DynAmp LKP Series Setup guide

DynAmp, LLC
3735 Gantz Road Phone +1 614.871.6900 www.dynamp.com
Grove City, Ohio 43123 USA Fax +1 614.871.6910 [email protected]
Model LKP-45, LKP-60, & LKP-80
DIRECT CURRENT METERING SYSTEMS
Installation, Operation and Service Manual
Manual Item No. 041736
Rev. N

Installation, Operation and Service Manual LKP Series
© 2020 DynAmp, LLC Page ii
041736 N
This Page is Intentionally Blank

Installation, Operation and Service Manual LKP Series
© 2020 DynAmp, LLC Page iii
041736 N
DYNAMP, LLC WARRANTY
Items and components manufactured by DynAmp, LLC for permanent installation are
warranted to be free from defects in material and workmanship for a period of two (2) years
from the date of shipment.
Items and components manufactured by DynAmp, LLC for portable and temporary use in
more than one location are warranted to be free from defects in material and workmanship
for a period of eighteen (18) months from the date of shipment.
Extended warranties may be available for purchase for some products. Extended
warranties are provided on a serial number by serial number basis as noted on DynAmp’s
original invoice and/or packing list.
Items and components not manufactured and resold by DynAmp, LLC are warranted by
their manufacturer.
Warranty repair shall be, at DynAmp’s option, in the form of repair or replacement of the
defective items or components. Concerning warranty repairs, DynAmp, LLC will be
responsible for DynAmp provided time, material and transportation costs (shipping or
travel). Actual method of warranty repair / correction will be determined by DynAmp, LLC
at DynAmp’s sole option. Such warranty repair shall constitute a fulfillment of all DynAmp,
LLC liabilities in respect to said items and components. In no event shall DynAmp, LLC be
liable for consequential damages.
Information in this document is subject to change without notice.
© 1997, 1998, 1999, 2000, 2002, 2003, 2004, 2006, 2008, 2011, 2016, 2018, 2020 DynAmp, LLC.
All rights reserved.
Reproduction in any manner whatsoever for purposes other than installation, operation, or service by
the purchaser or end user without the written permission of DynAmp, LLC is strictly forbidden.
This manual is part of the complete set of product documentation that includes installation, operation,
and service instructions, drawings and test results. Users should evaluate the information in the
context of the complete set of product documentation and their particular application. DynAmp, LLC
assumes no liability for any incidental, indirect, or consequential damages arising from the use of this
documentation.
While all information presented is believed to be reliable and in accordance with accepted
engineering practices, DynAmp, LLC makes no warranties as to the completeness of the information.
All trademarks used in association with LKP are trademarks of DynAmp, LLC.

Installation, Operation and Service Manual LKP Series
© 2020 DynAmp, LLC Page iv
041736 N
This Page is Intentionally Blank

Installation, Operation and Service Manual LKP Series
© 2020 DynAmp, LLC Page v
041736 N
The LKP Series 10 Channel includes the LKP-100 Metering Unit. This Metering Unit
conforms to the latest European directives and standards concerning safety and
electromagnetic compatibility.
Application of Council Directive(s):
73/23/EEC, 89/336/EEC and 93/68/EEC.
Standards to which conformity is declared:
•EN50081-2 utilizing method EN55011: Radiated and Conducted Emissions for Heavy
Industrial Environments, Class A.
•EN50082-2: Radiated and Conducted Immunity Tests for Heavy Industrial
Environments.
Safety Standards:
•EN 61010-1: Safety Requirements for Electrical Equipment for Measurement, Control,
and Laboratory Use.
Note
According to EN 50082, the manufacturer must state the degradation of performance level acceptable during
immunity tests. Unless otherwise noted in the manual or data sheet, DynAmp limits degradation during
immunity tests for this equipment to < 0.5% FS for A-criterion tests.

Installation, Operation and Service Manual LKP Series
© 2020 DynAmp, LLC Page vi
041736 N
This Page is Intentionally Blank

