Argantix XDS 30-167 Owner's manual

Revision L
February 2007
Copyright 2002-2007
By California Instruments
All rights reserved.
P/N 5005-981
XDS Series
DC Power Supply
User and Programming
Manual
Series II
TEL: +1 (858) 677-9040
FAX: +1 (858) 677-0940
Email: [email protected]
Web Site: http://www.argantix.com
Advanced Test Equipment Rentals
www.atecorp.com 800-404-ATEC (2832)
®
E
s
t
a
b
l
i
s
h
e
d
1
9
8
1

User and Programming Manual
XDS Series 2
User and Programming Manual
P/N 5005-981
DC Power Supplies
Argantix
XDS Series II
Copyright 2002-2007, California Instruments, Rev L.
Argantixis a registered trademark of California Instruments Corporation.
Specifications subject to change without notice.

User and Programming Manual
XDS Series 3
SAFETY SUMMARY
This power supply contains high voltage and current circuits that are potentially lethal.
Because of its size and weight, electrical and mechanical stability must be ensured. The
following safety guidelines must be followed when operating or servicing this equipment.
These guidelines are not a substitute for vigilance and common sense. If this power supply is
not used as specified in this manual, the protection provided by this equipment may be
impaired. California Instruments assumes no liability for the customer's failure to comply with
these requirements.
BEFORE APPLYING POWER
1. Check the units input rating on the type label and verify the correct voltage is applied to the unit
(for example 208 V L-L, 3 Phase).
2. The chassis and cabinet of this power supply must be grounded to minimize shock hazard. A
chassis ground is provided at the input terminal block. This is located at the back of the cabinet
on the right hand side (looking at the back of the unit). The chassis ground must be connected
to an electrical ground through an insulated wire (green/yellow) of sufficient gauge.
3. The XDS Series power supplies do not have internal AC mains disconnect. Instead, protection is
provided by fuses. The on/off button only engages or disengages the bias supplies, it does not
disconnect the AC mains to the unit. It is strongly recommended to use a suitably rated
circuit breaker or mains disconnect device with branch protection rating per local
electrical codes between point of connection and the XDS unit AC input.
FUSES
Use only fuses of the specified current, voltage, and protection speed.
DO NOT OPERATE IN A VOLATILE ATMOSPHERE
Do not operate the power supply in the presence of flammable gases or fumes. This product is
designed to operate in a controlled environment. Do not expose to rain or snow.
DO NOT TOUCH ENERGIZED CIRCUITS
Disconnect the power cable before servicing this equipment. Even with the power cable disconnected,
high voltage can still exist on some circuits. Discharge these voltages before servicing. Allow at least
30 minutes for all internal circuits to discharge before removing the top cover. Only qualified service
personnel may remove covers, replace components or make adjustments.
DO NOT SERVICE ALONE
Do not remove covers, replace components, or make adjustments unless another person, who can
administer first aid, is present.
DO NOT EXCEED INPUT RATINGS
Do not exceed the rated input voltage or frequency. Additional hazards may be introduced because of
component failure or improper operation.
DO NOT MODIFY INSTRUMENT OR SUBSTITUTE PARTS
Do not modify this instrument or substitute parts. Additional hazards may be introduced because of
component failure or improper operation.
MOVING THE POWER SUPPLY
When moving the power supply, observe the following:
1. Remove all AC power to unit.
2. Note that the handles are provided to pull instrument out of 19" instrument cabinet and are
not designed to support the weight of the unit.
3. Use two people to prevent injury.
SURFACE STABILITY
Operate the power supply only on a level surface.

User and Programming Manual
4 XDS Series
Electrical Safety Symbols Used in This Manual

