
These operating instructions include important information which must be observed when setting-up,
commissoning and operating the plant. These operating instructions must be kept readily available
at the place where the plant is employed.
The control may only be connected and maintained by a
suitably qualified specialist.
PPrior to commissioning and turning on the mains it must be ensured that
- the device and the power supply cords are free from visible damage
- in particular the mains connections and the motor connections are connected up properly
- all connections have been performed correctly and expertly
- the laying and conducting of all cables and cords complies with the applicable regulations
- the device is correctly closed
- the plant is expertly fused
The respectively applicable regulations (EN, VDE, ...) And the regulations of the local energy
supplier must be observed.
If a fuse is defective, it must only be replaced with a microfuse of the following type:
microfuse, time-lag, type 3,15 A , 5 x 20 mm in accordance with EN 60127-2/III with a maximum
power loss of 1,5 W. This fuse is also inserted in the factory.
Note:
A stronger fuse can be employed for larger plants (max. 6,3 AT).
Fuses must always be replaced with a fuse of equal strength.
Prior to replacing the fuse, ensure that the device is completely turned off and disconnected from
the electricity supply (unplug).
Ensure device is turned off and disconnected from the
power supply before opening it (Unplug!).
Caution:
- Sensitive components
- Risk internal cabling can become loose
- live parts
5
2 Safety instructions
Always unplug before working on pumps and aerator!