Installation, Operation and Service Manual LKP Series
© 2020 DynAmp, LLC Page vii
041736 N
TABLE OF CONTENTS
Paragraph Title Page
DYNAMP, LLC WARRANTY_____________________________________________________III
TABLE OF CONTENTS________________________________________________________ VII
HAZARD WARNING!__________________________________________________________ IX
SAFETY ____________________________________________________________________ XI
DYNAMP, LLC CUSTOMER SUPPORT & SERVICE ASSISTANCE____________________ XIII
MANUAL REVISIONS ________________________________________________________XV
1. HANDLING AND STORAGE................................................................................................1
2. PRODUCT DESCRIPTION...................................................................................................3
2.1 SYSTEM OVERVIEW _________________________________________________ 3
2.2 ADDITIONAL MEASURING HEAD DETAIL ________________________________ 3
2.3 ADDITIONAL METERING UNIT DETAIL___________________________________ 3
2.4 INTERCONNECTION CABLE DETAIL ____________________________________ 3
2.5 ELECTRICAL________________________________________________________ 4
3. SPECIFICATIONS................................................................................................................5
4. INSTALLATION....................................................................................................................7
4.1 HANDLING PRECAUTIONS ____________________________________________ 7
4.2 MAGNETIC CONSIDERATIONS: MEASURING HEAD _______________________ 7
4.3 MEASURING HEAD INSTALLATION _____________________________________ 8
4.4 INSTALLATION CONSIDERATIONS ____________________________________ 10
4.5 INSTALLATION PRECAUTIONS (LIVE BUS)______________________________ 12
4.6 COMPLETING THE MEASURING HEAD INSTALLATION____________________ 12
4.7 METERING UNIT INSTALLATION ______________________________________ 16
4.8 METERING UNIT WIRING ____________________________________________ 17
4.9 INITIAL SYSTEM CHECKOUT _________________________________________ 17
4.10 MAGNETIC CENTERING _____________________________________________ 18
4.11 REVERSING CABLE EXIT DIRECTION ON MEASURING HEAD ______________ 20
5. THEORY OF OPERATION.................................................................................................23
5.1 GENERAL _________________________________________________________ 23
5.2 MAGNETIC SENSOR (NULL DETECTOR)________________________________ 23
5.3 SYSTEM DESCRIPTIONS_____________________________________________ 23
5.4 CIRCUIT FUNCTIONS________________________________________________ 24
5.5 METERING UNIT____________________________________________________ 25
5.6 POWER SUPPLIES__________________________________________________ 25
5.7 SYNC, PLL, AND RAMPS _____________________________________________ 25
5.8 ERROR AMPLIFIERS ________________________________________________ 25
5.9 COMPARATORS AND PULSE GENERATOR _____________________________ 25
5.10 PULSE TRANSFORMER DRIVERS _____________________________________ 26
5.11 OUTPUT CIRCUIT___________________________________________________ 26
5.12 ACCURACY DIAGNOSTICS (OPTIONAL)________________________________ 26

Installation, Operation and Service Manual LKP Series
© 2020 DynAmp, LLC Page viii
041736 N
6. MAINTENANCE & SPARE PARTS ....................................................................................29
6.1 PERIODIC MAINTENANCE____________________________________________ 29
6.2 ANNUAL MAINTENANCE _____________________________________________ 29
6.3 RECOMMENDED CALIBRATION VERIFICATION INTERVALS _______________ 30
6.4 SPARE PARTS ORDERS - ROUTINE OR EMERGENCY ____________________ 31
6.5 RECOMMENDED SPARE PARTS ______________________________________ 31
7. RELATED TECHNICAL BULLETINS.................................................................................33
8. DRAWINGS........................................................................................................................35
FIGURES & TABLES_____________________________________________________________
Figure # Title...................................................................................................................Page
Figure 4.1 General Guidelines for Locating Measuring Heads .....................................................8
Figure 4.2 Window Insulation Nomenclature Typical For LKP Series Measuring Heads .............9
Figure 4.3 Proper Lifting Technique...........................................................................................12
Figure 5.1 Magnetic Null Detector Diagram................................................................................23
Figure 5.2 Functional Diagram of Four-Channel System............................................................24
Table 3.1 LKP Series 6 & 8 Channel Specifications....................................................................5
Table 3.2 Typical Error At Zero Bus Current*..............................................................................6
Table 4.1 (A) Measuring Head Resistance Chart LKP-45 ........................................................14
Table 4.1 (B) Measuring Head Resistance Chart LKP-60 ........................................................15
Table 4.2 Measuring Head Resistance Chart LKP-80...............................................................16
Table 4.3 Channel Voltage Measurements Form: LKP-45 & LKP-60 ........................................21
Table 4.4 Channel Voltage Measurements Form: LKP-80 ........................................................22
Table 6.1 Spare Parts List* .......................................................................................................32
Table 7.1 Technical Bulletin List................................................................................................33
Table 8.1 Drawing List...............................................................................................................35

