AQUATRIP AT302 Installation instructions

Pg. 1
Model AT302
Installaon and Owners Manual
The installing Plumber and the User MUST read this manual before use, to ensure
they understand the installation, operation, and service requirements of the system.
SECTION PAGE
1. Introducon and how it works…………………………………………………………………………………………….. 2
2. Installaon Preparaon and Warning Precauons ................................................................... 3
3. Commissioning the Control Panel and Control Box before installaon .................................... 4
4. Shuto Valve installaon .......................................................................................................... 5
5. Flow Sensor explanaon and installaon ................................................................................. 6
6. Mounng the Control Box ........................................................................................................ 6
7. The System Check procedure .................................................................................................... 8
8. Control Panel radio range tesng and set up procedures ........................................................ 9
9. The Radio Communicaons System - Operaon and Troubleshoong..................................... 10
10. Emergency Manual Override and Fire ghng procedure ....................................................... 11
11. The Control Panel Reference Guide .......................................................................................... 11
a. The RESET WATER buon ................................................................................................... 12
b. The INFO buon .................................................................................................................. 13
•Informaon Messages ..................................................................................................... 13
•System Warning Messages .............................................................................................. 14
c. The OK MENU buon .......................................................................................................... 15
•Set Up Menu summary .................................................................................................... 15
•Flow Time sengs ........................................................................................................... 16
•Peak Flow Periods ............................................................................................................ 17
•Exclusion Period (Sleep Mode) ........................................................................................ 17
•Turn Water O command ................................................................................................ 18
•The Clock .......................................................................................................................... 18
•The Trip Counter .............................................................................................................. 18
•Nite Watch seng ........................................................................................................... 18
•Away Watch seng ......................................................................................................... 19
•Wetness Sensor set up .................................................................................................... 19
•Radio Range Test ............................................................................................................. 20
d. The OVERRIDE buon ......................................................................................................... 20
e. The HOME AWAY buon .................................................................................................... 21
12. How to test and change the baeries ...................................................................................... 21
13. System Use and Funcon Warnings ......................................................................................... 23
14. System Troubleshoong and Leak Diagnoscs.......................................................................... 24
15. System Service and Maintenance Requirements ..................................................................... 25
16. Water Meter connecon and other oponal accessory funcons ........................................... 25
17. Technical Specicaons............................................................................................................. 26
18. Cercaons and Regulatory ................................................................................................... 26
19. Service Records ......................................................................................................................... 27
20. Customer Handover and Installaon checklist ......................................................................... 28
21. Warranty Policy ......................................................................................................................... 28
Table of Contents

Pg. 2
1. Introducon and how it works
The AquaTrip is a programmable electro-mechanical Water Trip Switch. It monitors water ow into the property and is
able to shut o the water automacally in the event of a leak, a cracked pipe, a tap or faucet le running, a leaky toilet
cistern or some other plumbing failure. It can detect very low water ow, and is more sensive than most water
meters. It consists of a Control Panel wirelessly connected to a Control Box, connected by a cable to a Flow Sensor,
with an integrated Shuto Valve.
The System works by measuring water ow over me, and is equipped with a Flow Sensor linked to a Timer. You must
program the Flow Time seng on the AquaTrip with the longest period of me you think water may ow connuously
on the property (without a break in ow), during normal use. This Flow Time can be set from 1 minute to 3 hours. The
System will shut o the water if it sees connuous water ow for longer than the Flow Time that you have
programmed into it.
For example: If you set the Flow Time to 30 minutes and the water ows connuously for more than 30 minutes, the
System will trip and shut o the water supply.
As long as all water ow stops at some point within the 30 minutes, the Flow Sensor mer is reset. The mer then
restarts from zero when the water ow resumes.
WARNING - Before you operate or program the System, read all the warnings in this manual. If you do not
In order for the System to respond as quickly as possible to a leak, it has mulple modes which allow for variable Flow
Times for dierent mes of the day and or night. These can be manually or automacally acvated if you are going to
be away from home, or used to enhance over night detecon while everyone is asleep.
AquaTrip cannot prevent leaks occurring, but it may alert you to the existence of a leak once the Flow Time has been
exceeded. It is up to you to program these Flow Times to a duraon which will suit your normal water usage. It is best
to start with shorter mes, as the system will then be able to indicate a leak or inadvertent use as quickly as possible
aer it occurs. You can change the Flow Time sengs at any me.
What to do if the water turns OFF ?
To turn the water back on, press the RESET WATER buon on the Control Panel. The water will turn on within 15 to 30
seconds. If the water does NOT turn back on, or the Control Panel does not respond for some reason, you can always
turn the water on manually by pressing the blue Control Buon on the underside of the Control Box for > THREE
seconds, OR, using the Emergency Manual Override procedure explained in Secon 10. If this does not work, check
the local Council mains water supply in your area has not been turned o.
If your AquaTrip turns o the water, the Control Panel will emit a beep and the display will ash every 5 minutes.
(To ensure peaceful sleep, the Panel will not beep between 10pm and 6am).
You must look for any obvious leaks to idenfy the cause of the ‘Trip’ before turning the water back on. If none are
evident, turn the water on and look for a less evident cause.
Blue
Control
Button
Control PanelControl Box
RESET
WATER
Buon
Flow Sensor and Shuto Valve
Rotate for
Emergency
Manual
Override

Pg. 3
2. Installaon Preparaon and Warning Precauons - READ CAREFULLY
This Leak Detecon System must be installed by a licensed plumber according to Local Government
Building, Plumbing and Water Ulity Supply regulaons. Local government approvals may be required.
Before installing the system, determine if any of the following devices are installed on the property:-
1. Irrigaon System 2. Solar Hot Water System 3. Water Soener or Humidier
4. Icemaker 5. Automac Pool Filler 6. Reverse Osmosis Filtraon System
Check for any other appliance that may use water in an automated or sporadic manner. Take into account the water
usage requirements of these appliances when programming the system. Ensure that you program the Flow Time
sengs so that there is no interference to the normal operang requirements of these systems. Alternavely, install
the system downstream of these systems. If you do this, they will not be monitored by the Leak Detecon System.
WARNING Freezing Condions - Do not t the Shuto Valve in an area where it is likely be exposed to freezing
condions. The system will not funcon below freezing. If condions are likely to drop to zero, only
the metal valve version of this product can be installed, and it must be insulated to prevent it freezing.
The PVC valve cannot be installed in zero or sub zero temperatures.
WARNING Pressure Rang - Do a pressure test on the main incoming supply to the property. Check that the
pressure does not exceed the pressure rang of the Shuto Valve version that you are installing. If the
pressure is within 80% of the maximum rated pressure of the valve, then a Pressure Reducon Valve
(PRV) must be ed. This is to allow for surges in pressure in the mains supply which may then exceed
the maximum rated pressure of the Shuto Valve. The valves respecve pressure rangs can be found
under the Technical Specicaons in Secon 17, Pg. 26.
WARNING Pumped Supply - If the water supply to the property is pressurised using a pump, the system may not
be suitable for the applicaon. If the pump has a pressure vessel to maintain a constant pressure in the
pipes, it will work in most circumstances. However if the pump has no pressure vessel the system will
not be able to detect smaller leaks, as the pressure drop from a small leak may be insucient to cause
the pump to come on, and maintain the pressure in the system (See Secon 3 step 5 for Pump Setup).
WARNING Backow Prevenon - If there is backow down the pipe from the house to the Flow Sensor, due to
very long distance piping and/or large diameter piping or undulang terrain or other circumstances
creang reverse ow and pressure, then it may be necessary to install a backow prevenon valve aer
the Shuto Valve. This is because the backow may prevent the Flow Sensor from detecng the
connuous ow caused by a leak. In addion, it may also be necessary to engage the Pump Mode
seng to compensate for the ebb and ow in the pipe (See Secon 3, Pg. 4, step 5 for Pump Setup).
WARNING Hard Water - In hard water areas where calcicaon is a problem with plumbing xtures, this could
inhibit funconality of the system. Therefore the user is advised to increase scheduled servicing and
system check procedures to compensate for this, as required by the severity of the water hardness.
NOTE: If a Water Soener or Humidier is ed, if possible, install the Shuto Valve downstream.
Always install the Shuto Valve and Control Box in a locaon easily accessible for maintenance. There must be a
manual stop cock upstream of its installaon point, so the system can be isolated from the incoming supply.
In installaons using rain water tanks, bore water or water supplied in some rural areas, we would recommend
installing an inline lter (if not already ed) on the incoming main line to minimise debris entering the system.
WARNING Before programming and using the system, read and take account of all the System Use Warnings in
Secon 13, Pg. 23. Make sure you understand the Maintenance and Service Requirements in Secon
15. Be certain that you understand how to override the System in an Emergency, see Secon 10, Pg.11
WARNING Fire Suppression Lines - Do not install the system on any Fire Suppression Supply lines. If a Fire
Suppression system is present, the Shuto Valve must be installed downstream of the supply lines to
that system, so that it has no inuence on the water supply to the Fire Suppression system.

