Page 5Dali-Scope User Guide
If new devices are added to an existing
network, short addresses already in use will
be avoided.
The commissioning process is separate to the
conguration of the devices and only needs
to be done once.
Dali-Scope Operation
Dali-Scope has six menu options:
yREAD - Read incoming DALI commands
yTEST - Transmit DALI levels
ySTATUS - Displays properties of a xture
yADDRESS- Shows & congures current
channel/group assignment
yCONFIG - Changes congurable
properties of a xture
yADVANCED CONFIG - Dali-Scope
setup options
Power
Power is provided by two AA batteries.
Approximate battery life is 12 hours continuous
and 6 months on standby. Dali-Scope can be
powered using rechargeable batteries.
Dali-Scope features an automatic power o
timer to conserve battery life. This may be
congured in the ADVANCED CONFIG menu.
Switch on by pressing the key. To switch
o, hold the key for 5 seconds.
During power on, Dali-Scope automatically
searches for DALI devices. This search will
only include devices that have been given
a channel number / short address. To nd
devices that are uncongured, please refer
to the ADDRESS section.
Important: Dali-Scope will not provide power
onto the Data Bus. Please ensure a DALI Bus
PSU is present such as a Rail-PSU-D4.
Note: Only one controller should be present
on the DALI circuit at any time. When using
the READ menu options, Dali-Scope does not
transmit data messages so can be added to
the DALI circuit at the same time as a DALI
controller.
READ
TEST
There are 3 options available:
yCURRENT VALUE: Displays the value of
the command or level that is transmitted by
the controller. This value will then be held
until the READ button is pressed again.
yLATEST VALUE: Displays the latest
values that are transmitted on the circuit.
The screen will refresh each time a new
value is received.
(The two options above display all the
information received. This will include control
commands).
yDISPLAY STATS: Displays the number of
commands being sent (Tx) and received
(Rx) on a DALI circuit.
(Note: The counter resets to 0 when it reaches
256).
Use the TEST button to scroll through the
dierent sub menus below:
yRIG: [CHANNEL / GROUP / SCENE] –
Sends a single value
- UP or DOWN used to control the value
(0 -100%)
- LEFT or RIGHT used to select the channel
/ group / scene index
- LEFT (hold) then RIGHT used to select
between channel / group / scene
yWALK: [CHANNEL / GROUP / SCENE] –
Walks between start and end index
- UP or DOWN used to select start index
- LEFT or RIGHT used to select end index
- LEFT (hold) then RIGHT used to select
between channel / group / scene
yALL: [BROADCAST] – All devices at a
specic level
- UP or DOWN used to select level (0 –
100%)