Arsin AR1230 User manual

Air Compressor Controller Unit
AR1230 USER’S MANUAL
All rights reserved. The content may be changed without prior notice. Rev. 9507
Page 1 of 14
CAUTION
For proper and safe use of the compressor, please follow all instructions and
safety precautions as identified in this manual, along with general safety
regulations and practices. Before installing and starting the compressor, read
and understand this manual.

Air Compressor Controller Unit
AR1230 USER’S MANUAL
All rights reserved. The content may be changed without prior notice. Rev. 9507
Page 2 of 14
Table of Contents
1.
General Safety Warnings .......................................................................................... 3
2.
Technical specifications ............................................................................................ 5
3.
Operation .................................................................................................................. 5
3.1. Compressor start-up ..................................................................................................... 5
3.2. Display panel................................................................................................................ 7
3.3. Panel Buttons ............................................................................................................... 7
3.4. Panel Status Lights ...................................................................................................... 8
4.
Controller installation................................................................................................. 9
4.1. Input/Output Connections ............................................................................................. 9
4.2. Wiring Diagram .......................................................................................................... 11
4.3. Controller Menu .......................................................................................................... 12
List of Tables
Table 1: Input/Output Terminals ................................................................................................. 9
Table 2: Controller Menu Items ................................................................................................ 12
List of Figures
Figure 1: Compressor Start/Stop Sequences ............................................................................. 6
Figure 2: Controller Back Cover ................................................................................................. 9
Figure 3: Controller Wiring Diagram ......................................................................................... 11

Air Compressor Controller Unit
AR1230 USER’S MANUAL
All rights reserved. The content may be changed without prior notice. Rev. 9507
Page 3 of 14
1. General Safety Warnings
Note! The instructions provided in this manual have been written to assist the operator
throughout the use and maintenance of the compressor and its controller (AR1710).
Important instructions for the safe use of the compressor warning: the inappropriate use
and poor maintenance of the compressor and its controller may cause physical injury to
the user. You are recommended to carefully follow the instructions provided hereafter to
avoid such risks.
Do not touch moving parts. Never put your hands, fingers or other parts of the
body near moving parts of the compressor.
Never use the compressor without the safety guards fitted. Never use the
compressor without all the safety guards fitted perfectly in their correct place (i.e.
panelling, belt guard, safety valve). If these parts are to be removed for
maintenance or servicing purposes, ensure that they are put back in their original
place perfectly before using the compressor again.
Always wear safety goggles. Always wear goggles or equivalent eye protection
means. Never direct compressed air towards any part of your body or that of
others.
Protect yourself against electric shocks. Avoid accidentally touching the metal
parts of the compressor with your body, such as pipes, the tank or metal parts
connected to earth. Never use the compressor where there is water or in damp
rooms.
Disconnect the compressor. Disconnect the compressor from the electric power
supply and completely discharge the pressure from the tank before carrying out
any service, inspection, maintenance, cleaning, replacing or inspection jobs of
each part.
Never move the compressor while it is connected to the electrical power supply
or when the tank is pressurized. Ensure that the main switch is turned off before
connecting the compressor to the electrical power supply.
Store the compressor and its controller appropriately. When the compressor is
not in use, it must be stored in a dry room away from atmospheric agents.
Keep the work area clean and remove any tools that are not required. Keep the
work area sufficiently ventilated. Never use the compressor in the presence of
flammable liquids or gas. The compressor may produce sparks while running. Do
not use the compressor where there may be paints, gasoline, chemical
compounds, glues and any other flammable or explosive material.
Do not wear unsuitable clothing, ties or jewellery as these may get caught up in
moving parts. Wear caps to cover your hair if necessary.

