XNX Universal Transmitter Quick Start Guide 3
WARNINGS
The XNX Universal Transmitter is certied and designed for installation and use »
worldwide in hazardous areas.
Installation must be in accordance with the recognized standards of the appropriate »
authority in the country concerned.
Access to the interior of the detector, when carrying out any work, must only be conducted »
by trained personnel.
Before carrying out any work, ensure local regulations and site procedures are followed. »
Appropriate standards must be followed to maintain the overall certication of the detector.
To reduce the risk of ignition of hazardous atmosphere, disconnect the equipment from »
the supply circuit before opening the detector enclosure. Keep assembly tightly closed
during operation.
Never open the XNX enclosure under power unless the area is known to be non hazardous.»
The detector must be earthed/grounded for Intrinsic Safety, electrical safety and to limit »
the effects of radio frequency interference. An earth/ground point is provided inside
and outside the unit. The internal grounding shall be used as the primary equipment
ground. The external terminal is only a supplemental bonding connection where local
authorities permit or require such a connection.
Take care when handling EC sensor cells as they may contain corrosive solutions.»
Do not tamper or in any way disassemble the sensor cells.»
Do not expose to temperatures outside the recommended range.»
Do not expose sensor to organic solvents or ammable liquids.»
At the end of their working life, sensors must be disposed of in an environmentally »
safe manner. Disposal should be according to local waste management requirements
and environmental legislation.
Alternatively, sensors may be securely packaged and returned to Honeywell Analytics »
clearly marked for environmental disposal.
Electrochemical cells should NOT be incinerated as they may emit toxic fumes.»
HAzARdouS LocAtIoNS INStALLAtIoN RequIRemeNtS (uL/cSA)
To reduce the risk of ignition of hazardous atmospheres, conduit runs must have a pour »
gland installed within 18 inches (457mm) of enclosure.
All ¾ inch NPT conduit, stopping plugs and adapters must be installed with 5 ¼ threads »
(minimum) engaged to Maintain Explosion Proof rating.
The XNX Cover Assembly must be fully seated to enclosure 9 threads (minimum) to »
maintain Explosion Proof rating.
Stopping Plugs supplied (Honeywell Part Number 1226-0258) are approved for use »
ONLY with the XNX Universal Transmitter.
For units tted with the Optional Relay Module: Relay Contact Ratings are 250 VAC »
5A, 24 VDC 5A Resistive Loads Only.
Use copper conductors only, 60/75»°C, terminal block screws should be tightened to
4.5 Lb/in maximum.
Reference XNX Control Drawing 1226E0402 for additional information regarding IS »
function (Local HART and EC Personality).
HAzARdouS LocAtIoNS INStALLAtIoN RequIRemeNtS (AteX)
Read and understand this manual before installation and use.»
Use only Certied M25 cable glands for installation.»
Shielded armoured cable is required for CE compliance.»