ARDETEM TAI60 Instruction Manual

®
ARDETEM Route de Brindas
Parc d’Activités d’Arbora
69510 SOUCIEU EN JARREST
France tel : 04 72 31 31 30
fax : 04 72 31 31 31
International tel : 33 4 72 31 31 30
fax : 33 4 72 31 31 31
www.ardetem.com e-mail : info@ardetem.com
TAI60
User handbook
AC transmitter
Measurement of alternating voltage and
current
For balanced networks
True RMS values
ARDETEM – TA CO102 V2. x A 02/15 – Any data in this documentation may be modified without prior notice.

Summary
Page 1
USE 2
1. RECEIPT OF THE INSTRUMENT & START UP 3
2. ORGANISATION OF THE FRONT FACE 3
3. LIST OF THE MEASURED PARAMETERS 4
4. USE OF THE « CUT OFF » 5
5. LIST OF THE ERRORS 5
PROGRAMMING 6
1. INTRODUCTION TO THE µCONSOLE 7
2. INFORMATION RELATING TO THE INSTRUMENT - FEATURES 7
3. READING OF THE MEASURES 7
4. ACCESS TO THE MAIN MENU 7
5. CONFIGURATION OF THE MEASURES (MENU « INPUTS ») 8
6. CONFIGURATION OF A RELAY OUTPUT (MENU « OUTPUTS ») 10
7. CONFIGURATION OF AN ANALOG OUTPUT 12
TECHNICAL FEATURES 13
1. GENERAL FEATURES 14
2. ELECTRICAL FEATURES 14
3. POSSIBLE OUTPUTS 15
4. DIMENSIONS 16
WIRING 17
1. WIRING RECOMMENDATIONS 18
2. WIRING OF THE POWER SUPPLY 18
3. WIRING OF A SINGLE PHASE NETWORK: « SINGLE » 19
4. WIRING OF A 3-PHASE BALANCED NETWORK WITHOUT NEUTRAL: « 3W BAL » 19
5. WIRING OF A 3-PHASE BALANCED NETWORK WITH NEUTRAL: « 4W BAL » 19
6. WIRING OF THE RELAY OUTPUTS 20
7. WIRING OF THE ANALOG OUTPUTS 20

Page 2
U
US
SE
E

Page 3
1. RECEIPT OF THE INSTRUMENT & START UP
Check that the configuration of the instrument (as indicated on the case bottom label) corresponds to your order.
Mount the instrument on a DIN rail.
Connect the power supply (see the wiring diagrams). The tension LED lights up.
The instrument now starts to measure, it has a standard configuration (except specific indications on your order).
The instrument can now be programmed, preferably before connecting the measure signals.
Now connect all the signals: see the wiring diagrams.
If not specified, the communication parameters for the PC software or the digital output are the following:
slave number = 250 speed = 9600 bauds without parity 1 stop bit
2. ORGANISATION OF THE FRONT FACE
IN CASE OF PROBLEM …
If the instrument does not light up: Check the presence of power supply (even for a self-powered instrument).
If the instrument does not measure: Check the presence of the measure signals.
Check the programming.
If the green LED is blinking: The instrument is detecting an error, connect the console or the PC software for
the analysis.
DIN rail
ON: Visualisation of the setting on tension /
error
COM:
Visualisation
of the communications
REL: Visualisation of the relays status
Connectics for the programming
micro-console / shifted display.
DIN plug: PC connection
DO NOT DISMOUNT THE FRONT FACE IF THE
MEASURE SIGNALS AND THE POWER SUPPLY
ARE CONNECTED

Page 4
3. List of the measured parameters
SINGLE
4W BAL
3W BAL
N°
Measured parameter
1U
13
(mesh voltage U13) X
2UL
1
(single voltage UL1) X X
3IL
1
(line current IL1) X X X
4
F
(Frequency) X X X
SINGLE: Single phase
4W BAL: 3-phase balanced with neutral
3W BAL: 3-phase balanced without neutral

Page 5
6. USE OF THE « CUT OFF »
The « cut off » is a programming option of the instrument which allows setting the display to 0 separately for low U
and I values (see the chapter « programming of the CUT OFF »).
Once the menu is validated the instrument will measure the values on its inputs and enforce the display to 0 for any
values lower than the « cut off » programmed in % of the caliber (1 or 5A, 100VL-N / 175VL-L or 330VL-N / 600VL-L).
7. LIST OF THE ERRORS
When the green LED on the front face is blinking, the instrument is indicating an error.
The number of the error can be seen connecting the micro-console or the PC software.
Err nr
Types of errors
Notes
0
Programme memory deleted Contact after sales
2
Wiring error Wrong wiring of the U / I measure signals
4
Current caliber overstepping CC’s not adapted
8
Voltage caliber overstepping VT’s not adapted – wiring error – error in the
programming of the network type
32
Configuration lost Re-programme the instrument
64
Calibration lost Return to the factory for re-calibration