User and Programming Manual
XDS Series 5
WARRANTY INFORMATION
CALIFORNIA INSTRUMENTS CORPORATION warrants each instrument manufactured by them
to be free from defects in material and workmanship for a period of five years from the date of
shipment to the original purchaser. Excepted from this warranty are fuses and batteries that
carry the warranty of their original manufacturer where applicable. CALIFORNIA
INSTRUMENTS will service, replace, or adjust any defective part or parts, free of charge, when
the instrument is returned freight both ways prepaid, and when examination reveals that the fault
has not occurred because of misuse, abnormal conditions of operation, user modification, or
attempted user repair. Equipment repaired beyond the effective date of warranty or when
abnormal usage has occurred will be charged at applicable rates. CALIFORNIA INSTRUMENTS
will submit an estimate for such charges before commencing repair, if so requested.
SERVICE PROCEDURE
representative, giving full details of the difficulty, including the model number and serial number.
On receipt of this information, service information or a Return Material Authorization (RMA)
number will be given. Add the RMA number furnished to the shipping label. Pack the instrument
carefully to prevent transportation damage, affix label to shipping container, and ship freight
prepaid to the factory. CALIFORNIA INSTRUMENTS shall not be responsible for repair of
damage due to improper handling or packing. Instruments returned without RMA No. or freight
collect may be refused at California Instruments discretion. All XDS Series Instruments repaired
will be returned freight collect, Ex Works CALIFORNIA INSTRUMENTS, 9689 Towne Centre
Drive, San Diego, CA 92121-1964. If requested, an estimate of repair charges will be made
before work begins on repairs not covered by the Warranty.
DAMAGE IN TRANSIT
The instrument should be tested when it is received. If it fails to operate properly, or is damaged
in any way, a claim should be filed immediately with the carrier. The claim agent should obtain a
full report of the damage, and a copy of this report should be forwarded to us by fax or email
an estimate of repair cost and repair the instrument when authorized by the claim agent. Please
include model number and serial number when referring to the instrument.
SPARE PARTS
To order spare parts, user manuals, or determine the correct replacement part for your California
Instruments products, please contact the Customer Service department by phone at + 1 858 404

User and Programming Manual
6 XDS Series
Table of Contents
1
Introduction.................................................................................................................................. 10
1.1
General Description............................................................................................................................. 10
1.2
Bench Top use.................................................................................................................................... 11
1.3
Equipment Rack use........................................................................................................................... 11
2
Specifications............................................................................................................................... 12
2.1
Electrical.............................................................................................................................................. 12
2.2
Measurements .................................................................................................................................... 15
2.3
Environmental ..................................................................................................................................... 17
2.4
Mechanical.......................................................................................................................................... 17
2.5
Agency Approvals ............................................................................................................................... 18
2.6
Remote Control Interfaces .................................................................................................................. 18
2.7
Protection............................................................................................................................................ 19
2.8
Controls and Indicators ....................................................................................................................... 19
2.9
Parallel Operation................................................................................................................................ 19
2.10
Factory Configuration Options......................................................................................................... 20
2.11
-LC Option....................................................................................................................................... 20
3
Installation and Functional Test................................................................................................... 21
3.1
Inspection............................................................................................................................................ 21
3.2
Location and Mounting........................................................................................................................ 21
3.3
Input / Output Connectors................................................................................................................... 22
3.4
Wire Sizing and Lug Size.................................................................................................................... 25
3.5
AC Input Wiring................................................................................................................................... 26
4
Front Panel Operation ................................................................................................................. 28
4.1
Functional Controls ............................................................................................................................. 28
4.2
How to examples................................................................................................................................. 31
4.3
Setting the Power on Initialization Values............................................................................................ 33
4.4
Operating Modes................................................................................................................................. 34
4.5
Special Features ................................................................................................................................. 35
5
Model Configurations................................................................................................................... 37
5.1
Available Configurations...................................................................................................................... 37
5.2
Changing Configurations..................................................................................................................... 38
5.3
Stand Alone Configuration .................................................................................................................. 40
5.4
Parallel Mode ...................................................................................................................................... 40
5.5
RPV Mode........................................................................................................................................... 43
5.6
RPC Mode........................................................................................................................................... 43
6
Principle of Operation.................................................................................................................. 44
6.1
General ............................................................................................................................................... 44
6.2
Overall Description.............................................................................................................................. 44
6.3
Bias Power Supply (A7)....................................................................................................................... 47
6.4
Power Module (A9 through A11)......................................................................................................... 48
6.5
Controller Module (A3)........................................................................................................................ 50
7
Calibration.................................................................................................................................... 52
7.1
Calibration Equipment......................................................................................................................... 52
7.2
Routine Calibration.............................................................................................................................. 53
7.3
Non-Routine Calibration...................................................................................................................... 56