Installation, Operation and Service Manual LKP Series
© 2020 DynAmp, LLC Page ix
041736 N
HAZARD WARNING!
Symbol Identification:
General definitions of safety symbols used on equipment and manual.
Caution/Warning: Refer to accompanying documents for instructions.
The CE mark proves the compliance of the equipment with the requirements
of the directives.
All installation, maintenance and service must be performed by qualified
technicians who are familiar with the warnings and instructions of this manual.
The enclosure doors must remain closed at all times during operation to ensure
safety of personnel. A set of keys are provided for locking the doors. Only
authorized personnel or technicians should be allowed to open and service the
unit.
Disconnect power to the system before servicing or replacing fuses.
Use of the equipment in a manner not specified by the manufacturer can impair
the protection provided within.
DynAmp, LLC does not assume liability for the customer’s failure to comply with
the rules and requirements provided in this manual.
GENERAL
HAZARDOUS
VOLTAGE
This equipment is designed to be connected to hazardous electric voltages.
Ignoring the installation precautions and warnings can result in severe personal
injury or equipment damage.
To avoid the risk of electrical shock or fire, the safety instructions and
guidelines in this manual must be followed. The electrical specifications must
not be exceeded and the unit must be installed according to directions
provided.
INSTALLATION
This equipment is intended for indoor use only. It should be mounted in a well-
ventilated area, away from high heat, dust, and corrosive atmosphere. The
ambient temperature must not exceed the specified limits.
For mounting considerations that fall outside the recommended specifications
provided in this manual, the factory should be contacted for approval.
This unit is rated for installation category III and pollution degree 2.

Installation, Operation and Service Manual LKP Series
© 2020 DynAmp, LLC Page x
041736 N
This Page is Intentionally Blank

Installation, Operation and Service Manual LKP Series
© 2020 DynAmp, LLC Page xi
041736 N
SAFETY
This equipment is designed to be connected to hazardous electric voltages. Ignoring
the installation precautions and warnings can result in severe personal injury or
equipment damage. Also, the equipment is heavy and requires special handling
procedures to ensure the safety of both personnel and equipment itself. The following
are general guidelines that should be followed when installing, operation and servicing
the Metering Unit and Measuring Head.
•All installation, maintenance and service must be performed by qualified technicians
who are familiar with the warnings and instructions of this manual.
•Always follow all local and plant safety procedures.
•Service must be performed by qualified technicians only. If use of an oscilloscope
becomes necessary during servicing, the scope must be floating and not grounded.
The Metering Unit is isolated from the mains via the power transformers. If a
grounded scope is used, a hazardous condition is created since current will flow
through the probe to ground.
•Units are not intrinsically safe. Do not place in explosive atmospheres
•Do not place in the rain, or under water, or submerge any part of the Measuring
Head or Metering Unit. The Measuring Heads are splash proof but are not
waterproof.
•The surface on which the Measuring Head is mounted must be sound and capable
of supporting the Measuring Head. Fasteners used must be capable of supporting
the weight of the Measuring Head.
•Make sure that the cables are disconnected from the Measuring Head during
installation.
•The Measuring Heads are supplied with connector covers, which must be used
whenever the Measuring Head cables are disconnected from the Measuring Head.
The covers are necessary to prevent dust and water from entering the Measuring
Heads. The covers also prevent fingers from contacting the connector pins during
installation, which can carry hazardous voltages if the Measuring Head is installed
on a live bus.
•If the installation is to be made on a "live" bus, the Measuring Head cables must be
disconnected from the Measuring Head. A condition hazardous to the Measuring
Head and any person handling un-insulated cable-lead terminals will result if metal
parts of the Measuring Head contact the bus, or sudden changes in the bus current
occur. Personal protective gear should be worn when reconnecting cable back to
Measuring Head. Please refer to “Installation Considerations” section 4.4 for
Measuring Head storage on a live bus.
•Measuring Head should be electrically isolated from the bus bars. A ¼” (6mm)
minimum distance between the bus and window insulation should be maintained.
This will insure electrical isolation of the Measuring Head structure from the bus.
The Measuring Head itself is grounded via the cables to the Metering Unit. Refer to
the “Installation Considerations” section of the manual for more details.