Air Compressor Controller Unit
AR1230 USER’S MANUAL
All rights reserved. The content may be changed without prior notice. Rev. 9507
Page 4 of 14
Do not disconnect the power supply plug by pulling on the cable. Keep the cable
away from heat, oil and sharp edges. Do not stand on the electrical cable or
squash it under heavy weights.
Follow the maintenance instructions. Inspect the power supply cable on a
periodic basis and if damaged it must be repaired or replaced by an authorised
service centre. Visually check the outside appearance of the compressor,
ensuring that there are no visual anomalies. Contact your nearest service centre
if necessary.
Pay attention to everything you do. Use your common sense.
Do not use the compressor if you are tired. The compressor must never be used
if you are under the effect of alcohol, drugs or medicines, which could make you
tired.
Use the compressor and its controller exclusively for the applications specified in
this instruction manual.
Operate the compressor in compliance with the instructions provided in this
manual. Do not allow children to use the compressor or those who are not
familiar with it.
Ensure that each screw, bolt and guard is firmly secured in place.
Keep the in-take grids clean. Keep the motor ventilation grids clean. Regularly
clean these grids if the work area is particularly dirty.
Operate the compressor at the rated voltage. Operate the compressor at the
voltage specified on the electric data plate. You could damage or burn-out the
motor and other electric components if the compressor is operated at a higher or
lower voltage than its rated voltage.
Never use the compressor if it is faulty. If the compressor is noisy or vibrates
excessively when running or it seems to be faulty, stop it immediately and check
its efficiency or contact your nearest authorised service centre.
Do not clean plastic parts using solvents. Solvents such as gasoline, thinners,
gas oil or other compounds that contain hydrocarbons may damage the plastic
parts. Clean them with a soft cloth and soapy water or other suitable liquids.
Turn the compressor off when it is not in use. When the compressor is not in use
turn the main on/off switch off.
Keep this instruction manual carefully and give them to personnel wishing to use
the compressor!
We reserve the right to make modifications where necessary without notice.

Air Compressor Controller Unit
AR1230 USER’S MANUAL
All rights reserved. The content may be changed without prior notice. Rev. 9507
Page 5 of 14
2. Technical specifications
Input Power AC 220V 50/60Hz
Power Consumption 7 VA
CPU AT mega 128, 16MHz
LCD 192 × 65 Graphic LCD
No. of Analog Inputs 4
No. of Digital Inputs 8
No. of Analog Output 1
Other Features:
Relay Output 16 Amp.
Main Thermistor Input
Soft Starter Output
Real Time Clock
Installation Conditions:
Installation Place Indoor
Operating Temperature 0 ~ +70°C
Storage Temperature -30 ~ +80°C
Operating Humidity 5 ~ 95% (Non- condensable)
3. Operation
3.1. Compressor start-up
In normal operation, the detected delivery pressure controls regulation of the
compressor once the compressor has been started by pushing the start button, or by a
remote start command if enabled. The controller will perform safety checks and start the
compressor if no inhibiting conditions are detected.
If a start inhibiting condition exists the compressor will not enter the started condition
and a start inhibit message is displayed. If a run inhibiting condition exists the
compressor will enter the started condition but a main motor start is inhibited; the
compressor will remain in the standby condition and a run inhibit message is displayed.
If a load request is present, in accordance with internal pressure settings or by remote
command, the main motor is started in a star/delta sequence. When running in delta
configuration, after the star/delta time (adjustable) has expired, the load delay time
(adjustable) prevents loading for a period to allow motor speed to stabilize. The load
delay time can be set to one second if required. When the load delay time has expired

Air Compressor Controller Unit
AR1230 USER’S MANUAL
All rights reserved. The content may be changed without prior notice. Rev. 9507
Page 6 of 14
the load valve output is energized and the compressor will load. If the unload pressure
setting is reached, or a remote unload command is received, the load valve output is de-
energized and the compressor will run offload for the standby run on time (adjustable)
before the main motor stops and the compressor enters Standby mode. The compressor
will load again if pressure falls below the load setting before the standby run on time
expires. If in Standby mode, a motor start sequence followed by the load delay time is
executed before loading.
In the event of a motor stop, initiated by a stop command or when entering standby
mode, a blow down timer (adjustable) is started. If a start request is made during the
blow down time the compressor will enter standby mode until the blow down time
expires. If already in standby mode and a load request is present, the compressor will
remain in standby mode until the blow down time has expired. For units with internal
pressure detection enabled, a minimum internal re-start pressure can also be set to
prevent a motor start sequence before internal pressure is vented. In the event internal
pressure fails to fall below the set minimum re-start pressure within two minutes after the
set blow down time has expired, a blow down fault is generated and the compressor will
shutdown. After an unload event a re-load timer (adjustable) is initiated that will prevent
reloading, this time can be adjusted to a minimum of one second if required. Normal
automated operation is ended by pushing the stop button, a remote stop command or in
the event of a shutdown fault.
When stopped manually, or by a remote command, the load value is de-energized and
the main motor allowed to run-on for the stop run on time (adjustable). This time can be
adjusted to a minimum of one second if required. Safety checks are made continuously,
if there is a condition detected that presents a hazardous or damaging situation an
immediate stop is performed and the reason displayed as a shutdown error message. If
a warning condition is detected an Alarm message is displayed and normal operation
continues.
Figure 1: Compressor Start/Stop Sequences