User and Programming Manual
XDS Series 7
8
Service......................................................................................................................................... 59
8.1
General ............................................................................................................................................... 59
8.2
Basic Operation................................................................................................................................... 59
8.3
Module Removal ................................................................................................................................. 62
8.4
Controller Jumper Settings.................................................................................................................. 65
8.5
Replaceable Parts............................................................................................................................... 67
9
Remote Control............................................................................................................................ 70
9.1
Introduction ......................................................................................................................................... 70
9.2
XDSGUI Program Requirements......................................................................................................... 71
9.3
RS232C Interface................................................................................................................................ 71
9.4
Optional IEEE Interface....................................................................................................................... 73
9.5
XDSGUI Installation ........................................................................................................................... 74
9.6
Trouble Shooting - RS232C ................................................................................................................ 75
9.7
Trouble Shooting - IEEE-488 / GPIB................................................................................................... 78
9.8
Software Registration.......................................................................................................................... 79
10
Introduction to SCPI................................................................................................................. 80
10.1
Conventions Used in This Manual................................................................................................... 80
10.2
The SCPI Commands and Messages ............................................................................................. 80
10.3
Using Queries.................................................................................................................................. 83
10.4
Structure of a SCPI Message.......................................................................................................... 83
10.5
SCPI Data Formats......................................................................................................................... 85
10.6
Programming Tips........................................................................................................................... 86
11
SCPI Command Reference...................................................................................................... 87
11.1
Subsystem Commands ................................................................................................................... 87
11.2
Measurement Subsystem................................................................................................................ 88
11.3
Source Subsystem.......................................................................................................................... 90
11.4
Output Subsystem........................................................................................................................... 95
11.5
Display Subsystem.......................................................................................................................... 97
11.6
System Commands......................................................................................................................... 98
11.7
Common Commands .................................................................................................................... 100
12
Programming Examples.........................................................................................................107
12.1
Introduction ................................................................................................................................... 107
12.2
Programming the Output............................................................................................................... 107
12.3
Making Measurements.................................................................................................................. 108
13
Status Registers.....................................................................................................................109
13.1
Power-On Conditions .................................................................................................................... 109
13.2
Standard Event Status Group........................................................................................................ 110
13.3
Status Byte Register...................................................................................................................... 110
13.4
Examples ...................................................................................................................................... 111
Appendix A: SCPI Command tree ....................................................................................................112
Appendix B: SCPI Conformance Information ................................................................................... 113
Appendix C: Error Messages............................................................................................................114
Index..................................................................................................................................................115

User and Programming Manual
8 XDS Series
List of Figures
Figure 1-1: XDS Series DC Power Supply.......................................................................................................... 10
Figure 3-1: Location of rear panel connectors..................................................................................................... 24
Figure 3-2: DC Output bus bar studs. ................................................................................................................. 25
Figure 3-4: Toroid Installation, -400V input model............................................................................................... 26
Figure 3-5: Outline Drawing XDS DC Supply...................................................................................................... 27
Figure 4-1: Front Panel View............................................................................................................................... 28
Figure 4-2: Shuttle Knob ..................................................................................................................................... 29
Figure 5-1: XDS Configuration Jumper Locations............................................................................................... 38
Figure 5-2: XDS Controller Jumper Locations – Front view, far side of PWB...................................................... 39
Figure 5-3: Master / Auxiliary Interconnect Cable Diagram................................................................................. 40
Figure 5-4: Parallel Cable Interconnect Accessory.............................................................................................. 41
Figure 5-5: XDS 30KW System Connections...................................................................................................... 42
Figure 6-1: DC Power Supply Block Diagram - -IF option shown........................................................................ 45
Figure 6-2: XDS DC Supply Simplified Block Diagram........................................................................................ 46
Figure 6-3: Power Module Block Diagram........................................................................................................... 48
Figure 7-1: Test Equipment Hookup for Routine Output and Measurement Calibration...................................... 53
Figure 7-2: Calibration Adjustments.................................................................................................................... 54
Figure 8-1: Assembly Location............................................................................................................................ 62
Figure 8-2: XDS Controller Jumper Locations – Front view, far side of PWB...................................................... 66
Figure 8-3: Replaceable Fuse Locations............................................................................................................. 69
Figure 9-1: XDSGUI Main screen........................................................................................................................ 70
Figure 9-2: Rear Panel View............................................................................................................................... 73
Figure 9-3: GPIB Address Selection Switch........................................................................................................ 73
Figure 9-4: System Properties Dialog Box .......................................................................................................... 76
Figure 9-5: Advanced Port Settings Dialog Box.................................................................................................. 76
Figure 9-6: COM Port Properties Dialog Box ...................................................................................................... 76
Figure 9-7: NI PCI-GPIB Settings........................................................................................................................ 78
Figure 9-8: NI PCI-GPIB Advanced Settings Dialog............................................................................................ 78
Figure 10-1: Partial Command Tree.................................................................................................................... 81
Figure 10-2: Command Message Structure ........................................................................................................ 83
Figure 13-1: Power Supply Status System Model............................................................................................. 109

