Setting the switch-on delay of switch point 1
After pressing both control
keys simultaneously in the
menu shown, the switch-on de-
lay after reaching activation
point 1 can be set. The adjust-
able range is between 0 to 100
seconds.
To complete the setting, press both control keys si-
multaneously.
Setting the switch-off delay of switch point 1
After pressing both control
keys simultaneously in the
menu shown, the switch-off
delay after reaching deactiva-
tion point 1 can be set. The ad-
justable range is between 0 to
100 seconds.
To complete the setting, press both control keys si-
multaneously.
Setting the switch-on delay of switch point 2
(model DAS only)
After pressing both control
keys simultaneously in the
menu shown, the switch-on
delay after reaching activation
point 2 can be set. The adjust-
able range is between 0 to 100
seconds.
To complete the setting, press both control keys si-
multaneously.
Setting the switch-off delay of switch point 2
(model DAS only)
After pressing both control
keys simultaneously in the
menu shown, the switch-off
delay after reaching deactiva-
tion point 2 can be set. The ad-
justable range is between 0 to
100 seconds.
To complete the setting, press both control keys si-
multaneously.
High pressure
After pressing both control
keys simultaneously in the
menu shown, the maximum
pressure applied during meas-
urement is indicated in the dis-
play. If both control keys are
pressed again within one sec-
ond, the stored value will be
deleted.
Please note that the value will not remain
stored if the power supply (current loop) is
interrupted.
Low pressure
After pressing both control
keys simultaneously in the
menu shown, the minimum
pressure applied during meas-
urement is indicated in the dis-
play. If both control keys are
pressed again within one sec-
ond, the stored value will be
deleted.
Please note that the value will not remain
stored if the power supply (current loop) is
interrupted.
Settings in the special menu
Span adjustment
Correction of the indication in case of deviation of the
full scale of the pressure transmitter
Depending on the measuring range of the pres-
sure transmitter, a pressure reference is required!
During the service life of a transmitter, a shift of the
full scale (FS), nominal value 20,000 mA, may occur.
Resulting from this, the DAS / DASA might indicate a
signal value deviating from the set upper range limit.
The DAS/ DASA control software includes a function
for adjusting this indication:
ÆSelect the menu “PAoF”.
ÆPress both control keys simultaneously.
ÆEnter 0238 to select the special function.
ÆPress both control keys simultaneously again.