Installation, Operation and Service Manual LKP Series
© 2020 DynAmp, LLC Page xii
041736 N
•An external circuit breaker or fuse with proper rating is required for branch circuit
protection when wiring the main circuit to this Metering Unit. Each Metering Unit
must have its own breaker. Use a wire and breaker or fuse (time-delay) sized
adequately for the maximum burden of 20 VA/kA of measured current. The wire
should have an insulation rating of 600Vac and 80°C minimum temperature rating.
•Replace fuses with correct type, size and value. All channel fuses are Time lag
MDA (or MDL) style 3AB (or 3AG) ¼” by 1 ¼” (6.3 mm x 32mm), 250 Volt. Refer to
the servicing instructions or spare parts list for more information on replacement
fuses. Do not bypass the fuses or modify the electronics. Disconnect power to the
System before replacing fuses. Failure to follow these instructions will result in
intermittent operation and premature failure and will void the warranty.
•Metering Unit enclosure doors and module covers must be present and remain
closed at all times during operation to insure safety of personnel. A set of keys is
provided for locking enclosure doors. Only authorized personnel or technicians
should be permitted to open and service the unit.
•Bus current must be zero when taking resistance measurements.
•Use of the equipment in a manner not specified by the manufacturer can impair the
protection provided within.
DynAmp, LLC does not assume liability for the customer’s failure to comply with the rules
and requirements provided in this manual.

Installation, Operation and Service Manual LKP Series
© 2020 DynAmp, LLC Page xiii
041736 N
DYNAMP, LLC CUSTOMER SUPPORT & SERVICE ASSISTANCE
For further assistance, contact DynAmp, LLC Customer Support at:
Americas:
Telephone: +1 614.871.6900 Fax: +1 614.871.6910
8:00 AM to 5:00 PM USA Eastern Time
From first Sunday in November to second Sunday in March – 13:00 GMT to 22:00 GMT
From second Sunday in March to first Sunday in November – 12:00 GMT to 21:00 GMT
After Hours Critical Service Emergency:
Telephone: +1 614.871.6906
5:00 PM to 8:00 AM USA Eastern Time
From first Sunday in November to second Sunday in March – 22:00 GMT to 13:00 GMT
From second Sunday in March to first Sunday in November – 21:00 GMT to 12:00 GMT
Central e-mail:
DynAmp web:
www.dynamp.com

Installation, Operation and Service Manual LKP Series
© 2020 DynAmp, LLC Page xiv
041736 N
This Page is Intentionally Blank

Installation, Operation and Service Manual LKP Series
© 2020 DynAmp, LLC Page xv
041736 N
MANUAL REVISIONS
Page
Change
Reason For Revision
Date
all
Rev NEW
6/97
10
Rev A
Installation Notes
12/97
12
Rev A
Installation Considerations
14, 15
Rev A
Measuring Head Resistance Chart
33
Rev A
Spare Parts List
35
Rev B
Drawing list
12/97
All
Rev C
Safety, Installation, & Drawing list
5/98
14,15
Rev C1
Typing Error - Table 4-1 & 4-2
9/99
All
Rev D
Warranty, Safety, Installation Considerations,
Maintenance & Spare Parts, Added Related Technical
Bulletins section
05/00
29, 36
Rev E
Updated Accuracy Diagnostics & Spare Parts section
04/02
iii, 7
Rev F
Updated Warranty and Installation paragraph
10/03
All
Rev G
Update to DynAmp, LLC, update Table 2 – Measuring
head resistance chart LKP-80
11/04
vii, 1, 34,
36
Rev H
Update fuse precautions per ECR 1304
07/06
41
I
ECO 3166 update accuracy diagnostics drawings/list
09/08
All J PAR 10245 – Handling & Storage, ECR 1440-
Calibration Intervals / New Manual Format 05/11
1,2,13,19
K
ECO 3307 – Section 1 Safety, Installation Precautions,
Metering Unit Wiring
10/16
2,23,24,36,
41 L ECR 1955 / ECO 3330 – Update fuse value for LKP-45 -
Safety, Change Note in Table 5.3 & 5.4, Spare parts list
7.1,and Drawing list size changes 9.1 11/16
6, 24, 35,
iii, xiii
M
ECO 3350 – Add head assembly torque, Add verbiage
to Circuit Function Description 5.4, Add drawing
revisions in Table 8.1, Remove obsolete MVI & SVI
options on 83C108255, Update title blocks in drawings,
and General verbiage updates for Customer Support &
Service and Warranty Page.
10/18
9, 35
N
ECO 3350 – Update verbiage under Section 4.3 and
update drawing 02A108033 revision in Table 8.1
01/20

Installation, Operation and Service Manual LKP Series
© 2020 DynAmp, LLC Page xvi
041736 N
This Page is Intentionally Blank

