF CONTENTS
Introduction ................................................................................... 3
Installation ................................................................................. 4-5
Wiring Diagram...............................................................................6
Operation ................................................................................... 7-9
Routine Maintenance .................................................................. 10
Troubleshooting .................................................................... 11-12
Warranty ..................................................................................... 13

ACT 2009
- 3 -
INTRODUCTION
The AquatiControl Technology (ACT) Model ELC-810 is designed to provide the
most accurate and reliable automatic water level control for swimming pools, spas,
fountains, and spray pads. All of the user-friendly features incorporated into the system
were designed with the operator in mind.
The importance of precise control of water level in relation to proper filtration and
water chemistry makes it possible to appreciate a device that will maintain levels within
+/- 1/8 of an inch. Installing the system requires basic tools and is accomplished quickly.
Installation and operating directions can be found on the following pages of this manual.
The ELC-810 should ship with the following contents:
(1) Control unit
Sensing Unit(s)
Standard Well
Sight Glass
Wet Well
Surge Tank
Deck Well
(1) Mounting Hardware
(1) Operation and Maintenance Manual
(1) Warranty Card
If any items are not found in this package, please call your closest distributor or
the factory at (877) 755-8817.
ELC-810-SW ELC-810-DW ELC-810-SG ELC-810-WW ELC-810-ST
Standard Well Deck Well Sight Glass Wet Well Surge Tank
Sensing unit Sensing well Sensing box Sensing stick Sensing stick
5' of ½”
Polytubing Sensing box Mounting
hardware 1 compression
fitting 2- 1" Clic
clamps
1/2" PVC ball
valve Mounting
hardware 25' remote
cable Mounting
hardware Mounting
hardware
2- 1/2" Parker
fittings 25' remote
cable
25' remote
cable 25' remote
cable
1/2"xclose
Nipple TBE
Mounting
hardware
25' remote
cable

ACT 2009
- 4 -
INSTALLATION
The controller and sensing unit should be securely mounted on a sound surface.
The controller should be mounted within 5 feet of a 120 VAC, 60 Hz grounded outlet.
The controller can be wired up to 300 feet from sensor unit (contact ACT for
exceptions). ACT recommends mounting the controller in the most favorable
environment possible.
The standard well sensing unit is installed at the water level of the pool. The
center of the clear ½” PVC tube on the sensor unit should be at the normal
operating water level of the pool. An isolated static water line from the pool to
the sensor unit is necessary to provide stable water conditions. A valve
arrangement is provided. The valves are installed so that the operator may
maintain and clean the sensing unit.
The sight glass sensing unit is installed by attaching the unit to a balance tank
sight glass. The sensor should be mounted at normal operating water level of the
balance tank using the attached clic connectors.
The wet well sensing unit is installed in a 2” PVC pipe which serves as a still
water stand pipe from the pool. The normal water level should sit approximately
1.5” up from the bottom of the end cap.
The surge tank sensing unit is installed in the surge tank at normal operating
water level with the included clic connectors. The normal water level should sit
approximately 1.5” up from the bottom of the end cap.
The deck well sensing unit is installed at pool side. The unit has a ½” static line
sight glass inside to attach a sight glass sensing unit to, which is also provided.
The deck well is connected to the pool using a 2” static line. Conduit connection
and drain connections are also present to make installation quick and easy.
The 3 conductor extension cable provided with the system is the electrical
connection for the sensor unit to the controller. With the standard well, sight glass, wet
well and deck well, a terminal strip is provided in the sensor housing for terminating the
cable (please see wiring diagram for color connections located inside sensor box for
standard well, sight glass, wet well, and deck well applications). The other end of the
cable terminates inside the ELC-810. The interconnecting cable carries low voltage.
Local codes may require the cable to be housed in conduit.
Refer to www.aquaticontrol.com for sensing applications, drawings, and other product
information offered by AquatiControl Technology.