Air Compressor Controller Unit
AR1230 USER’S MANUAL
All rights reserved. The content may be changed without prior notice. Rev. 9507
Page 7 of 14
3.2. Display panel
The following information is shown on controller display panel.
1) Compressor Status & Faults
2) Oil Temperature
3) Air Pressure: Discharge air pressure is shown in barg.
4) Oil Pressure: Oil pressure of compressor crankcase is shown in barg.
5) Air Temperature: Discharge air temperature is shown in barg.
6) Time & Weekday
7) 3-Phase Power Current
8) Operation Time from 1st Startup: number of compressor running hours is shown.
9) Compressor Health Status: the compressor status is shown.
3.3. Panel Buttons
Start/Stop
The equipment starts/stops when pushing the buttons.
Program Entering to programming / enter to new menu
Reset
Reset when trip (the trip reset automatically doesn’t
need to push reset button)
Up/Down
Increase / Decrease Selected Value
Select Menu Items
Escape Exit from current menu
Info
Show operating information

Air Compressor Controller Unit
AR1230 USER’S MANUAL
All rights reserved. The content may be changed without prior notice. Rev. 9507
Page 8 of 14
3.4. Panel Status Lights
The panel Status lamps shows that the compressor components are ready for operation
and also the compressor fault or service requirements as shown in below picture.
In case of any malfunction, the fault will be shown by red light on the part of system which
has error.

Air Compressor Controller Unit
AR1230 USER’S MANUAL
All rights reserved. The content may be changed without prior notice. Rev. 9507
Page 9 of 14
4. Controller installation
4.1. Input/Output Connections
The following figure shows controller back-cover. The I/O connections are categorized
and numerated as shown in below table.
Figure 2: Controller Back Cover
Table 1: Input/Output Terminals
Cat.
Pin
Name Function Type Active state / Range
Display Output
GND RS232, GND
TXD RS232, TXD
RXD RS232, RXD
A RS485, A
B RS485, B
Power
Supply
R Main Power
N Main Power
Digital Inputs
COM Input Common Terminal
RMT Remote Input Signal
Remote (close)
ROT Rotation Fault Signal
Alarm (close)
EMS Emergency Stop Signal
Alarm (close)
MOT Motor Bimetal Fault Signal
Alarm (close)
FAN Fan Bimetal Fault Signal
Alarm (close)

Air Compressor Controller Unit
AR1230 USER’S MANUAL
All rights reserved. The content may be changed without prior notice. Rev. 9507
Page 10 of 14
Cat.
Pin
Name Function Type Active state / Range
PSW Pressure Switch Signal
Alarm (close)
TSW Thermo Switch Signal(Motor)
Alarm (close)
OIL Oil Level Sensor Signal
Alarm (close)
Analog Inputs
TMP1 Oil Temperature Sensor (1) Pt1000
-50 ~ +150
o
C
TMP1 Oil Temperature Sensor (2) Pt1000
-50 ~ +150
o
C
TMP2 Air Temperature Sensor (1) Pt1000
-50 ~ +150
o
C
TMP2 Air Temperature Sensor (2) Pt1000
-50 ~ +150
o
C
+12V Oil Pressure Transmitter (+) 4~20mA
Adjustable
PR1 Oil Pressure Transmitter (-) 4~20mA
Adjustable
+12V Air Pressure Transmitter (+) 4~20mA
Adjustable
PR2 Air Pressure Transmitter (-) 4~20mA
Adjustable
PT100 Motor Temp. Sensor 4~20mA
Adjustable
Motor
Therm Motor Thermistor 4~20mA Adjustable
Inverter
Enb Main Motor VFD
Enb Main Motor VFD
Gnd Main Motor VFD
10V Main Motor VFD
Power Outputs
COM Power Common Terminal
STU Status
AUX Auxiliary
DRN Drain
FAN Fan Motor Output
Δ Delta Contactor Output
Y Star Contactor Output
NOR Normal Contactor Output
TR1 Temp. Relay

Air Compressor Controller Unit
AR1230 USER’S MANUAL
All rights reserved. The content may be changed without prior notice. Rev. 9507
Page 11 of 14
4.2. Wiring Diagram
The following figure shows the wiring diagram of the controller.
Figure 3: Controller Wiring Diagram