User and Programming Manual
XDS Series 9
List of Tables
Table 3-1: Rear Panel Input and /Output Connectors ......................................................................................... 22
Table 3-2: Output Connection Description .......................................................................................................... 22
Table 3-3: Input Connection Description............................................................................................................. 23
Table 3-4: RS232C Connector J20..................................................................................................................... 23
Table 3-5: Analog I/O Connector J22.................................................................................................................. 23
Table 3-6: Auxiliary I/O Connector (Isolated ) – J21............................................................................................ 24
Table 3-7: Minimum Wire Size Table .................................................................................................................. 25
Table 4-1: Factory Default Power on Settings..................................................................................................... 33
Table 5-1: XDS Controller Configuration Options................................................................................................ 37
Table 5-2: Configuration Jumper Settings - Mode............................................................................................... 38
Table 7-1: Calibration Equipment........................................................................................................................ 52
Table 7-2: Load Resistors and Current by model................................................................................................ 52
Table 7-3: Calibration Adjustment Reference by number.................................................................................... 55
Table 7-4: Calibration Adjustment Reference by location left to right.................................................................. 55
Table 8-1: Basic Symptoms ................................................................................................................................ 59
Table 8-2: Poor Output Voltage Accuracy........................................................................................................... 59
Table 8-3: Poor Output Voltage Regulation......................................................................................................... 59
Table 8-4: No Output and No Lights on Front Panel........................................................................................... 60
Table 8-5: No Output But "Display" Is On........................................................................................................... 60
Table 8-6: DC Controller Configuration Jumper Settings - Mode ........................................................................ 65
Table 8-7: DC Controller Jumper configurations - Power Level........................................................................... 65
Table 8-8: DC Controller Jumper configurations - OVP mode............................................................................. 65
Table 8-9: Replaceable Parts.............................................................................................................................. 68
Table 8-10: Power Module Output Capacitance.................................................................................................. 68
Table 11-1: Mode query result decoding............................................................................................................. 92
Table 11-2: Display Mode Command Encoding.................................................................................................. 97
Table 11-3: Bit Configuration of Standard Event Status Enable Register......................................................... 101
Table 11-4: Bit Configuration of Standard Event Status Register...................................................................... 102
Table 11-5: *RST Default Parameter Values..................................................................................................... 104
Table 11-6: Status Registers - Power on Conditions......................................................................................... 104
Table 11-7: Bit Configuration of Status Byte Register....................................................................................... 106
Table 13-1: Bus Error Messages....................................................................................................................... 114

User and Programming Manual
10 XDS Series
1 Introduction
1.1 General Description
Figure 1-1: XDS Series DC Power Supply
The Argantix XDS Series of DC Programmable Power Supplies are designed specifically for
laboratory test and systems applications requiring single output, variable DC voltage and current
with good ripple and regulation characteristics. The XDS Series comes in a 3U chassis and can
operate in constant current or constant voltage mode with auto crossover feature. Available
Power levels are 5kW, 10kW and 15kW.
Simple front panel controls enable the voltage and current limit to be changed. Measurements of
voltage, current, peak current and power can also be read from the front panel LED displays.
The front panel contains a output on/off button for controlling the DC supply output and an LED
indicator that informs the operator of the output status at all time.
The left hand side LED display is used to display the programmed voltage as well as the
measured output voltage. The LED display to the right is used to program the current or to
display measured current, peak current or power. The display SELECT button can be used to
set the desired display mode.
A standard RS232C and optional IEEE 488 interface is available for applications that require
remote control and measurements. While operated remotely, the front panel can be locked out
and the remote control status is indicated by a REMOTE LED.
A power on/off switch can be used to turn the DC supply on or off.
Note: This user manual applies to the XDS models series II with the 5005-720-1
controller assembly. For first generation XDS DC models with controller
assembly 5005-708-1, refer to user manual P/N 5005-980 instead. First
generation XDS models typically do not have the air vents in the front
panel.