Pg. 4
The Control Panel and Control Box communicate with each other using a radio signal. Before installaon you must
power up both devices in the sequence described below and they will automacally establish the radio link.
STEP 1 - Remove the lid from the Control Box by squeezing the lid lock tabs
and then slide out the circuit board, nong the orientaon of the lid. Get all
the AA baeries ready and only install ONE of them into the baery holder.
STEP 2 - Remove the baery cover from the Control Panel and install the
3xAA baeries, nong their polarity. The message “Add baeries to Control
Box Now” will appear on the Control Panel display. Now insert the remaining
baery into the baery holder on the Control Box circuit board. The Control
Panel will show “Busy searching for Control Box”, and the Control Box LED will
blink GREEN whilst searching. Within about 10 seconds the Control Panel will
beep and display the message “Link to Control Box successful” and the LED will
blink RED once as it links. The two devices are now linked and synchronised.
If for some reason they do not link the rst me and go into a search mode,
remove both sets of baeries, press the buon on the Control Box for 10
seconds and the OK buon on the Control Panel for 10 seconds. This powers
them down properly. Now repeat the process in the same order as in Step 2.
If this fails, refer to Secon 8 on the Radio Communicaons System.
STEP 3 - The display will now say - “Set the Clock - use OK to start”. Press the
OK buon and now set the correct DAY and TIME (if you miss this step, set the
clock later using the OK MENU buon - Pg. 18). You must set the clock before
compleon. If the clock is wrong, system features will not funcon correctly.
STEP 4 - MOST IMPORTANT - Close the Control Box by carefully sliding the
circuit board into the grooves on the inside of the lid. The board will ONLY slide
in all the way when inserted into the CORRECT side of the box. It is
IMPERATIVE that the lid latches click shut and engage properly with the lid, as
any moisture ingress can destroy your device. This is NOT covered under
warranty should it occur!
STEP 5 - Aer installaon, you will need to set up all the Flow Times and Peak
Flow periods and other sengs to suit the users requirements. If you do not
change any of these sengs then the factory default sengs will apply.
SPECIAL NOTE - FOR PRESSURE PUMP WATER SUPPLIES
If you are connecng to a water supply that is supplied by a pressure pump with
NO pressure tank or air tank to maintain the pressure in the line, then you need
to enable PUMP mode.
To do this, remove one baery from the Control Panel, hold down the OK MENU
buon and simultaneously re-insert the baery. Now look at the LCD display.
Two oponal menus will appear consecuvely:-
1. Pump Mode - Use the arrow buons to change to ON then press OK to save
2. Automac Reset - Leave at the default seng of NO and press OK to save
Automac Reset - The Auto Reset funcon only operates when the Exclusion
Period funcon is being ulised. This funcon is designed for public washrooms
or commercial applicaons, and it allows the system to automacally turn the
water back on, if it has tripped. While the Exclusion Period is acve, all water
use is ignored. Outside of the Exclusion Period, if a leak is detected the water
will shut o. However, if Auto Reset is turned ON, when the next Exclusion
Period begins, even if the leak is sll present, the water will automacally be
turned back on again so the facility can be used.
UNDERSIDE VIEW
TOP VIEW
INTERNAL VIEW
3. Commissioning the System BEFORE installaon.
Service
Plug
CONTROL BOX
CONTROL PANEL
LED Display window
Blue Control Buon
Batteries
x5
Mounting
Screws

Pg. 5
The Shuto Valve may be supplied with the Flow Sensor screwed into place.
The Flow Sensor is connected by a cable to the Control Box. The Shuto
Valve may be PVC or Metal depending on the model version. If ng the
PVC valve version try to use PVC ngs. If using metal ngs with PVC
valves, take extra care not to overghten them.
Install the Shuto Valve on the incoming main COLD water line, AFTER the
Mains shut o valve, water meter and re suppression system (if ed). This
allows the system to monitor as much of the property’s plumbing as possible.
Aer installaon is complete, place the Service Plug in its bag for protecon and aach the bag to the Flow Sensor.
Horizontal Pipe Installaons
The Shuto Valve must preferably be mounted horizontally in line on the incoming pipe. This is because the Flow
Sensor must always be upright in a vercal plane. If the installaon is in a horizontal plane, the parts will generally be
arranged as per Diagram A. The system must be installed according to local government plumbing and building
regulaon requirements, and the installer must take into account the plumbing and appliances already at the
installaon, which may have a bearing on the funconality of the system and its interacon with those appliances.
Vercal Pipe Installaons
If the incoming pipe runs vercally, e.g. coming up through the oor from under
the house slab or in the basement, the Shuto Valve may be mounted vercally
in line on that pipe, BUT, if this is the case, you MUST t the oponal Right Angle
Adapter (Part # RA90) see Diagram B alongside, before you screw the Control
Box into the Shuto Valve. (See Secon 5, Pg. 6 of this manual for vercal pipe
installaons.)
External or Below Ground Installaons
If it is necessary to install the Shuto Valve outside or underground, install a suitable ground box or valve box to
protect the system from the elements. Do not leave it exposed out in the open. The Flow Sensor is fully waterproof
and can be immersed in water if required. If it is mounted outside in below zero temperatures, make sure the ground
box is fully insulated to prevent it freezing. The system cannot operate below freezing temperatures and may fail.
WARNING If it is likely that the system may be exposed to zero or sub zero temperatures, you must use the
Metal Shuto Valve only, and it must be insulated to prevent it freezing. DO NOT FIT the PVC Valve
version in an installaon where it may be exposed to freezing temperatures, it may fail.
If mounted underground, make sure the underside of the ground box lid has at least 5cm or 2” clearance above the
TOP of the Flow Sensor, when the lid is replaced on the ground box. This is to prevent damage to the Flow Sensor if
the lid is forced down by some impact to it.
4. Shuto Valve Installaon
SERVICE
PLUG SHUTOFF VALVE
(PVC or Metal)
Mains Shut Water Fire Suppression System PRV Valve AquaTrip Water Flow
O Valve Meter (If ed!) (If ed!) Shuto Valve Direcon
Diagram A Typical Horizontal Installaon format (Example only)
Diagram B
# RA90
Right Angle
Adapter
WARNING The Shuto Valve is direconal and the water ow direcon must match the direcon of
the arrow stamped on the valve, else the system will not funcon. DO NOT install the valve
in Hot Water Lines. The maximum water operang temperature is 50 C or 122 F.
NOTE: Whether the Shuto Valve is mounted horizontally or vercally, the Flow Sensor MUST
ALWAYS sit vercally or the system will NOT funcon.
PRV