Page 6
P
PR
RO
OG
GR
RA
AM
MM
MI
IN
NG
G

Page 7
1. INTRODUCTION TO THE µCONSOLE
The µconsole allows displaying the measures of the instrument.
It also allows modifying the configuration. It can be connected either before setting the
instrument on tension or while it is operating.
2. INFORMATION RELATING TO THE INSTRUMENT- FEATURES
The instrument will display its features on the setting on tension (if the µconsole is connected) or after the key
menu (M) is pressed.
Type of the instrument: TAI60
Programme version
Options: 2R 2 relay outputs
3. READING OF THE MEASURES
3.1. Changing of displayed parameter
Press the above keys to switch to the next/previous parameter(s). If 2 measures are being displayed, the unit will
appear on the side of the parameter name. Otherwise, it will appear under the value.
The measures are displayed on 4 digits, the energies on 6.
4. ACCESS TO THE MAIN MENU
In the menus, the key (M) is used as a « back » key.
The key menu allows entering the configuration.
The instrument will show its features, and then open access to the main menu (in reading only).
Access / exit of the configuration menu:
- Configuration in readin / writing (code 111)
- Revert to the previous menu or revert to the measure
To modify the configuration enter the code 111:
« PROGRAM » « CODE » « 111 »
Exit and save by pressing Muntil the display shows
« SAVE » and validate « YES »
Increase / navigation
following measure
Decrease / navigation
previous measure
Validation
Switching to the next character for an entering

Page 8
The navigation keys allow selecting the menus:
To enter the mode programming: validate the choice « CODE » in the menu « PROGRAM », and enter the code
111.
5. CONFIGURATION OF THE MEASURES (MENU « INPUTS »)
5.1. Choice of the measure network « NETWRK », « TYPE »
SINGLE Single phase
3W BAL 3-phase balanced without neutral
4W BAL 3-phase balanced with neutral
If a mesh voltage is connected on the instrument, programme the network 3W BAL.
If a single voltage is connected on the instrument, connect the network 4W BAL.
5.2. Choice of the ranges « RANGE »
Voltage range « RANG U »
173V 173VL-N(4W BAL or 1PH) 173VL-L(3W BAL)
600V 600VL-N(4W BAL or 1PH) 600VL-L(3W BAL)
Current range « RANG I »
1A 1A
5A 5A
5.3. Entering of the CT/VT ratios « CT VT »
PRI VT / SEC VT
0230 . Programming of the VT primary and its unit (V or kV)
V Programming of the VT secondary, without unit
(Do not programme a ratio but the real values)
PRI CT / SEC CT
0005 . Programming of the CT primary and its unit (A or kA)
A Programming of the CT secondary, without unit
(Do not programme a ratio but the real values)
PROGRAM Modification of the language, entering in mode programming.
INPUTS Configuration of the measure inputs.
RS-485
OUTPUTS
Configuration of the digital data link RS485 (if option present)
Validate to enter the chosen menu.
Configuration of the instrument outputs (relay, analog).
IMPORTANT:
programme the VT ratios in single voltage (if you
have 15kV/100V VTs between lines, programme 8.33kV / 57.7V
for the ratios)

Page 9
5.4. Entering of the Cut Off « CUTOFF »
CUT U / CUT I
05 . 0 Programming of the voltage and current cut offs (value below which the instrument will
% enforce the measure to 0). To be entered in % of the caliber value (1 or 5A, 100 or
330V).
5.5. Processing « FONCT »
Choice of the digital fitlering « FILTER »
OFF Choice of the digital filtering weight.
NR 1 Increase the value in case of unsteady measures.
NR 2
NR 3
De-validation of the errors « DIAG »
OFF Allows validating or de-validating the measure errors.
ON