User and Programming Manual
XDS Series 11
1.2 Bench Top use
The XDS Series DC Supply may be used as a bench top unit provided adequate provisions are
made to protect the end-user from touching the output terminals. To this end, output covers are
provided on all XDS units. These covers must be installed during use and may only be removed
when the unit is not in use and disconnected from AC mains.
Adequate air flow must be maintained at all times so care should be taken not to block the front,
top and side air intakes or the rear air exhaust. Leave at least 4" of clearance at the back of the
unit to allow proper airflow.
1.3 Equipment Rack use
The XDS Series uses a 19" cabinet with rack ears and can be installed in a standard equipment
rack. Due to the weight of the unit however, it must be properly supported by either a shelf or L
brackets on both sides. The rack ears are not designed to support the full weight of the XDS unit
when installed in a cabinet but only to prevent it from sliding out.
specific cabinets depths.
Proper airflow must be maintained in the instrument cabinet and the rear of the cabinet should
not be closed off by a door but rather a perforated screen allowing adequate airflow. It is also
important to leave enough clearance above each unit as some of the air intake is on the top
cover.
Note: For optimal cooling, it is recommended to leave a 1.75" (1 U) space above
each XDS unit.
This space may be covered by a louvered cover plate to allow some air intake from the front of
the cabinet. When planning cabinet space, allow for 4U per DC supply.
If insufficient rack space is available, the top vents may be blocked off by stacking units directly
on top of each other but maximum power may not be available at maximum ambient temperature
due to over temp fault.

User and Programming Manual
12 XDS Series
2 Specifications
All specifications at 23 5C unless noted otherwise.
2.1 Electrical
2.1.1 AC Line Input
Standard: -208: 208 VAC L-L -10% to 230VAC L-L +10 %
Options: -400: 400VAC L-L ± 10 %
-480: 480VAC L-L ± 10 %
Frequency: 50 to 60 Hz ± 3 Hz
Phases: 3-phase, 3-wire plus safety ground
Power Factor: > 0.65 typical.
2.1.2 Maximum Line Input Current per Phase at Low Line
Current 5 KW 10 KW 15 KW
Standard -208 27A 54A 81A
Options -400
-480: 18A
18A 36A
36A 54A
54A
Recommended circuit protection per phase. (CB)
Standard -208 30A 60A 90A
Options -400
-480: 20A
20A 40A
40A 60A
60A
2.1.3 Output Power
DC Power: 5 KW, 10 KW or 15 KW depending on model. See section 2.1.5.
Maximum power is available at full-scale voltage.
2.1.4 Output Voltage
Voltage Range: See section 2.1.5
Voltage Programming:
Model Range Resolution Accuracy
XDS 30-XXX 0 - 30 V 0.01 V ± 0.08 V
XDS 40-XXX 0 - 40 V 0.01 V ± 0.08 V
XDS 50-XXX 0 - 50 V 0.02 V ± 0.16 V
XDS 80-XXX 0 – 80 V 0.02 V ± 0.16 V
XDS 100-XXX 0 - 100 V 0.1 V ± 0.2 V
XDS 150-XXX 0 - 150 V 0.1 V ± 0.4 V
XDS 250-XXX 0 - 250 V 0.1 V ± 0.8 V

User and Programming Manual
XDS Series 13
XDS 300-XXX 0 - 300 V 0.1 V ± 0.8 V
XDS 400-XXX 0 - 400 V 0.1 V ± 1.6 V
XDS 600-XXX 0 - 600 V 0.2 V ± 1.6 V
Noise and Ripple: See section 2.1.5
Line Regulation: < 0.1% of V Range
Load Regulation: < 0.1% of V Range
External Sense External Voltage Sense mode.
Maximum voltage drop allowed at load terminals is 5% of voltage
range.
Note: For 600V models, maximum drop allowed is 3% (20Vdc).
OVP Range: 0 to 110 % of V Range
Transient Response: A 30% step load will recover to within 2% of voltage range value
within 2 msec.
Stability: +/- 0.05% of max. rating for 8 Hrs. at fixed line, load and temp
after 30 minutes warm up period
2.1.5 Ranges, Noise and Ripple
Model Output
Power
Max. Volts
Max. Amps
Max. RMS Ripple
Typical
1
Peak-Peak
Ripple typ.
XDS 30-167
XDS 30-333
XDS 30-500
5
10
15
30
30
30
167
333
500
15 mV
15 mV
15 mV
90 mV
90 mV
90 mV
XDS 40-125
XDS 40-250
XDS 40-375
5
10
15
40
40
40
125
250
375
15 mV
15 mV
15 mV
90 mV
90 mV
90 mV
XDS 50-100
XDS 50-200
XDS 50-300
5
10
15
50
50
50
100
200
300
15 mV
15 mV
15 mV
90 mV
90 mV
90 mV
XDS 80-62
XDS 80-125
XDS 80-187
5
10
15
80
80
80
62.5
125
187.5
25 mV
25 mV
25 mV
250 mV
250 mV
250 mV
XDS 100-50
XDS 100-100
XDS 100-150
5
10
15
80
80
80
50
100
150
25 mV
25 mV
25 mV
250 mV
250 mV
250 mV
XDS 150-33
XDS 150-66
XDS 150-100
5
10
15
150
150
150
33.3
66.7
100
25 mV
25 mV
25 mV
300 mV
300 mV
300 mV
XDS 250-20
XDS 250-40
XDS 250-60
5
10
15
250
250
250
20
40
60
100 mV
100 mV
100 mV
400 mV
400 mV
400 mV
XDS 300-17
XDS 300-33
XDS 300-50
5
10
15
300
300
300
17
33.3
50
100 mV
100 mV
100 mV
400 mV
400 mV
400 mV
XDS 400-12
XDS 400-25
XDS 400-37
5
10
15
400
400
400
12.5
25
37.5
250 mV
250 mV
250 mV
2 V
2 V
2 V
1
Maximum RMS Ripple < 2 x typical value shown.