Pg. 6
The Flow Sensor may be supplied already screwed into the Shuto Valve. It is designed to be mounted on a horizontal
pipe. The Flow Sensor must always be in a VERTICAL orientaon. If you need to mount the valve on a pipe running
vercally, you will need to unscrew the Flow Sensor and install oponal part # RA90 right angle adapter, into the valve,
and then screw the Flow Sensor into the RA90. Note the Flow Sensor seals via an O Ring. IT IS NOT A COMPRESSION
FITTING SO DO NOT OVERTIGHTEN IT PAST THE POINT WHERE YOU FEEL IT STOP. TAKE GREAT CARE TO NEVER
OVERTIGHTEN THE FLOW SENSOR WHEN SCREWING IT INTO THE VALVE, YOU COULD DAMAGE OF FRACTURE IT.
The Control Box is connected to the Flow Sensor via a 2 metre waterproof cable. This cable can be
extended by a further 6m or more if required (oponal Accessory # CBL-SOL6). Mount the Control Box
securely, in a locaon where the radio signal can best reach the Control Panel located inside the building,
and can also be easily accessed for servicing - See installaon opons below and on the next page.
While the Control Box is waterproof it must always be mounted with the
lid and buon facing downward to minimise the chance of water ingress.
ABOVE GROUND INSTALLATION OPTIONS (The best opon for maximum radio range)
1. Using the supplied cable e, the Control Box can be aached to the pipe work aer the Valve
OR
2. It can be mounted on a nearby fence post with the provided screws or Cable Tie. Take care to protect
or bury the cable running from the Flow Sensor to the Control Box to avoid it being damaged
OR
3. It can be ed to a pole or garden stake pressed into the ground, using the screws or cable e
provided. If using this method, ensure it is not in a locaon where it can be damaged.
BELOW GROUND INSTALLATION OPTIONS (Ensure the Control Box is close to the surface)
1. If the Shuto Valve is mounted underground in a valve box, always try to mount the Control Box to the
wall of the valve box or underside of the lid, using the short screws or cable es provided OR
2. By drilling a hole through a supporng web on the underside of the valve box lid, and cable tying the
box to the underside of the lid.
3. It is preferable to try to get the Control Box out into the open air above ground to maximise the radio
recepon.
5. The Flow Sensor
Water
Flow
Must be
Vertical
SHUTOFF VALVE
(May be PVC or Metal)
# RA90
Right Angle
Adapter
SHUTOFF VALVE
(May be PVC or Metal)
FLOW
SENSOR
Water
Flow
Horizontal Installaon Vercal Installaon
Step 2
Step 1
6. Mounng the Control Box
Must be
Vertical
FLOW
SENSOR
The Flow Sensor seals using an
O-ring, it is not a compression
ng. Never use PTFE tape on
the Flow Sensor or RA90 threads
(if ed).
If the Shuto Valve is mounted
Vercally you must install the
oponal Right Angle Adapter
(Part # RA90) so the Flow Sensor
is sll sing in a vercal plane.
Follow the instrucons supplied
with the RA90.

Pg. 7
Possible Control Box installaon opons
There are many possibilies for the installaon of the Shuto Valve, and the mounng of the Control Box, and this is
very dependent on the layout of the water supply to the property. For maximum eecveness, the Shuto Valve
should be ed as close to the Water Meter or Main Shuto Valve as possible. This way, all of the underground piping
is protected against leaks. The valve can however, be ed anywhere on the incoming water main supply.
Some water mains and their meters are fully underground, and some are raised above ground. Below are some
suggesons as to how the Control Box may be mounted :-
Insert Tie in this direcon
Supplied
Cable Tie
Protect cable run into the ground with Poly Pipe
Control Panel Mounts (55mm) HOLE DRILLING GUIDES Control Box - Between Tube Holes (64mm) Control Box (35mm)
Use the supplied Cable Tie in the following fashion
to mount the Control Box to your chosen locaon.
You may need to slide the mounng bracket onto
the Control box. NOTE: The bracket can slide on
in both direcons. IF you wish to use the Screw
Mount keyholes, make SURE you slide the bracket
on the correct way around! Horizontal
Mount direcon
Installaon to Above Ground
Water Meter, with Control Box
Cable Tied to meter—Thin secon
or thick secon. Water Pump
Cover boxes make a great cover for
your completed AquaTrip and
Water Meter assembly!
Vercal mount
direcon
Installaon to above or below
ground Water Meter, with Control
Box aached to a stake in the
ground. If running the cable
external to a Valve Box, be sure to
pass it through some poly pipe to
prevent Garden Trimmer damage
Installaon within below ground
Valve Box, with Control Box
aached to the internal sidewall of
the box using the supplied screws.
For improved Radio Range, run the
cable external to the Valve Box,
being sure to pass it through some
poly pipe to prevent Garden
Trimmer damage. Example shows
Cable Tying the Control Box to the
fence.
Use the drilling guide on the papers edge to
make it easy to mark your Drill holes.