Page 10
6. CONFIGURATION OF THE RELAY OUTPUTS (MENU « OUTPUTS »)
Each output is configured as alarm setpoint.
6.1. Configuration in mode setpoint « ALARM »
2 modes can be combined with 2 types of safeties:
Choice of the parameter to be watched « MEAS O »
U13 Selection of the measure to be watched.
IL1
…
MODE SINGLE WITH 1 SETPOINT , LOW SAFETY:
Setpoint
Contact closed
Value of the parameter
Contact open
The hysteresis is centered around the setpoint (0 to 15%).
MODE SINGLE WITH 1 SETPOINT , HIGH SAFETY:
Contact open
Value of the parameter
Contact closed
Setpoint
The hysteresis is centered around the setpoint (0 to 15%).
MODE WINDOW WITH 2 SETPOINTS , LOW SAFETY:
Setpoint 1 Setpoint 2
The hysteresis are centered around the setpoint (0 to 15%).
Contact open Contact open
Contact
closed
Value of the parameter
MODE WINDOW WITH 2 SETPOINTS, HIGH SAFETY:
The hysteresis are centered around the setpoint (0 to 15%).
Value of the parameter
Contact closed Contact closed
Contact
open
Setpoint 1 Setpoint 2

Page 11
Choice of the operating mode « CTRL »
1S LOW 1 setpoint, low safety
1S HIG 1 setpoint, high safety
2S LOW 2 setpoints, low safety (mode window)
2S HIG 2 setpoints, high safety (mode window)
Entering of the threshold(s) « THRES1 » « THRES2 »
0005 . Entering of the threshold in the measure unit.
A In the case of the mode window, the 2
nd
setpoint must be entered.
Choice of the hysteresis « HYSTER »
0 % Choice of the hysteresis attributed to the setpoint (in % of the setpoint value).
1 %
…
9 %
Choice of the time delay « DELAY »
0 . 0 S Choice of the time delay on the relay switching.
0 . 1 S
…
5 S

Page 12
7. CONFIGURATION OF AN ANALOG OUTPUT (MENU « OUTPUTS »)
7.1. Operating mode of an analog output – general case:
To configure a current output, it is necessary to define:
- the type of output: 4-20mA , 0-20mA, 0 5mA , 0 10mA
- the n° of the parameter attributed to the output (see the list of the parameters)
- the down and full scale for the measured parameter
- the return value for the output in case of error of the instrument.
N.B: on the setting on tension , the outputs can deliver 22mA during 1s.
Example: output 4-20mA for Vr from 50kV to 500Kv.
7.2. Configuration of the outputs: procedure to be followed
Choice of the measure to be transmitted « MEAS O »
U13 Choose the measure to be transmitted.
IL1
…
Choice of the output range « OUT RA »
4 20mA Choice of the output range in current.
0 20mA Positive scale only in the case of an instrument with the option ‘‘2A’’.
…
Down scale « DOWN S »
0000 . Enter the value of the measure corresponding to the output down scale.
A
Full scale « FULL S »
0005 . Enter the value of the measure corresponding to the output full scale.
A
Return value « RETURN »
22mA Choice of the return value in case of measure error.
20mA
10mA
…
500kV50kV
4mA
20mA

Page 13
T
TE
EC
CH
HN
NI
IC
CA
AL
L
F
FE
EA
AT
TU
UR
RE
ES
S

Page 14
1. GENERAL FEATURES
Housing Self-extinguishing case of black UL94VO ABS.
Format (H x L x D) 75 x 22.5 x 120 mm without µConsole
80 x 26.5 x 130 mm with µConsole
Mounting on DIN rail
Protection Housing IP30 (with the terminals mounted).
Connectings By plug-off screw terminals (wire section: 2.5 mm
2
).
Indicators 3 LEDs.
Programming by µConsole or PC programme
2. ELECTRICAL FEATURES
POWER SUPPLY
Voltage High or low voltage
Universal power supply:
20 to 270 VAC or 20 to 300VDC
Power draw 3 VA max. INPUTS
Voltages 2 programmable calibers: Un=173VAC & 600VAC. Oversteppings 120% Un
Currents 2 programmable calibers: 1A & 5A: In=1.2A & 6A. Oversteppings 120% In
Overload Permanent: 750V, 10A
During 10 s: 1000V, 50A
Power draws Voltage inputs: 1Mresistance
Current inputs: < 0.2VA
Test voltage 2kV, 50Hz /1min.
Frequency 10 … 50 … 70Hz (in standard)
Type of network Single or 3-phase balanced with or without neutral.
Thermic drifts <200ppm MEASURES
Number of parameters Up to 3 in basic version
Accuracy rating In digital output Cl. 0.2 voltage/current
Measure cycle 40 ms for all network types
Measuring method Fast simultaneous sampling of the voltage and the current.
Digital calculation on 32 bits.
Measurement of disturbed signals pass band 6.4kHz.
Digital filtering Various levels on choice by programming.
TEST AND OPERATING CONDITIONS
Reference T° 23°C
Operating T° -10°C to 55°C (others on request) IEC 60068-2-1 and IEC 60068-2-2
… in damp area 40°C to 93% condense free dampness IEC 60068-2-30
Storage T° -25°C to 70°C IEC 60068-2-1 and IEC 60068-2-2
T° gradiant in storage 3°C/min from –20°C to +70°C IEC 60068-2-14
Relative dampness 5% to 95% without condensation IEC 60068-2-30
HF rayed field IEC 61000.4.3 level 3
Electrostatic discharge IEC 61000.4.2 level 3
RF conducted field IEC 61000.4.6 level 3
50Hz magnetic field IEC 61000.4.8 level 3
1,2/50s shockwave IEC 61000.4.5 level 3 mode series/common
Fast transient IEC 61000.4.4 level 3 mode common
GSM RF field ENV 50204
Generic standards immunity: IEC 61000-6-2 rejections: 61000-6-4
test standards: EN 55011 class A
Vibration withstanding +/-150µm from 10 to 57 Hz and +/- 2G from 57Hz to 500Hz conform with 68-2-6
- CE marking -