ACT 2009
- 5 -
CONNECTING THE SOLENOID VALVE
The ELC-810 unit will actuate up to a 2” solenoid valve with a 24 VAC, 10 watt
(max) supply, without the use of an auxiliary relay. We recommend an anti-water
hammer or slow close solenoid valve. The power and ground cables should be directly
connected to the ELC-810 terminal strip.
Refer to www.aquaticontrol.com for a full line of solenoid valves.
CONNECTING ALTERNATE LEVEL SENSOR
The ELC-810 has an alternate level sensing feature that allows a surge tank to run
at two different levels. This feature is activated with a flow switch or through a signal
from the contactor on the feature pump located near the starter; and is normally used in
conjunction with spray features.
In order to setup the use of an alternate level on the ELC-810, a second sensing
application should be placed at the chosen lower water level and a flow switch, supplied
with the ELC-810, needs to be installed in the feature pump line. The second sensing
application and flow switch must be wired following the wiring diagram on page 6 of this
manual.
CONNECTING HIGH LEVEL WATER DRAIN OFF
The ELC-810 has a high water drain off feature that allows a NC/NO relay inside
the unit to be used to open a solenoid that will drain water.
In order to setup the use of the high water drain off feature on the ELC-810, a
third sensing application should be placed at the chosen higher water level and a second
24 VAC solenoid, not supplied with the ELC-810,should be used (can be a general
purpose solenoid). The third sensing application and second solenoid must be wired
following the wiring diagram on page 6 of this manual.

ACT 2009
- 6 -

ACT 2009
- 7 -
OPERATION
Once installation has been completed as described on pages 4 and 5, open water
supply valve to sensor unit. If the water is not up to normal operating level in the pool,
manually adjust the water level to that point.
After level is set and water is at normal operating level, it is time to power the
control unit. Plug the unit into the 120 VAC, 60 Hz electrical outlet; turn the on/off
toggle switch on the side of the controller to the ON position. The unit will go through a
self-test and beep to let you know it is on.
Once power is applied to the controller there are settings in the menu that can be
changed. You can scroll through the menu by pressing the up and down arrows. The enter
button will bring you back to the startup screen. Options can be changed by following the
directions below.
The first six screens as you scroll down through the menu are for informational
purposes. The screens give you the following information.
STARTUP SCREEN
This screen will tell you the version of code that your controller is running.
SCREEN 1
This screen will tell you what your controller settings are for Delay Time To
Shutoff and Maximum Fill Time.
SCREEN 2
This screen will tell you what your controller settings are for Manual Override
and Delay To Normal.
SCREEN 3
This screen will tell you what your controller settings are for Level Sensor Type
and Alternate Sensor Option.
SCREEN 4
This screen will tell you what the Last Fill Time was.
SCREEN 5
This screen will tell you what the Last Drain Time was.
SCREEN 6
This screen will tell you when the Last Alarm was.

ACT 2009
- 8 -
Following the informational screens is the ability to change menu options. In
order to change settings, bring up the option and press the right arrow until a small “p”
appears in the lower right corner of the LCD. The user is then able to change the settings
using the specified arrows for each setting.
PASSWORD (enables password protection of settings)
NONE – No password required to change settings
SETUP- Press the enter button and input up to an 8 digit (0-9) password, press the
enter button to confirm new password.
If the password is forgotten the user can perform a master reset by powering the
unit on while holding the left and right arrows (this will reset all settings to the
factory default settings).
DEFAULT:None
MANUAL OVER-RIDE (turns on fill solenoid for specified time, for testing purposes)
Manual Over-ride can be set from 5 seconds to 99 seconds. (use up and down
arrows to change) To activate this option hold the left and right arrows for
3 seconds.
DEFAULT:10 seconds
DELAY TO SHUTOFF (time solenoid valve will stay on after sensor begins sensing water)
Delay to Shutoff can be set from 2 seconds to 5 minutes. (use up and down arrows
to change)
DEFAULT:0:02 seconds
MAXIMUM ON TIME (maximum time solenoid valve is allowed to stay on per fill cycle)
Maximum On Time can be set from 30 minutes to 240 minutes using the up and
down arrow buttons, or continuous using the left and right arrow buttons.
DEFAULT:120 minutes
ALTERNATE SENSOR (enables alternate level feature option)
On or Off (use left and right arrows to change)
DEFAULT:Off
DELAY TO NORMAL (time before solenoid is turned on after switching from alternate level
sensing to normal level sensing)
Delay to Normal can be set from 1 minute to 60 minutes. (use up and down
arrows to change)
DEFAULT:60:00 minutes
HIGH LEVEL OPTION (enables high level feature option)
No or Yes (use left and right arrows to change)
DEFAULT:No

ACT 2009
- 9 -
FLOW SENSOR ACTIVE (allows use of normally open or normally closed flow switches)
Open or Closed (use left and right arrows to change)
DEFAULT:Closed
SENSOR TYPE (set to Other)
DEFAULT:Other
SOUNDER WITH ALARM (beeping will occur when in alarm mode if yes is selected)
Yes or No (use left and right arrows to change)
DEFAULT:Yes