Air Compressor Controller Unit
AR1230 USER’S MANUAL
All rights reserved. The content may be changed without prior notice. Rev. 9507
Page 12 of 14
4.3. Controller Menu
The following list shows the controller menus in different access levels.
Table 2: Controller Menu Items
Access
Level Menu Item Set-point Range/Description
Operator 1. USER SETTING
1.1. Contrast 35 ~ 63
1.2. Load/Unload Pressure
1.2.1. Load Pressure 2.0 ~ 7.5 bar
1.2.2. Unload Pressure 2.5 ~ 10 bar
1.3. Show Alert fault no./time/date/fault description
1.4. Reset Maintenance Info
1.4.1. Oil Filter
1.4.2. Air Filter
1.4.3. Sep. Filter
1.4.4. Oil Change
1.5. Units bar / psi
1.6. Clock
1.6.1. Time setting
1.6.2. Date setting
1.7. Buzzer Enable yes / no
1.8. Change Password
Operator 2. INSTALLATION
2.1. Times
2.1.1. Delta/Star 1 ~ 60 sec.
2.1.2. Start Time 1 ~ 60 sec.
2.1.3. Stop Time 1 ~ 60 sec.
2.1.4. Standby 1 ~ 50 min.
2.1.5. Load Delay 1 ~ 60 sec.
2.1.6. Oil Pressure Delay 0 ~ 291 sec.
2.1.7. Discharge Time 1 ~ 50 sec.
2.1.8. Condensate (Drain) On
1 ~ 50 sec.
2.1.9. Condensate (Drain) Off
1 ~ 50 min.
2.2. Pressure Setting
2.2.1. Start Pressure 0.2 ~ 3.0 bar

Air Compressor Controller Unit
AR1230 USER’S MANUAL
All rights reserved. The content may be changed without prior notice. Rev. 9507
Page 13 of 14
2.2.2. Trans. Adj. 2.0 ~ 49 bar
2.2.3. Pd Offset 0 ~ 1.5 bar
2.2.4. Pi Offset 0 ~ 1.5 bar
2.2.5. Dif. Pressure Al. 0.5 ~ 2.5 bar
2.2.6. Dif. Pressure Ft 3.0 ~ 10 bar
2.2.7. Dif. Delay 10 ~ 250 sec.
2.3. Temperature
2.3.1. Fan on 55 ~ 80
o
C
2.3.2. Fan off 120 ~ 50
o
C
2.3.3. High Temp. Fault 83 ~ 100
o
C
2.3.4. Temp. Offset -10 ~ +10
o
C
2.3.5. High Temp. Alarm 60 ~ 82
o
C
2.3.6. Min. Temp. Start -20 ~ +10
o
C
2.4. Maintenance Interval Adjustable working Hours
2.4.1. Oil Filter -
2.4.2. Air Filter -
2.4.3. Sep. Filter -
2.4.4. Oil Change -
2.5. Transducers
2.5.1. Pd #1 4 ~ 20 mA / none
2.5.2. Pi # 2 4 ~ 20 mA / none
2.5.3. Temp. Sensor Type Pt100 / Pt1000
2.5.4. Temp2 Sensor Enable / Disable
2.6. Weekly Program Week days working hour adj.
2.7. Various Networks
2.7.1. High Pressure
2.7.2. Fan Overload Active
2.7.3. Voltage Detect
2.7.4. Motor Thermistor
2.7.5. Auto Restart
2.7.6. Enable Maintenance
2.7.7. Weekly Program
2.7.8. TSW Enable

Air Compressor Controller Unit
AR1230 USER’S MANUAL
All rights reserved. The content may be changed without prior notice. Rev. 9507
Page 14 of 14
Supervisor
3. MANUFACTURER
3.1. Safety Parameter
3.1.1. Pd Max. 2.0 ~ 18 bar
3.1.2. Sep. Pressure 0.5 ~ 4.0 bar
3.1.3. Max. Temp. 80 ~ 120
o
C
3.1.4. Pi Max. 5.0 ~ 20 bar
3.2. Hour Counter shows working hours
3.3. Manufacturer Test Rotation Test
3.4. Reset Configuration Reset all settings
3.5. Operating Mode Select Start Command
3.6. Relay Program1 (MF1) Warning/Fault/F+W/Heater/Drain
Valve/Fan/Standby/Main Motor
Run/Load&Unload/Start/2
nd
Fan/Disch. Sep. Valve
3.7. Relay Program2 (MF2) Warning/Fault/F+W/Heater/Drain
Valve/Fan/Standby/Main Motor
Run/Load&Unload/Start/2
nd
Fan/Disch. Sep. Valve
3.8. Relay Program3 (MF3) Fault/Warning