User and Programming Manual
14 XDS Series
XDS 600-8
XDS 600-17
XDS 600-25
5
10
15
600
600
600
8.33
17
25
250 mV
250 mV
250 mV
2 V
2 V
2 V
2.1.6 Output Current
Current Range: See section 2.1.5
Current Programming:
Accuracy: Accuracy shown in last column as % of Full Scale (FS) from 100
% programmed to 0% programmed.
Resolution: Shown in column 3 by model.
Model Range Resolution Accuracy
XDS 30-167
XDS 30-333
XDS 30-500
0 - 167 A
0 - 333 A
0 - 500 A
0.1 A
0.1 A
0.2 A
0.5 %
XDS 40-125
XDS 40-250
XDS 40-375
0 - 125 A
0 - 250 A
0 - 375 A
0.1 A
0.1 A
0.2 A
0.5 %
XDS 50-100
XDS 50-200
XDS 50-300
0 - 125 A
0 - 250 A
0 - 375 A
0.1 A
0.1 A
0.1 A
0.5 %
XDS 80-62
XDS 80-125
XDS 80-187
0 - 62.5 A
0 - 125 A
0 - 187.5 A
0.02 A
0.1 A
0.1 A
0.5 %
XDS 100-50
XDS 100-100
XDS 100-150
0 - 50 A
0 - 100 A
0 - 150 A
0.02 A
0.1 A
0.1 A
0.5 %
XDS 150-33
XDS 150-66
XDS 150-100
0 - 33.3 A
0 - 66.7 A
0 - 100 A
0.01 A
0.02 A
0.1 A
0.5 %
XDS 250-20
XDS 250-40
XDS 250-60
0 - 20 A
0 - 40 A
0 - 60 A
0.005 A
0.01 A
0.02 A
0.5 %
XDS 300-17
XDS 300-33
XDS 300-50
0 - 16.7 A
0 - 33.3 A
0 - 50 A
0.005 A
0.01 A
0.02 A
0.5 %
XDS 400-12
XDS 400-25
XDS 400-37
0 – 12.5 A
0 – 25.0 A
0 – 37.5 A
0.005 A
0.01 A
0.02 A
0.5 %
XDS 600-8
XDS 600-17
XDS 600-25
0 - 8.3 A
0 - 16.7 A
0 - 25 A
0.003 A
0.005 A
0.01 A
0.5 %
Line Regulation: < 0.1% of I Range
Load Regulation: < 0.1% of I Range
Stability: +/- 0.05% of max. rating for 8 Hrs. at fixed line, load and temp
after 30 minutes warm up period

