Arthur Grillo DS85P User manual

Doc.-no.:DS85P_01_EN issue: 09/2018
Installation and operation manual
DS85P – DIFFERENTIAL PRESSURE SENSOR
Low pressure sensor with analogue
output and selectable measuring ranges

3
Doc.-no.:DS85P_01_EN issue: 09/2018
Manufacturer:Arthur Grillo GmbH
Am Sandbach7
40878 Ratingen
Phone:+49 21 02 – 47 10 22
Fax:+49 21 02 – 47 58 82
E-Mail: info@grillo-messgeraete.de
Website: www.grillo-messgeraete.de
Webshop: www.sensor-store.de
Issue:09/2018
Doc.-No.: DS85P_01_DE
This documentation including all parts is protected by copyright. Any utilization or modi-
fication other than permissible under the strict limitations of copyright law is prohibited
and liable to prosecution without the approval of the Arthur Grillo GmbH. This applies in
particular to duplications, translations, microfilming and storage and processing in elec-
tronic systems.

4
Doc.-no.:DS85P_01_EN issue: 09/2018
Table of content
1. General safety instructions.................................................................... 5
1.1 Signal words for safety instructions ........................................................ 5
1.2 Pictograms and symbols used................................................................ 5
1.3 General notes.......................................................................................... 5
2. Product description ................................................................................ 6
2.1 Intended use ........................................................................................... 6
2.2 Functional description............................................................................. 6
3. Montage.................................................................................................... 6
3.1 Dimension ............................................................................................... 7
3.2 Wall mounting ......................................................................................... 7
4. Start-up..................................................................................................... 7
4.1 Pressure connections.............................................................................. 7
4.2 Electrical connection ............................................................................... 7
5. Measuring range selection..................................................................... 8
6. Error limits ............................................................................................... 9
7. Maintance................................................................................................. 9
8. Warranty................................................................................................... 9
9. Disposal ................................................................................................. 10
10. Technical specifications....................................................................... 10
10.1 CE- label.............................................................................................. 11

5
Doc.-no.:DS85P_01_EN issue: 09/2018
1. General safety instructions
1.1 Signal words for safety instructions
The safety instructions in this operating manual are intended to avert danger. They are
contained in the operating instructions before any action / work / activity is described
which could result in a hazard.
CAUTION
Identification of a low-risk hazard that may result in property dam-
age or minor injury.
.NOTICE.
Signal word for an important information about the product, which
should be drawn special attention to.
.Hazard word.
Type of hazard
Hazard source
Hazard prevention
1.2 Pictograms and symbols used
The following characters are used in this manual:
General danger symbol (dan-
ger, warning, caution)
General information
1.3 General notes
.NOTICE.
These operating instructions contain instructions for the correct in-
stallation and operation of the differential pressure regulator and
are intended exclusively for the operator and authorised specialist
personnel. Observing the operating instructions helps to avoid
dangers and downtimes.

6
Doc.-no.:DS85P_01_EN issue: 09/2018
2. Product description
The differential pressure sensor DS85P is used to measure small differential pressures
of non-aggressive gases, especially air.
2.1 Intended use
The area of application is, for example, air conditioning technology, room pressure mon-
itoring or filter control. A signal of 0...10 V DC is available to the user as an analogue
output. The area of application is, for example, in air-conditioning technology for the con-
trol of fans, room pressure monitoring or filter control.
2.2 Functional description
A soft silicone diaphragm with a corresponding measuring spring is used as the sensor,
which is fine-tuned to each measuring range. The deflection of the diaphragm is meas-
ured contactless with a differential transformer and converted into a standardized output
signal by the electronics. The ranges from 0...50 Pa to 0...6000 Pa are covered by three
measuring range groups, and in each device group four calibrated measuring ranges
can be selected via a 2-pole DIP switch.
3. Montage
The differential pressure sensor DS85P is designed for wall mounting. Please consider
the following factors when selecting the location:
•The mounting surface must be sufficiently firm and vibration-free.
•The environment must comply with the climatic conditions specified in the
technical data.
VORSICHT
Material damage
Read the operating instructions carefully before installation and
use. The device may only be connected and used by experienced
specialist personnel.

7
Doc.-no.:DS85P_01_EN issue: 09/2018
3.1 Dimension
All specifications in mm.
3.2 Wall mounting
1. Hold the DS85P against the wall, mark the mounting holes.
2. Drill fixing holes for sufficiently dimensioned screws or dowels.
3. Press in the dowels.
4. Insert the fixing screws through the screw channels of the housing screws so that
the screws protrude from the rear of the housing.
5. Place the housing with the screws exactly on the fixing holes with the dowels.
6. Tighten the screws.
4. Start-up
4.1 Pressure connections
Connect all pressure connections properly with plastic hoses (inner diameter 5mm).
4.2 Electrical connection
The differential pressure sensors are electrically connected via a three wire 50 cm long
colour-coded cable.