Pg. 8
Use the BLUE Control Buon on the underside of the Control Box to conduct the following tests:-
If you have turned on a tap, and no water ows inially, reset the system by pressing the BLUE buon for three
seconds. You may hear a click as the Control Box resets the Shuto Valve, and the water will now begin owing.
STEP 1 - Flow Sensor Test
• Turn on a tap so that the water is owing connuously at a slow trickle of at least 40 to 50ml or 1.25 to 1.5oz
per minute, this is when a drip just becomes a constant trickle.
• Press the buon once, the LED will light GREEN to let you know the baeries are OK, then ash BLUE to indicate
it can see the water owing. The Blue LED will connue to display when water is owing, for up to 240 ashes
(or 4 minutes), then stay o to conserve the baeries. If you need to visually check ow again, press the buon
once more.
• If the Flow Sensor cannot see the ow. Check the Flow Sensor is rmly screwed into the Shuto Valve and test
again. If need be, increase the ow slightly, and retest. If ow now registers, then scale the ow back to around
40 to 50ml or 1.25 to 1.5oz per minute, and recheck the Flow Sensor can see the reduced ow.
This Flow Sensor test conrms the Flow Rate that the Flow Sensor can detect. It should see ow down to around 50ml
or 1.5 oz per minute. Due the eect of hysteresis, a slightly larger ow may be required to start the Flow Sensor, but
once it has begun sensing the ow, it will connue to do so, even if it drops down to around 50ml or 1.5oz per minute.
STEP 2 - Water Shuto Test
• Turn on a tap to give a steady stream of water ow. Now press the blue buon for three seconds. The valve will
shut and the water ow will stop. This may take up to a minute as the pressure in the pipes must dissipate. This
test checks that the Shuto Valve is working correctly. The Control Box LED will ash RED briey, every few
seconds to indicate that the water is o!
STEP 3 - Water Reset Test
• Now that the water has shut o, press the Control Buon for three seconds and the water will come on. You
should hear a click as the Control Box signals the Shuto Valve to open and the water begins owing again.
STEP 4 - Leak Detecon Test
Turn the tap on again, press and hold the buon down.
• As long as the Flow Sensor can see the ow, the BLUE LED will ash. Now turn o the tap to stop the water ow.
The BLUE LED will stop ashing as soon as the Flow Sensor can no longer see any ow. This should be within 30
or so seconds of turning o the tap.
• If the BLUE LED display does not stop ashing, it means that the Flow Sensor is sll sensing water owing on the
property somewhere. Check for taps dripping or le running or leaking toilets etc.
STEP 5 - Flow Sensor Funconality Test
If the Flow Sensor connues to detect water ow, and you are certain that there is no water owing anywhere, you
need to test if the Flow Sensor is working correctly, as follows:-
• Turn on a tap to a ow of about 50ml or 1.5oz per minute, then turn o the MAIN incoming tap to the property
and, as you are cung o the main supply, the BLUE LED should stop almost immediately. This conrms that
the Flow Sensor is no longer seeing any ow and is working correctly.
If the BLUE LED connues ashing even aer the main supply is cut, it means the Flow Sensor may be jammed or
damaged and the Flow Sensor may need replacing, or the Shuto Valve itself may need servicing.
With water owing (Flow Sensor IS detecng ow) With NO water owing (Flow Sensor NOT detecng)
Press the Buon
The LED will light up GREEN if the baeries are okay
and RED if they need replacing
IF water is owing, the LED will then ash BLUE
Press the Buon
The LED will light up GREEN if the baeries are okay
and RED if they need replacing
IF NO water is owing the LED will then turn o
7. The System Check Procedure [Five Steps]

Pg. 9
A. Tesng the Radio Range of the Control Panel
A Radio Range Test MUST be carried out to ensure the radio signal will reach the desired Control Panel mounng
locaon, and this is completed as follows:-
1. Trip the Shuto Valve by holding down the blue Control Buon on the Control Box for three seconds unl the
water goes OFF.
2. Now press OK MENU on the Control Panel and scroll through to the Radio Range Test menu, then press OK.
3. The Control Panel will now detect the signal from the Control Box every 15 seconds and indicate the signal
strength as a percentage. Start by standing next to the Shuto Valve for the rst reading (should come up as
100%), then walk towards the desired Control Panel mounng posion, re-tesng as you go, every 10 metres.
4. Aer each reading, press OK again to iniate the next test. (TIP: if you have a wristwatch with a second hand,
take a note of when you get a response. It will ALWAYS respond at exactly the same me every 15 seconds).
Areading of GREATER than 50% is desirable at the chosen Control Panel mounng locaon.
5. Try to locate the Control Panel in a locaon where it is not too far from the Control Box. Note that metal or
concrete walls and mesh metal security/insect screens can act as barriers, prevenng the radio signals from the
two units reaching each other.
6. Ensure that wherever the Control Panel is to be located, that the Control Panel has a constant signal strength in
excess of 50% linking it to the Control Box. Always hang the Control Panel upright on a nail or screw in a locaon
where it can receive the maximum strength signal strength from the Control Box.
NOTE: If the range is insucient, because of excessive distance, or geophysical shielding, you can also relocate
the Control Box. It is on a 2m cable allowing it to be located up and away from the Shuto Valve. The
higher it is located the beer the radio recepon. If necessary, oponal 6m cable extensions are
available to relocate the Control Box to a posion where the signal strength is best.
B. Radio Signal Delay
In order to preserve Baery Life, normal update commands are passed between the Control Panel and the Control Box
at 10 minute intervals.
If a water shuto event has occurred the Control Box will respond to a reset signal from the Control Panel within 15 to
30 seconds. This depends on the me between the leak occurring and the me the Control Panel ‘Reset Water’ buon
is pressed. ( < 40 Minutes, responds in < 15 Secs, aer 40 minutes responds in < 30 Secs. )
C. Radio Signal Strength contribung factors
1. Rain or Water - If there is heavy rain or if the Control Box becomes immersed in water, this can cause a
temporary block to the radio signal travelling between the Control Panel and Control Box. This will show as LINK
SCAN or LINK BAD on the Control Panel display. Once the weather clears or the Control Box is no longer
submerged, the two units will re-establish the connecon.
2. Below Ground Installaons - If the Control Box is mounted below ground level, this can reduce the ability of the
Radio Signal to get out into the environment to be received by the Control Panel. If this is the cause of the
Control Panel having diculty maintaining a signal strength in excess of 50%, then a soluon can be to relocate
the Control Box to be above ground and mount it on a nearby fence or garden stake or pole in the ground.
3. Distance and Barriers - if the Control Box and Control Panel are installed too far apart or with barriers between
them which can block the radio signal, this will have an impact on radio signal strength and connecvity. By
conducng the procedures outlined in Secon 8 Part A and Part C.2 above, it is possible to minimise their
impact.
For more details on how the Radio Communicaons system works, and for further advice on the operaon and trouble
shoong of the Radio Link system, please refer to Secon 9, Pg. 10.
8. Control Panel Radio Range Tesng - Setup and Tips

Pg. 10
The system uses a coded Radio Signal to communicate and create a wireless link between the Control Panel and the
Control Box. Once linked together, they only communicate every ten minutes, except if the water has been turned o,
then they communicate every 15 or 30 seconds. So if you issue a command by changing a seng, that command will
only take eect at the next ten minute update between the two devices.
During installaon, if you have trouble linking the Control Panel to the Control Box as described in Secon 4 Step 1. or,
if the Control Panel loses the link with the Control Box aer installaon at some point, you can link the two devices by
using one of the following two methods:-
A. Manual Radio Link Procedure
The Control Box must be tripped to put it into Search mode, so it will be looking for the Control Panel signal. Trip the
valve by holding down the blue buon on the Control Box for three seconds (unl the LED lights RED). Once you hear
the valve shut, press the RESET WATER buon on the Control Panel. The Panel may inially not respond, but will enter
search mode. Within about two minutes, it will have located the Control Box and the radio link will be established.
B. Automac Radio Link Procedure Opon
If the Control Panel and Control are in range of each other, they will automacally link up aer about 90 minutes.
If the Control Panel loses the radio link with the Control Box
The Control Panel will begin to scan and search for the Control Box signal. This will show up as Link Searching on the
display. Aer a few hours of trying the display will change to Link BAD with a number to denote the number of mes
the Panel has tried to relink with the Valve. At 100 aempts it will stop counng, but connue searching for the
Control Box. This will connue unl the Control Box is found. This searching will run down the baery more quickly.
So if you noce the display says - Link BAD - follow one of the procedures below.
To x this, you must rst try to re-establish the radio link. There are three oponal ways to do this:-
• You can either follow Step 2 in Secon 3, Pg.4 OR
• Complete the Manual Link Procedure listed earlier in this secon, OR
• Place the Control Panel near to the Control Box, and let the Automac Radio Link Procedure take place.
Once you have re-established the Radio Link, perform a Radio Range Test to nd the strongest signal locaon. Refer to
Secon 8, page 9 or Secon 11c, Pg. 20 in this manual for instrucons on how to conduct a Radio Range Test. A signal
strength above 50% is best for reliable operaon.
If necessary, it is possible to add one or more 6m extensions to extend the cable connecng the Control Box to the
Flow Sensor. This allows you to relocate the Control Box to a posion where it can beer receive and send signals to
and from the Control Panel.
NOTE: If you cannot re-establish the radio link, there may be a problem with the radio in either the Control Panel
or Control Box, so both will need to be serviced or replaced.
Replacing the baeries
At some point, the system will require its baeries to be replaced. You will be prompted to do this by the Control
Panel, however we recommend you do it every 12 months as a safety precauon in any event. Aer the new baeries
are installed, the Control Panel and Control Box will link up automacally again within 90 minutes. Do not forget to set
the clock again aer you have replaced the Control Panel baeries.
WARNING: Once again, it is absolutely imperave that you clip the lid shut PROPERLY on your Control Box.
Failure to do this will likely cause water damage. Make SURE you slide the PCB into the
grooves on the inside of the box, as if forced, it is possible to close the lid with the PCB not
properly in the grooves. This will allow water in!!!
9. The Radio Communicaons System - Operaon and Troubleshoong