User and Programming Manual
XDS Series 15
2.2 Measurements
Voltage
Model Range Resolution Accuracy
XDS 30-XXX 0 - 30 V 0.01 V ± 0.05 V
XDS 40-XXX 0 - 40 V 0.01 V ± 0.05 V
XDS 50-XXX 0 - 50 V 0.02 V ± 0.1 V
XDS 80-XXX 0 - 80 V 0.02 V ± 0.1 V
XDS 100-XXX 0 - 100 V 0.1 V ± 0.2 V
XDS 150-XXX 0 - 150 V 0.1 V ± 0.3 V
XDS 250-XXX 0 - 250 V 0.1 V ± 0.5 V
XDS 300-XXX 0 - 300 V 0.1 V ± 0.5 V
XDS 400-XXX 0 - 400 V 0.1 V ± 0.5 V
XDS 600-XXX 0 - 600 V 0.2 V ± 1.0 V
Current
Model Range Resolution Accuracy
XDS 30-167
XDS 30-333
XDS 30-500
0 - 167 A
0 - 333 A
0 - 500 A
0.1 A
0.1 A
0.2 A
± 0.3 A
± 0.5 A
± 1 A
XDS 40-125
XDS 40-250
XDS 40-375
0 - 125 A
0 - 250 A
0 - 375 A
0.1 A
0.1 A
0.1 A
± 0.3 A
± 0.5 A
± 0.5 A
XDS 50-100
XDS 50-200
XDS 50-300
0 - 100 A
0 - 200 A
0 - 300 A
0.1 A
0.1 A
0.1 A
± 0.3 A
± 0.5 A
± 0.5 A
XDS 80-62
XDS 80-125
XDS 80-187
0 - 66 A
0 - 125 A
0 - 187 A
0.02 A
0.1 A
0.1 A
± 0.1 A
± 0.3 A
± 0.3 A
XDS 100-50
XDS 100-100
XDS 100-150
0 - 50 A
0 - 100 A
0 - 150 A
0.02 A
0.1 A
0.1 A
± 0.1 A
± 0.3 A
± 0.3 A
XDS 150-33
XDS 150-66
XDS 150-100
0 - 33 A
0 - 66 A
0 - 100 A
0.01 A
0.02 A
0.1 A
± 0.05 A
± 0.1 A
± 0.3 A
XDS 250-20
XDS 250-40
XDS 250-60
0 – 20 A
0 - 40 A
0 - 60 A
0.005 A
0.01 A
0.02 A
± 0.025 A
± 0.05 A
± 0.1 A
XDS 300-17
XDS 300-33
XDS 300-50
0 - 17 A
0 - 33 A
0 - 50 A
0.005 A
0.01 A
0.02 A
± 0.025 A
± 0.05 A
± 0.1 A
XDS 400-12
XDS 400-25
XDS 400-37
0 – 12.5 A
0 - 25 A
0 – 37.5 A
0.005 A
0.01 A
0.02 A
± 0.025 A
± 0.05 A
± 0.1 A
XDS 600-8 0 - 8 A 0.003 A ± 0.013 A

User and Programming Manual
16 XDS Series
XDS 600-17
XDS 600-25 0 - 17 A
0 - 25 A 0.005 A
0.01 A ± 0.025 A
± 0.05 A
Power
Model Range Resolution Accuracy
All 0 - 5 KW
0 -10 KW
0 - 15 KW
1 W
2 W
5 W
± 0.3 % FS
Peak Current
Model Range Resolution Accuracy
All See current table See current table See accuracy in
current table
+ 3 x resolution

User and Programming Manual
XDS Series 17
2.3 Environmental
Temperature Coefficient
Voltage Set Point: 0.02%/C of V Range
Current Set Point: 0.03%/C of I Range
Ambient Temperature
Operating: 0° to 40° C / 32° to 104° F
Storage: -40° to 75° C /-40° to 167° F
Humidity: 0 to 80 % RH, non condensing
Cooling: Forced Air. Front, side and top air intake, rear exhaust.
Altitude
Operating: 2000 meters max.
Storage: 6000 meters max.
2.4 Mechanical
Dimensions: Width: 19.00 “/ 482.6 mm
Depth: 22.19”/ 563.3 mm
(excluding bus bars and cover)
Height: 5.25”/133.35 mm
Unit Weight: 15 kW model: Net: 90 Lbs. / 40.8 Kg.
Gross: 125 Lbs. / 56.7 Kg
10 kW model: Net: 70 Lbs. / 31.8 Kg.
Gross: 105 Lbs. / 47.6 Kg
5 kW model: Net: 50 Lbs. / 22.7 Kg.
Gross: 85 Lbs. / 38.6 Kg
Material: Chassis: Steel. (Anodized)
Top cover: Aluminum (Anodized)
Front panel Aluminum (Anodized)
Cooling: Forced air, side and top intake, rear exhaust
Acoustic Noise Level:
(Measured at 1 meter
from front of unit).
5 KW: < 55 dBA
10KW: < 60 dBA
15KW: < 65 dBA
Internal Construction: Modular construction.
Rear Panel
Connections: AC Power Input, DC power out, RS232, GPIB (option), Analog
Programming (option)
Rack Mounting Unit must be supported by shelf or brackets when mounted in 19"
cabinet.
No provisions for rack slides are made on instrument.

