Page 8
The navigation keys allow selecting the menus:
To enter the mode programming: validate the choice « CODE » in the menu « PROGRAM », and enter the code
111.
5. CONFIGURATION OF THE MEASURES (MENU « INPUTS »)
5.1. Choice of the measure network « NETWRK », « TYPE »
SINGLE Single phase
3W BAL 3-phase balanced without neutral
4W BAL 3-phase balanced with neutral
If a mesh voltage is connected on the instrument, programme the network 3W BAL.
If a single voltage is connected on the instrument, connect the network 4W BAL.
5.2. Choice of the ranges « RANGE »
Voltage range « RANG U »
173V 173VL-N(4W BAL or 1PH) 173VL-L(3W BAL)
600V 600VL-N(4W BAL or 1PH) 600VL-L(3W BAL)
Current range « RANG I »
1A 1A
5A 5A
5.3. Entering of the CT/VT ratios « CT VT »
PRI VT / SEC VT
0230 . Programming of the VT primary and its unit (V or kV)
V Programming of the VT secondary, without unit
(Do not programme a ratio but the real values)
PRI CT / SEC CT
0005 . Programming of the CT primary and its unit (A or kA)
A Programming of the CT secondary, without unit
(Do not programme a ratio but the real values)
PROGRAM Modification of the language, entering in mode programming.
INPUTS Configuration of the measure inputs.
RS-485
OUTPUTS
Configuration of the digital data link RS485 (if option present)
Validate to enter the chosen menu.
Configuration of the instrument outputs (relay, analog).
programme the VT ratios in single voltage (if you
have 15kV/100V VTs between lines, programme 8.33kV / 57.7V
for the ratios)