Pg. 11
The system has an Emergency Manual Override facility, ensuring that you can always disengage the system in an
Emergency, and that you will have unrestricted access to water. The Emergency Manual Override is used when you
need to use water nonstop for an extended period, e.g. FIRE FIGHTING, or in the event of a system malfuncon. You
can also use the Emergency Override if the baeries go at and you do not have replacements handy.
1. To place the system in Emergency Manual Override, rotate the Flow
Sensor HALF a turn an-clockwise.
2. To cancel Emergency Manual Override, gently rotate the Flow
Sensor clockwise unl it just sens, but DO NOT OVERTIGHTEN IT!
IT IS NOT A COMPRESSION FITTING, IT SEALS USING AN O-RING. IF
OVER TIGHTENED IT CAN BE DAMAGED OR FRACTURE.
3. If you have re-engaged the Flow Sensor aer using the Manual
Override facility, you MUST ALWAYS conrm that the system is
funconing correctly by running the System Check Procedure as
covered in Secon 7 of this manual.
The Control Panel has seven buons which can be used to control most of the funcons and sengs of the system. In
the unlikely event that your Control Panel should malfuncon, you can sll control the system from the Control Box
itself. See Secon 7, Pg. 8 for System Tesng and the secon above for the Emergency Override funcon.
WARNING When the system is in Emergency Manual Override, it
cannot shut o the water in the event of a leak. DO NOT
leave the system in this mode unnecessarily, as there will
be no leak detecon capability.
10. Emergency Manual Override and Fire Fighng Procedure
Rotate Flow Sensor ONLY HALF a turn
an-clockwise to override the system
11. The Control Panel
RESET WATER buon
OK MENU buon, also
referred to as the OK buon
OVERRIDE Buon
Baery Cover
(on back of Control Panel)
Informaon Display
INFO buon
UP and DOWN Arrows
HOME AWAY buon
Internal Warning Beeper
( inside the housing )
NOTE: WARNING BEEP - The Control Panel will emit a short beep every ve minutes if there are any warning
messages. Press the INFO buon to read the message. This will also silence the beep. For peaceful sleep,
the Control Panel will not issue any warning beeps between 10pm and 6am.
Radio Signal Strength Indicator Temperature Display
Internal (IN) and External (OUT)
Day and Time Display
Radio Link Status Indicator

Pg. 12
The RESET WATER buon is used to turn the water back on aer the system has turned the
water o. Press the buon once to turn the water on. The water will turn on within a 15 to 30
second period. If you press this buon again for more than three seconds, it will cancel your
original command.
If the system shuts o the water it means that it has detected water owing connuously for longer than the Flow
Time programmed in to it, for that parcular me of the day. Aer the water has shut o, the Control Panel will emit a
short beep every ve minutes to let you know the water is o.
If you ever hear a beep from the Control Panel, always press the INFO buon to nd out what message is waing for
you on the display. If the water has gone o, the Control Panel will start to beep within 10 minutes of the water being
o. When you press the INFO buon the following message will display.
When you see this message, press the RESET WATER buon. Refer to the ow chart to
show you the possible messages displays which may occur when you press the RESET
WATER buon
If the Control Panel loses its radio signal connecon with the Control Box, the Control Box will not be able to respond
and will not be able to turn the water back on, and an error message will appear on the Display. The Control Panel will
automacally try to turn the water back on again. If the retry fails, you must turn the water back on manually by
pressing the blue buon on the underside of the Control Box. See illustraon below.
When you press the RESET WATER buon, the following displays will appear.
If the water does not turn on, you can turn the water on manually by holding down the blue Control Buon on the
Control Box for 3 seconds - this will open the Shuto Valve. If that should also fail to turn the water back on, you can
manually override the system by turning the Flow Sensor half a turn an-clockwise, this will open the Shuto Valve and
allow water to ow. See Secon 10, Pg. 11 for how complete the Emergency Manual Override procedure.
Water OFF! Reset
and look for cause
RESET
11.a The RESET WATER buon
Your water has
been turned ON It went off on
Th 13:21
Radio, Battery or
other error
See Manual or
www.aquatrip.com Use Control Button on
Control Box
Turning water ON
wait 12 seconds
Retrying - Wait!
Unable to reset
water may be on
Blue Control Button
OR
OR
Control Box found near
Shutoff valve

Pg. 13
The INFO buon displays the general system status and warning messages. If there are
any warning messages or if you have acvated any special features these will be shown
rst. These will be followed by standard system messages telling you key informaon on
the status of various aspects of the system.
INFO Buon - Informaon Message Displays
When you press the INFO buon, the display will scroll through the following menus to inform you of the status of key
aspects of the system:-
This display shows the strength of the Radio Signal Link between the Control Panel and
Control Box, and the day, me and indoor and outdoor temperatures. If the radio signal
link is lost between the Control Panel and the Control Box, the Control Panel will begin to
search for the Control Box. This will show up as Link Searching on the display. If aer
repeated failed aempts to nd the Control Box, the display will change to Link BAD.
OR
NOTE: If this occurs, to resolve the issue, refer to Secon 9, Pg. 10 - The Radio Communicaons System.
Aer the Radio Signal Link & general status display, the display will scroll through the following menus:-
This shows what the Flow Time is currently set for, at this exact moment in me. As the
me of day changes and dierent Flow Time sengs come into eect, the current Flow
Time seng for that exact me of day, will display on this menu. If currently Overridden
or Excluded, this status will also be shown here.
This is the longest connuous ow of water this week. The gure clears every Sunday at
midnight, so the me shown will be your longest connuous water ow since last Sunday
at midnight.
This is the last day and me that the System detected connuous ow which exceeded
the programmed Flow Time and caused the system to shut o the water.
This is the number of “Trip” events that the system has recorded since the counter was
last reset. You can reset the counter from the Trip Count menu within the SETUP menu,
which you access using the OK MENU buon.
This screen shows the capacity of the baeries in the Control Panel. The Panel will start
to beep when the baeries get low. We suggest replacement when they fall below 50%.
Use 3 x AA Alkaline or Lithium baeries.
This screen shows the capacity of the baeries in the Control Box. The Panel will start to
beep when the baeries in the Control Box get low. To prevent damage, we suggest
replacement annually or when they fall below 50%. Use 2 x AA Alkaline or Lithium ones.
This screen shows whether the Nite Watch and Away Watch funcons are turned ON or
OFF. Refer to the OK MENU buon secon for an explanaon of these features and how
to turn them on or o.
Link BAD 99
Tu 17:54 21C IN
11.b The INFO buon
Link Searching
Tu 17:54 21C IN
INFO
Link OK 25C OUT
Tu 17:54 21C IN
Control Box
Batteries 100%
Longest Flow
this week 19 mins
NITE WATCH = ON
AWAY WATCH = OFF
Trip Count = 13
Control Panel
Batteries 100%
Last Trip Time
We 08:35
FLOW TIME right
now is XX min