8
Doc.-no.:DS85P_01_EN issue: 09/2018
5. Measuring range selection
Four measuring ranges can be selected via a 2-pole DIP switch under the rubber plug
in the front cover.
Device typ
DS85P
200
DE85P
1000
DS85P
6000
Measuring
DIP-switch
range
1
2
MB1:
off
off
0…200 Pa
0…1000 Pa
0…6000 Pa
MB2:
on
off
0…150 Pa
0…500 Pa
0…4000 Pa
MB3:
off
on
0…100 Pa
0…300 Pa
0…3000 Pa
MB4:
on
on
0…50 Pa
0…200 Pa
0…2000 Pa

9
Doc.-no.:DS85P_01_EN issue: 09/2018
6. Error limits
Zero
deviation
Final value
deviation
Linearity
deviation
Resolution hysteresis
DS85P-200
0…200 Pa
± 0.5 %
± 0.5 %
± 0.25 %
0.1 %
1 %
0…150 Pa
± 0.75 %
± 0.6 %
± 0.4 %
0.2 %
0.7 %
0…100 Pa
± 1 %
± 0.7 %
± 0.5 %
0.2 %
0.5 %
0…50 Pa
± 2 %
± 1 %
± 1 %
0.3 %
0.5 %
DE85P-1000
0…1000 Pa
± 0.5 %
± 0.5 %
± 0.25 %
0.1 %
0.2 %
0…500 Pa
± 0.7 %
± 0.7 %
± 0.5 %
0.2 %
0.2 %
0…300 Pa
± 0,9 %
± 0.9 %
± 0.9 %
0.3 %
0.2 %
0…200 Pa
± 1 %
± 1 %
± 1.25 %
0.3 %
0.2 %
DS85P-6000
0…6000 Pa
± 0.5 %
± 0.5 %
± 0.25 %
0.1 %
0.2 %
0…4000 Pa
± 0.7 %
± 0.7 %
± 0.4 %
0.15 %
0.2 %
0…3000 Pa
± 0.9 %
± 0.9 %
± 0.6 %
0.2 %
0.2 %
0…2000 Pa
± 1 %
± 1 %
± 0.75 %
0.25 %
0.2 %
Temperature drift (related to the respective highest measuring span)
Zero point:
± 0.2 % / K
End value:
± 0.3 % / K
7. Maintance
The DS85P contains no wearing parts or consumables. Maintenance is not necessary.
Upon request, Arthur Grillo GmbH offers an annual calibration with works certificate. In-
formation on this can be obtained from:
Arthur Grillo GmbH
Am Sandbach 7
40878 Ratingen
Phone: 0 21 02 - 47 10 22
Fax: 0 21 02 - 47 58 82
E-Mail: info@grillo-messgeraete.de
8. Warranty
Warranty and liability claims for personal property damage are excluded if they are at-
tributable to one or more of the following causes:
•Unapproved use of the device.
•Improper installation, start-up, operation and maintenance of the device.
•Unauthorized structural changes to the device beyond the intended purpose.
•Improperly carried out repairs.
•Disasters caused by foreign bodies and force majeure.

10
Doc.-no.:DS85P_01_EN issue: 09/2018
9. Disposal
When disposing of electronic components and devices, observe the legal regulations in
the country of use.
10.Technical specifications
PERFORMANCE:
Overload safety:
0,2 bar
Static pressure:
Max. 0,2 bar
Zero-point calibration:
Adjustable via REED contact, no cyclic zero-point
calibration required
Reaction time:
Immediately
ACCURACY / ERROR LIMITS:
Zero offset:
See chapter 6. error limits
Sum of linearity and
hysteresis:
See chapter 6. error limits
Temperature drift measuring
span:
Due to 4 measuring ranges in 3 measuring groups
TECHNICAL SPECIFICATIONS:
Operating mode:
measurement mode
Medium:
Air or non-aggressive gases
Measuring sensor:
Electromechanical diaphragm movement
Measurement unit:
Pa
Smallest measuring span:
0…50 Pa (0,5 mbar)
Largest measuring span:
0…6000 Pa (60 mbar)
Measuring ranges:
0…50 Pa (0,5 mbar), 0…200 Pa (2 mbar),
0…500 Pa (5 mbar), 0...1000 Pa (10 mbar),
0…2000 Pa (20 mbar), 0…4000 Pa (40 mbar),
0…6000 Pa (60 mbar)
Measuring range selection:
Yes via 2-pole DIP switches
Characteristic:
Linear
Ambient temperature:
-10...+50 °C
Storage temperature:
-25...+60 °C
PHYSICAL:
Case:
Ultramid
Dimensions:
∅70 mm, depth 50 mm
Weight:
approx. 90 g
Protection class:
IP 54 according EN 60529

11
Doc.-no.:DS85P_01_EN issue: 09/2018
Electrical connections:
3-core cable, color-coded, electronics protected
against reverse polarity
Pressure connections:
hose nozzles 4 mm ø
Operating position:
Vertical, position dependence for 90° rotation ap-
prox. 25 Pa
ELEKTRONIK:
Supply voltage:
15...30 Vdc; 24 Vac (+/-15%)
Current consumption
Approx. 10 mA @ 24 Vdc
Output:
0...10 V; three-wire circuit
CONFORMITY:
EMC:
EN 61000-6-2, EN 61000-6-3, CE-Zeichen
RoHS:
Entspricht RoHS-Richtlinie 2011/65/EU
10.1 CE- label
As electrical equipment, the DS85P falls within the scope of the 2004/108/EC Directive
(EMC Directive). The following standards have been applied within the scope of the
EMC Directive:
DIN EN 61000-6-2:2006-03
corrigendum 1:2011-06
Electromagnetic compatibility (EMC) - Part 6-2:
Generic standards - Immunity for industrial environ-
ments
DIN EN 61000-6-3:2011-09
Electromagnetic compatibility (EMC) - Part 6-3:
Generic standards - Emission for residential, com-
mercial and light-industrial environments
You can request the declaration of conformity here:
Arthur Grillo GmbH
Am Sandbach 7
40878 Ratingen
Telefon: 0 21 02 - 47 10 22
Telefax: 0 21 02 - 47 58 82
E-Mail: info@grillo-messgeraete.de