ACT 2009
- 10 -
ROUTINE MAINTENANCE
AquatiControl Technology’s Model ELC-810 controller is completely solid state
and normally will not require any maintenance.
SENSOR UNIT CLEANING
STANDARD WELL
The ½” PVC tube on the Standard Well Sensing Unit may need to be cleaned
periodically. To clean the tube, isolate the sensor unit by closing the valve that
supplies the water to it. Remove the cap from the top of the tube and fill with a
diluted acid solution, 3 parts water to 1 part acid. A brush may be used to clean
the inside of the tube.
The valve at the bottom of the sensing unit can be opened to drain out the acid
solution. Place the solution into a container and dispose of it properly. The tube
can then be flushed with fresh water. After flushing, open the valve from the
pool. The unit is now ready for operation.
SIGHT GLASS
The Sight Glass Sensing Unit will not normally need to be cleaned.
SURGE TANK
The Surge Tank Sensing Unit will not normally need to be cleaned; however, if
the cap on the bottom of the sensing application becomes clogged with debris, it
can be unscrewed and rinsed until clean and then replaced.
WET WELL
The Wet Well Sensing Unit will not normally need to be cleaned; however, if the
cap on the bottom of the sensing application becomes clogged with debris, it can
be unscrewed and rinsed until clean and then replaced.
DECK WELL
The Deck Well Sensing Unit will not normally need to be cleaned; however,
debris and stagnant water may enter the Deck Well which can be cleaned out
being very careful not to get any water near the sensing unit or electrical conduit.
SENSOR REPLACEMENT
The proximity switch used for the control system is good for thousands of on/off
switching. Typically the sensor should be replaced every three years for year round
usage. Seasonal pools may require replacing every five years or as needed. Replacement
sensors are available from the distributor and factory for all but the surge tank sensing
units which need to be replaced in whole.

ACT 2009
- 11 -
TROUBLESHOOTING
SYMPTOM
POSSIBLE CAUSE
CORRECTIVE ACTION
Plugged into a dead outlet Check outlet power and
switch setting on controller
No power to controller Bad system fuse Replace fuse
Filling light flashing Fill is in delay Normal operation for ELC-
810
Water supply flow is too
low Increase flow
Solenoid not opening Repair/replace valve
Frequent fill time alarm
Exceeded maximum time
on alarm sequence Increase setting
Sensing unit not set
properly Readjust sensor to water
level
Normal operating water
level too low Supply valve to sensor shut
off Turn on valve
Defective sensor Replace sensor
Sensing unit not set
properly Readjust sensor to water
level
Wiring is incorrect in sensor
junction box Check wiring connection
Level light does not come
on
Cable in ELC-810
controller wired improperly Check wiring connection
Sensing unit is dirty Clean sensing unit
Level light continually on Defective sensor Replace sensor
Hammering of water supply Water pressure is too high Install slow close solenoid
valve
Bad system fuse Check voltage on valve:
24 VAC (10 watts max)
Solenoid valve does not
activate Defective solenoid Clean or replace valve or
coil
Wiring is incorrect in ELC
or at contactor Check wiring connection
Feature not turned on Change setting in menu
options
Alternate water level not
sensed at
Flow switch not working Replace flow switch

ACT 2009
- 12 -
SYMPTOM
POSSIBLE CAUSE
CORRECTIVE ACTION
Can’t change settings Forgotten/wrong password Reset ELC by turning the
power on while holding the
left and right arrows

ACT 2009
- 13 -
WARRANTY
AquatiControl Technology (ACT) warrants equipment of its manufacture and
bearing its identification to be free of defects in workmanship and material. ACT’s
liability under this warranty extends for a period of one year from date of delivery from
our factory or authorized distributor. It is limited to repairing or replacing any device or
part which is returned, transportation prepaid, to the factory within one year of delivery to
the original purchaser, and which is proven defective upon examination.
ACT disclaims all liability for damage during transportation, for consequential
damage of any nature, for damage due to handling, installation or improper operation,
and for determining suitability for the use intended by the purchaser.
ACT makes no warranties, expressed or implied, other than those stated above.
No representative has authority to change or modify this warranty in any respect.
This manual suits for next models
5
Table of contents
Other AquatiControl Technology Controllers manuals
Popular Controllers manuals by other brands

Danfoss
Danfoss vlt soft starter mcd 500 operating guide

Softmaster
Softmaster MMP 2 operating instructions

Omron
Omron Sysmac NJ-series Network Connection Guide

Mitsubishi Electric
Mitsubishi Electric XD3500U user manual

Victron energy
Victron energy Isolated SmartSolar MPPT RS 450/100 manual

Emerson
Emerson FISHER T208 Series instruction manual