Pg. 14
When you press the INFO buon, in addion to the Informaon Messages that are displayed and were explained on
the previous page, any System Warning messages will also be shown. Warnings are always shown rst. Here are some
of the Warning messages that could display, and an explanaon of them:-
INFO Buon - System Warning Message Displays
This message will display if the water has been shut o for any reason. The Control Panel
will also beep every ve minutes, aer the next update has been received from the
Control Box (within ten minutes). Press the RESET WATER buon to turn the water back
on and nd out why it was shut o.
This message advises you that the Control Panel and the Control Box can no longer
communicate with each other. Please refer to Secon 9, Pg. 10 that deals with the Radio
Communicaons system.
If you have set the Exclusion Period (Sleep Mode) to allow use of an irrigaon system or
for some other purpose, this menu will appear to remind you that it is set and show a
summary of the current seng.
This message advises you that the baeries in the Control Panel are LOW and need
replacing. See Secon 12, Pg. 22 on how to replace the baeries.
This message advises you that the baeries in the Control Box which controls the Flow
Sensor and Shuto Valve, are FLAT and need replacing. See Secon 12, Pg. 22 on how to
replace the baeries.
This message is to remind you that the system has been overridden and is now inacve
unl Saturday at 14:45pm (as an example). This is the result of pressing the Override
buon, which will disengage the system for whatever override me period you have set.
There is no leak detecon during this me period. See Secon 11d, Pg. 20 on the
OVERRIDE buon for a more detailed explanaon.
This indicates that the system is in AWAY mode, and it will display the Flow Time you have
chosen for when the system is in Away mode. However, if an Exclusion Period has been
set, the water sll ows normally during the excluded me(s). This will allow irrigaon or
other water consumpon to happen while you are away.
This menu appears when the manual Turn Water OFF funcon has been acvated. This
funcon is accessed from the system menu, by using the OK MENU buon. The display
tells you how long it will be before the water turns o.
This will be followed by a second screen when the water actually turns o, which tells you
that the water was turned o by the user and not a leak or over-use. This could be for
plumbing maintenance or some other reason.
Exclusion Period
M-W-F-S 17-19hrs
Water OFF! Reset
& look for cause
Radio Link Error
(See Manual)
Control Panel
Batteries LOW!
No flow detected in
past 24 hours
System may need
to be serviced
VERY IMPORTANT MESSAGE
This message is an alert that the Flow Sensor has not seen any ow for more than 24 hrs and this
may indicate a potenal system problem. One of the following three condions may apply:-
1. The most common reason for this message is you have actually not used any water for
more than 24 hours. In this case, the system is sll funconing normally. However, if this
is not the case, there may be a denite problem with the Flow Sensor and the procedure
described in (3) below must be followed.
2. The system has been manually overridden and is no longer sensing water ow, so will no
longer funcon as a Leak Detector (the MOST important reason for this message).
3. The Flow Sensor or Shuto Valve has developed a problem and needs to be checked.
Please conduct the System Check Procedure and if the system fails those tests, contact
your distributor. You may also engage your plumber to check the system’s funconality
for you.
System INACTIVE until
Sa 14.45
AWAY mode is set
Flow Time 3 mins
Water turned OFF
by the user
Water will turn
OFF in 5 mins
Control Box Bats
FLAT Replace NOW
Conduct System
Check Procedure

Pg. 15
The OK MENU buon is used to access all the SETUP menus for adjusng the various
programmable features of the system. Use the UP and DOWN arrows to scroll though the
menus available.
NOTE: The menu explanaons are arranged in the order you will nd them if you use the UP arrow to scroll
through the menus. If you use the DOWN arrow they will appear in reverse order.
OK MENU Buon Summary - Menu Display Order (if scrolling using the UP arrow)
From this menu you can scroll up and down the menus to access the various sengs and
funcons. Follow the instrucons on the screen within each menu to access and change
the sengs (prompts appear aer a delay).
The FLOW TIME menu is where you set the length of me water can ow connuously
before the system shuts o the water. See the FLOW TIME sengs menu on the following
pages.
You can choose two dierent me periods of the day when you expect to use water for
the longest me. Generally this would be in the morning (say 6am to 8am) and then
again in the evening, (say 6pm to 10pm). You can set them to whatever suits your water
usage. You set the start hour and the nish hour of each me period.
The EXCLUSION PERIOD menu is where you program the system to ignore water ow for
certain periods of me on certain days, like pung the system to into a sleep mode. See
the EXCLUSION PERIOD sengs menu on the following pages.
The CLOCK is set from this menu. It is important that the clock is set correctly, as the
whole system relies on the clock to co-ordinate all the ming of the other leak detecon
sengs. See the CLOCK seng menu on the following pages.
The TURN WATER OFF menu is where you can use the Control Panel to close the Shuto
valve and turn o the water supply directly. See the TURN WATER OFF menu funcon on
the following pages.
The TRIP COUNT logs how many mes the System detected ow which was long enough
to cause the system to “trip” and shut o the water. See the TRIP COUNT menu funcon
on the following pages.
The NITE WATCH is a selectable feature which puts the System into the Night Watch Flow
me for night me period that you have selected. This oers extra protecon if a leak
occurs overnight. See the NITE WATCH menu seng on the following pages.
The AWAY WATCH is a selectable feature which automacally puts the System into Away
mode, if the system sees no ow for a 24 hour period starng at midnight. See the AWAY
WATCH menu seng on the following pages.
The WATER FLOW check menu allows you to see on the Control Panel if water is actually
owing at that exact moment in me, and allows idencaon of leaks if present. See
the WATER FLOW CHECK menu seng on the following pages on how to use this feature.
This reminds the user of the most important items that will need service and aenon
over the life of the system. See the System Service and Maintenance secon of this
manual for full details of the maintenance requirements of the system.
The WETNESS SENSING menu is where you link any of the oponal Wetness Sensors to
the Control Panel. If these sensors detect wetness in their immediate locaon, they will
signal the Control Box to shuto the water, within one minute. See the WETNESS
SENSING setup menu on the following pages.
The RADIO RANGE TEST menu is where you can test to check that the radio signal link
between the Control Panel and the Control Box is good enough for reliable
communicaon. See the RADIO RANGE TEST setup menu on the following pages.
WATER FLOW TIMES
Use OK to change
EXCLUSION PERIOD
Use OK to change
SETUP MENU - use
Arrows to select
OK
MENU
11.c The OK MENU buon
TRIP COUNT = 12
Use OK to clear
Turn water OFF!
Use OK to begin
NITE WATCH = OFF
Use OK to change
CLOCK - Sa 20:14
Use OK to change
AWAY WATCH = OFF
Use OK to change
WETNESS SENSING
Hold OK to setup
PEAK FLO PERIODS
Use OK to change
WATER FLOW CHECK
Use OK to begin
SERVICE SCHEDULE
Use OK to view
RADIO RANGE TEST
Use OK to begin