Page 15
3. POSSIBLE OUTPUTS
The instrument includes in standard:
-2 setpoint relay outputs (S5-S6 and S7-S8).
The relay outputs are programmed as alarm setpoint – option R .
Type of contact : potential free contac, galvanic partition 2.5KV
Rated load : 5A – 250VAC
Lifetime : 20 000 000 operations empty, 300 000 operations at 2A/250V
-Setpoint outputs:
Setting of the setpoints : 0 to 100% of the measure range (programmable)
Switching hysteresis : 0 to 15% of the setpoint (programmable)
Time delay : 0 to 15s (programmable)
Analog output – option A :
Galvanic partition : Inputs 2kV, RS485 1kV
Output signal : programmable (0/20mA or 4/20mA).
Scale setting : 0 to 100% of the measure range (programmable)
Admissible load : up to 600(20mA)
Resolution : 24000 points
Accuracy : <0.2% of the full scale on 0/20mA (in relation to the display)
Residual ripple : -/+2.5mV (dc) on 50load
Response time of the output : 50ms (<120ms input output)
Thermic drifts : <200ppm caliber 0/20mA

Page 16
4. DIMENSIONS
May be modified any time for technical reasons.
75.5
120
127
µConsole
102.5
DIN rail
22.5
13.5
26.5
80

Page 17
W
WI
IR
RI
IN
NG
G

Wiring
Page 18
1. WIRING RECOMMENDATIONS
The input network ( UL1, IL1) may carry significant disturbances, and they may disturb the complete processing
chain. In order to avoid this the disturbance immunity can be improved efficiently by respecting a few simple rules:
Do not connect too close: the input network and the instrument power supply wires.
Do not connect too close: the input network and all the instrument output wires (pulse outputs, relay outputs ...)
Use for all the outputs of the instrument shielded cables connected to the GND on both ends.
In order to avoid any influence of the current take
up on the voltage measure, connect the CT’s
before the VT’s.
2. WIRING OF THE POWER SUPPLY
LoadNetwork
S1
µConsole
Power
supply Measure inputs
Connector of the relay outputs
Configuration label
A3
A2
A1
E4
E3
E2
E1
S1
S2
S3
S4
S5
S6
S7
S8
N1
N2
Note
:
For an AC supply
, the phase and
the neutral can be connected indifferently
on the terminals A1 and A3.
For a DC supply, the + and the – can be
connected indifferently on A1 and A3.
A1 A3
P
+N
-
AC supply
DC supply
A2
Connector of the analog outputs

Wiring
Page 19
3. WIRING OF A SINGLE PHASE NETWORK : « SINGLE »
4. WIRING OF A 3-PHASE BALANCED NETWORK WITHOUT NEUTRAL : « 3W BAL »
5. WIRING OF A 3-PHASE BALANCED NETWORK WITH NEUTRAL : « 4W BAL »
without VT
without CT
Umax = 330V
Imax = 5A
with VT
with CT
without VT
without CT
Umax = 600V L-L
Imax = 5A
with VT
with CT
without VT
without CT
Umax = 330V L-N
Imax = 5A
with VT
with CT
Respect the correct connection: The secondaries S2 of the CT’s must be set to the earth.
Load
Load
Load
Load
Load
Load
Table of contents
Popular Transmitter manuals by other brands

Extron electronics
Extron electronics XTP T HWP 101 Setup guide

FMS
FMS RTM MP Plus EMGZ482T.PLUS.MP.W.24VDC Operation manual

Lectrosonics
Lectrosonics IFBT4/E01-VHF quick start guide

Advanced Instruments
Advanced Instruments GPR-2800 IS manual

Elmes Electronic
Elmes Electronic STX manual

Bürkert
Bürkert 8025 Series operating instructions