User and Programming Manual
18 XDS Series
2.5 Agency Approvals
CE Mark: GENERAL: IEC 61326-1, 1998
SAFETY: IEC 61010-1, 2001
EMC: EN55011, Class A, Group 1
IEC 61000-4-2, 1995 IEC 61000-4-4, 1995
IEC 61000-4-5, 1995 IEC 61000-4-6, 1996
IEC61000-4-8, IEC 61000-4-11, 1994
2.6 Remote Control Interfaces
Standard:
Digital RS232C Interface:
9 pin D-Shell connector
Handshake: CTS, RTS
Data bits: 8
Stop bits: 1
Baud Rate: 19200
SCPI Syntax
Analog
Input: 0 - 10 VDC / 0 – 5 VDC for 0 to full scale voltage (RPV) or
current limit (RPC) .
Input impedance 10 KOhm
Accuracy: 0.5 %
See section 5 for details.
Output: Auxiliary drive output signal.
See section 5 for details.
Remote
Inhibit Shuts down output. Factory default operation is output disabled with contact
closure or logic low input. Operation mode can be inverted to shut down when
connection is broken/interrupted using SYST:CONF and SYST:SAVE
commands.
Connects to J22 pin 1 and 14 (Iso com) on rear panel.
-IF Option: GPIB Interface is part of -IF Option
IEEE-488 IEEE-488 Interface option:
IEEE-488 (GPIB) talker listener
Subset: AH1, L3, RL2, SH1, T8
IEEE-488.2 SCPI Syntax

User and Programming Manual
XDS Series 19
2.7 Protection
Over temperature shut down
Short circuit protection
Overload protection
Over voltage
Voltage sense lines open.
2.8 Controls and Indicators
Controls: Voltage Setting: Digitally encoded rotary knob
Current Setting: Digitally encoded rotary knob
Measurement
Select Push button
Output on/off: Push button
Power on/off: Toggle Switch
Indicators: Display: Dual, seven segment LED's
LED’s for: Output on/off
Constant Current mode
Constant Voltage mode
Remote Interface state
Selected Measurement: Curr, Peak Curr, Power
2.9 Parallel Operation
Two or more XDS power supply of the same model number (voltage range and power level must
match) may be combined to create a higher power system. This requires one master unit
(default) and one or more auxiliary units (-AUX).
The maximum number of XDS units that can be paralleled is 5 (1 master + 4 auxiliary units).
The following specifications apply to multi-box XDS configurations:
Parameter
Current Range: Multiply by number of XDS units.
Current Programming:
Accuracy: Multiply by number of XDS units.
Resolution: Same as single XDS unit.
Current Sharing Within 2 % of combined current range.
Current ripple Multiply by number of XDS units

User and Programming Manual
20 XDS Series
2.10 Factory Configuration Options
All XDS models can be factory configured with the options shown below. Configuration changes
can be made in the field if needed. Refer to Chapter 5 for details on changing configuration
settings.
Option Configuration
none Stand-alone and Master operation.
-AUX Auxiliary configuration. Can be used with Master XDS unit to increase
power level.
-RPV10 Stand-alone operation with analog voltage programming, 0 – 10 V.
-RPV5 Stand-alone operation with analog voltage programming, 0 – 5 V.
-RPC10 Stand-alone operation with analog current limit programming, 0 – 10 V.
-RPC5 Stand-alone operation with analog current limit programming, 0 – 5 V.
2.11 -LC Option
The –LC option reduces the output capacitance of each DC power module. This results in
improved rise and fall times compared to a standard XDS unit. The output noise and ripple
specification is increased by a factor of 2 when adding the –LC option. This option is available
only on models with voltage ranges of 100V and below. The –LC option must be ordered at time
of initial orders. This option cannot be retrofitted.
-LC Option Output capacitance with LC option
Capacitance per 5 KW module. Standard Unit
Capacitance per 5 KW module.
30V 11200 uF 44000 uF
40V 7800 uF 30000 uF
50V 7800 uF 24000 uF
80V 3000 uF 7800 uF
100V 940 uF 4400 uF
Note: -LC option is available only on 30V, 40V, 50V, 80V and 100V output voltage range models.
This manual suits for next models
29
Table of contents
Other Argantix Power Supply manuals
Popular Power Supply manuals by other brands

Rolls
Rolls RPB486 Specifications

GW Instek
GW Instek ASD Series user manual

Conductix-Wampfler
Conductix-Wampfler 91008-111-3130923 operating instructions

Omron
Omron S8FS-G Series instruction manual

Omega Engineering
Omega Engineering iDRN-PS-1000 user guide

KOHSEL ELEPHANT
KOHSEL ELEPHANT M40 installation guide