Pg. 16
All seng changes which are set from the Control Panel, will be sent by coded radio signal to the Control Box. In order
to conserve baery power, these commands are only sent every ten minutes, when the two devices exchange
informaon. Aer you change any seng and the command is sent from the Control Panel, the message screen below
will nearly always appear. It will tell you how long it will be before the new sengs take eect.
It is important to set the shortest possible Flow Time that suits your normal water use. This Flow Time can vary
according to the dierent mes of the day or night, when you are likely to be using more or less water. This menu is
used to set up those ow mes. You can change these sengs at any me. In order to make the System more
responsive, there are two sengs available: -
1. Peak Use Flow Time - The Peak Use Flow Time period is when the property is likely to be fully occupied and
connuous water usage is likely to be higher. Select the maximum connuous water Flow Time you would like for
those mes when your water use is at its peak. Default is 25 min’s.
2. Standard Use Flow Time - Within this seng you select the maximum Flow Time for all mes outside the Peak
Flow Time period, i.e., the rest of the day or night. This is generally the me when the house is less likely to be
occupied and connuous water usage will probably be lower. This allows you to (usually) set a shorter Flow Time
for the standard or o peak period. Default is 25 min’s.
3. Away Mode Flow Time - This is the amount of me that you want water to be able to ow while the system is in
Away mode. Set this ow me to be as short as possible, taking into account any appliances you have which may
need water ow while you are away e.g. Ice Makers, Solar Water Heaters etc. Default is 3 min’s.
4. Night Mode Flow Time - This is the length of me that water can ow during the me you think you will be
asleep or overnight, when the system is in Night Mode. Default is 3 min’s.
5. Early Warning Pause Timer - So you can never be caught out by the water turning o when you do not expect it,
e.g. being caught in the shower without water, there is an early warning funcon. Three minutes before you
reach the maximum Flow Time seng, the system will pause the water ow for 1 to 15 seconds (programmable),
then reinstate the ow. If you turn o the water, wait 10 seconds or so, and turn it on again, you can restart the
Flow Timer (Don’t tell the kids!) You must set the Pause Timer length in this menu. If your house has long pipe
runs, choose a longer Pause Time, as it takes me for the loss of ow to be noced. The default seng is OFF.
Refer to the Warnings in Secon 2, Pg. 3 and Secon 13, Pg.23 before acvang this feature.
Change will be
active in 7 mins
ADJUSTING THE SETTINGS USING THE SETUP MENU
In this case, the new seng that you have
entered will take eect in seven minutes.
WATER FLOW TIME - SETTING
Std Flow 25 min
Peak Flow 25 min
Past water usage
suggests XX min Set Peak Use
Flow Time XX min
WATER FLOW TIMES
Use OK to change
Set Away Mode
Flow Time XX min
Set Night Mode
Flow Time XX min
If you do NOT press OK on this rst menu,
the current Flow Time sengs will display.
If you press OK on this rst menu, the setup menus for the four Flow Time sengs will show as below.
If the system has been in use for some me, it will make a suggeson. This will be your historic longest
Flow Time plus ve minutes. Set it to suit your usage requirements during each mode.
Use the arrow buons to change the me in each menu and then press OK to save that me seng.
Set Standard Use
Flow Time XX min
Warning Pause
Length XX sec
For the rest of the manual, this symbol denotes the ashing value being changed.

Pg. 17
This funcon allows you to set up TWO dierent periods within the 24 hour cycle, to be designated as PEAK periods
(where you would like a usually LONGER, but can be SHORTER ow me). The Peak Flow me seng will apply during
these hours chosen. If you do NOT wish to use these PEAK FLOW periods, simply make the PEAK use and STANDARD
use ow mes in the WATER FLOW TIMES menu to be equal to one another. NOTE: 24 hour clock format.
This funcon allows you to exclude a certain period of the day and/or days of the week from your system’s detecon
schedule. It puts the system into a Sleep Mode while the Exclusion Period is acve and the system will ignore all water
ow during this me period. It is designed to allow much longer Flow Times for certain designated periods, e.g. for
garden irrigaon or some other automated water usage requirements.
It is also useful for Commercial and Public Washrooms, where the system can be set to ignore all water use during
business hours and only operate aer hours. This seng, in combinaon with the Automac Reset Funcon, allows
the system to potenally reduce water waste and improve maintenance schedules by controlling leaks and plumbing
failures while sll allowing uninterrupted normal use of the facility.
The factory default seng is OFF. If you have previously set an Exclusion Period and then want to turn it o, set the
Start Time and Finish Time both to the same hour. The Exclusion Period funcon will now be turned o.
PEAK FLOW PERIODS - SETTING
The Start hour will ash. Enter the hour you want the Exclusion Period to start. Use the
arrow buons to adjust, then press OK to save the value. It is only possible to set whole
hours, not minutes. NOTE: 24 hour clock format.
The Finish hour will ash next. Enter the hour you want the Exclusion Period to end. Use
the arrow buons to adjust and then press OK to save the value. Again, only whole
hours may be set.
Set the days you would like the Exclusion Period to apply to. The menu which allows the
day sengs to be changed appears next.
Starng from Monday, each day will appear in sequence. Use the arrows to toggle
between Yes or No for each day (its leer will become a — ), then press OK to store the
seng for that day. Pressing OK, moves on to the seng for the next day.
The nal screen displays the saved sengs. In this example, the System will ignore all
water ow between the hours of 8am ll 10am on Monday, Wednesday, Friday and
Sunday. This seng will also appear in the INFO menu display.
Exclusion Period
Use OK to change
Set START Hour
08:00 - 00:00
Exclusion Period
M-W-F-S 08 - 10Hrs
Exclude MON NO
M-W-F-S
Set END Hour
08:00 - 10:00
Choose Days to
Exclude MTWTFSS
Exclusion Period
<None Set> If you do not press OK to change the sengs, the current
seng will appear. In this example no Exclusion Period is set.
EXCLUSION PERIOD - SETTING (Sleep Mode)
Press OK to begin, and the START hour of the FIRST period
will ash. Use the arrow buons to adjust, then press OK to
save the value. It is only possible to set whole hours.
The END hour will ash next. Enter the hour you want the
Peak Period to end. As before, use the arrow buons to
adjust and then press OK to save.
In the same manner as before, you may now set the START
and END hour for the SECOND Peak Flow Period.
The nal screen will advise when the change acvates.
NOTE: If you only want ONE Peak Flow Period, set the 2nd
one the same as or within the mes of the 1st one.
PEAK FLO PERIODS
Use OK to change
Set 1st PEAK FLO
PERIOD to apply
Change will be
active in XX minutes
Set 2nd PEAK FLO
PERIOD to apply
Set START Hour
18
1st PEAK 05 - 07
2nd PEAK 18 - 21
If you do not press OK to change the sengs, the current
seng will appear. In this example, the rst peak period is
5am to 7am and the second peak period is 6pm to 9pm.
Set START Hour
05
Set END Hour
05 - 07
Set END Hour
18 - 21

Pg. 18
The Clock MUST be set to the correct Day and Time for all the other me based funcons of the system to work
correctly. The system does not log the actual date, only the days of the week and the me.
NOTE: The clock is in the 24 hour format.
NITE WATCH is a special feature which, if enabled, gives a faster leak detecon response me for the overnight period.
If you enable the NITE WATCH feature, whatever me you have set it to nish will apply, and whatever Flow Time you
have chosen will apply. The start me is xed at 11 pm (23) and only the End Time can be set, from midnight (00) to
7am. The ashing digit represents whole hours.
If you exceed your Nite Watch Flow Time during the mes it applies, it will shut o the water. When you reset the
water and turn it back on, the system will know you are awake and need extended ow, so will cancel the Nite Watch
mode for that night only. The following night it will re-engage as programmed.
The factory default seng is OFF. Press the OK buon to turn this feature ON or OFF.
This menu allows you to manually turn the water o from the Control Panel. Once you acvate this command, the
water will only turn o, aer the next data update, which will be within the next ten minutes.
Turn the water on again using the RESET WATER buon and then the OK MENU Buon. This double conrmaon
reduces the risk of accidental reseng of the water. Inform all occupants of the property, that if the water has been
turned o using this funcon, there may be plumbing work taking place on the property!
TURN WATER OFF - COMMAND
To cancel this command, re-enter the same
menu, then press the OK buon when prompted.
Turn Water OFF
Use OK to begin Water will turn OFF
in 8 minutes
THE CLOCK - SETUP [IMPORTANT]
CLOCK - Su 10:16
Use OK to change Set Day
We 10:16 Set Hrs
We 10:16 Set Mins
We 10:16
Use the arrow buons to change the sengs (ashing item) and then press OK to advance and save the seng.
TRIP COUNTER - INFORMATION
NITE WATCH - SETTING
NITE WATCH = ON
Use OK to change
TRIP COUNT = 12
Use OK to clear
The Trip Counter logs each me the system trips and shuts o the water in response to
any of the Flow Times being exceeded. It will not count the mes you have used the
‘Manual Water O’ command.
You can reset the counter back to zero by pressing the OK buon while in the menu.
NITE WATCH = OFF
Use OK to change
NITE WATCH = ON
3 Min Flow 23 - 07

Pg. 19
AWAY WATCH - SETTING
The AWAY WATCH funcon is designed to help those users who may forget to acvate the AWAY mode when they leave
the property unaended for an extended me. Away Watch does it automacally for you. It works as follows:-
The Away Watch funcon looks to see if there has been any water ow in a 24 hour period. If there was no ow during
that me, it presumes you are not home and will automacally acvate AWAY mode, and only allows the Flow Time you
have set for Away mode. This speeds up the response me of the system to any leak that may occur while you are away.
When you return home, if the AWAY mode has been automacally engaged, press the Home/Away buon to cancel.
The factory default seng is OFF, so you must consciously turn this feature ON if you want to use it.
WARNING: Refer to the Warnings in Secon 2, Pg. 3 and Secon 13, Pg. 23 before seng this funcon.
NOTE: If possible, subject to local condions, set the system to AWAY mode whenever you leave the property
unaended (see HOME AWAY buon Secon). However, it is also a good idea to keep this automated
AWAY funcon enabled, as if you do forget to manually turn AWAY mode on, you know that within 48 hours
at most, this mode will automacally engage.
AWAY WATCH = ON
Use OK to change
AWAY WATCH = OFF
Use OK to change
As oponal extras in some markets, there are Wireless Wetness Sensors available which can be wirelessly linked with
your Control Panel. The Sensors can sit in areas which have the highest risk of leaks or have a pipe burst, such as water
dispensers, washing machines, dishwashers or water heaters. If the Sensors detect a water leak they will send a coded
radio signal to the Control Box and it will shut o the water within one minute of the leak occurring (provided the
water is CURRENTLY owing). Order model # WS-1
You can add as many Sensors to the Control Panel as you like. You must pair each Sensor with the Control Panel in
order for it to be able to communicate with the Control Box and Shuto Valve. The Sensors are powered by long life
baeries, and will begin beeping when their baeries need replacing.
You will not need to use this menu unless you want to add new Sensors to the system. We suggest you ask your
plumber to do this as part of the inial installaon and setup, alternavely you can purchase the Sensors aerwards
and easily add them to your system.
Link up to
Sensor Successful
Wetness Sensing
Hold OK to set up Searching for
Wetness Sensor
WETNESS SENSORS - SETUP (Oponal extra accessory)
Add Batteries to
Wetness Sensor
If you add Wetness Sensors to your system, link them to the System by following the instrucons included with the
Wetness Sensors. The menus which will appear on the Control Panel for this process will be as shown above.
Do not hold OK on this menu unless you intend adding a Wetness Sensor.

Pg. 20
This menu allows the user to test how strong the Radio Signal link is between the Control Panel and the Control Box. It
is used to nd the best locaon for your Control Panel, and to ensure it receives the best strength signal from the
Control Box and vice versa. We recommend mounng your Control Panel near your most used entry/exit point to your
property, for easy system access, as long as the signal strength is sucient at that mounng point.
To use the Range Test feature, the system must be in the tripped condion, i.e. the water has shut o. In this state,
the Control Box is searching for the Control Panel reset signal every 15 seconds. To trip the Shuto Valve, the quickest
way is to hold down the buon on the Control Box for three seconds (unl LED ashes RED), please refer to Step 2 of
the System Check procedure on page 8 if you are uncertain how to do this.
Once the Valve has shut o the water, the test can begin. Start by standing next to the Control Box and the signal
should be 100%. Now, slowly move away, tesng the system say every 10 metres or so. Once you get to your preferred
Control Panel locaon, make sure you have a minimum signal strength of at least 40%. The menus will display as
follows: -
RADIO RANGE TEST
Radio Range Test
System must be
tripped to test Radio Range Test
Use OK to begin
Control Valve
Signal is 89% Testing Range
wait 12 seconds
If you need to repeat the test,
press the OK button again,
after each result, in order to
quickly initiate the next test
and stay in test mode.
Press OK buon
The OVERRIDE mode cancels all the Flow Time sengs for an adjustable period. When you enter
this mode the hour number will ash, use the UP/DOWN arrows to set the amount of me in hours
that you want the system to be overridden for. Then press the OK buon to save the seng. While
the system is in Override mode, water can ow connuously without interrupon. Once the
Override period is over, normal Flow Times will apply. Remember to allow for up to a 10 minute
delay for the command to take eect.
Override Buon Message Displays
11.d - The OVERRIDE buon
NOTE: If you need to override the system for much longer than fourteen hours, say for a few days:-
For example: you are having construcon done on your property, or you are re ghng or for some other
reason you need constant ow for a very long period, you can manually override the system. See Secon 10.
Do NOT forget to re-engage the system aerwards.
Do NOT use this Override for Fire Fighng.
Use the Emergency Manual Override
funcon explained in Secon 9.
System INACTIVE
for next XX hours Command sent to
Valve in 6 minutes
System ACTIVE Command sent to
Valve in 2 minutes
OVER
RIDE
Table of contents
Popular Switch manuals by other brands

Avocent
Avocent DSR Series DSR1020 Specifications

Texas Instruments
Texas Instruments TPS20 EVM-293 Series user guide

Factor Electronics
Factor Electronics HD100BaseT-In-Wall-Balun manual

Belkin
Belkin OmniView F1D104-USB user guide

COMPRION
COMPRION TraceCase operating instructions

Cisco
Cisco Catalyst 3650 Series Guide

Huawei
Huawei CloudEngine 16816 Quick installation guide

NETGEAR
NETGEAR GS724TS - ProSafe 24 Port Gigabit Stackable Smart... datasheet

Comprehensive
Comprehensive CSW-HDBT300M Operation manual

Festo
Festo VPEV-1/8-M12 operating instructions

Versitron
Versitron SGX368244M user manual

Dell EMC
Dell EMC Z9264F-ON Setup guide