Installation, Operation and Service Manual LKP Series
© 2020 DynAmp, LLC Page 1
041736 N
1. HANDLING AND STORAGE
DynAmp products are engineered and manufactured for use in industrial environments.
However, they contain sensitive electronic and mechanical components which may be
damaged and fail if not handled and stored properly. All products must be handled and
stored with the same care as any precision measurement instrument. Severe bumps or
jolts may damage internal parts and cause malfunction or premature failure. DynAmp
products are designed and assembled with conformal coating, shock mounting, and
environmental seals, when appropriate or when specified. However, this protection
requires that the product must be properly installed and operational before the protection is
fully functional. Therefore, adequate protection from humidity, shock, and temperature
must be provided during handling and storage prior to installation.
The handling and storage of equipment must be sufficient to meet the storage temperature
and humidity specifications of the product and to prevent any condensation or contact with
water or any other liquid. The storage location and container or crate must provide
adequate protection from precipitation (rain, snow, ice) and direct water contact. Adequate
shelter must be provided to prevent the accumulation of precipitation (rain, snow, ice) and
water which can lead to the deterioration or failure of shipping containers or crates and
cause water ingress. Storage in coastal or industrial areas subject to salt-laden or
corrosive air or areas of wind-driven sand or other abrasive dust must be adequate to
prevent the deterioration or failure of shipping containers or crates and cause ingress.
Frequent inspection of storage areas and storage containers or crates is required to ensure
proper storage conditions are being maintained.
If the shipping container or crate is opened and/or the equipment is removed for inspection
prior to installation, the equipment must be repackaged in the original undamaged
container or crate in the same manner as it was shipped to prevent environmental damage
or placed in a storage location that meets the required environmental and storage
conditions.
General product storage temperature and humidity requirements:
Storage Temperature: -40 to 70°C
-40 to 158°F
Storage Humidity: Maximum 85%, non-condensing
DynAmp, LLC does not assume liability for the customer’s failure to comply with handling
and storage requirements.
For further assistance, contact DynAmp customer support.

Installation, Operation and Service Manual LKP Series
© 2020 DynAmp, LLC Page 2
041736 N
This Page is Intentionally Blank

Installation, Operation and Service Manual LKP Series
© 2020 DynAmp, LLC Page 3
041736 N
2. PRODUCT DESCRIPTION
2.1 SYSTEM OVERVIEW
The DynAmp, LLC LKP Series 6 & 8 channel are systems for accurately measuring direct
current in a bus. The Models in this series are: LKP-45 and LKP-60 (6 channel), and LKP-
80 (8 channel). Each model consists of a two-piece Measuring Head, a Metering Unit, and
two multi-conductor cables. For the sake of simplicity throughout this manual, the LKP 6
and 8 channel Metering Units might be referred to as the LKP system, or LKP metering
system.
2.2 ADDITIONAL MEASURING HEAD DETAIL
A magnetic core encircles the bus passing through the center of the Measuring Head.
Magnetic null detectors are mounted in air gaps in the core. Each null detector is flanked
by coils located on the magnetic core.
The Measuring Heads are constructed of cast aluminum with a tough epoxy finish,
insulation from the bus being provided by a 3/8 in. (9.5mm) layer of high-grade epoxy. The
Measuring Head halves are easily joined around the bus by use of 8 bolts.
The LKP-60 and LKP-80 Measuring Heads are provided with mounting feet as standard
equipment. The mounting feet facilitate the mounting of the Measuring Heads vertically on
the floor or on a platform. The LKP-45 can be provided with mounting feet or with a bus
bar mounting kit (both are optional).
2.3 ADDITIONAL METERING UNIT DETAIL
The Metering Unit is housed in a standard NEMA 12 enclosure (IP54). In addition to the
electronic circuitry (housed within two modular units), the Metering Unit contains terminals
for all external connections. The Metering Unit requires 120/240 Vac (other voltages
available), 50 or 60 Hz power. Burden on the supply circuit will not exceed 2400 VA. A
thermo-magnetic circuit breaker is mounted on the inside of the enclosure and serves as
the power on-off control.
2.4 INTERCONNECTION CABLE DETAIL
A standard 33-foot (10 meter) interconnecting cable is supplied with each system (longer
cable lengths are available - consult the factory for details). Each of the individual
conductors is tagged with a numbered label corresponding to a terminal block connection,
providing an easy hookup to the Metering Unit. Keyed connectors are provided on the
Measuring Head side of the cables to ensure correct hookup.

Installation, Operation and Service Manual LKP Series
© 2020 DynAmp, LLC Page 4
041736 N
2.5 ELECTRICAL
Six outputs are provided by the system:
1. A standard voltage output exists at terminals TS2-6 and TS2-7 inside the Metering Unit.
The output voltage is 1mV/kA for model LKP-80, and 10mV/kA for models LKP-45 and
LKP-60.
2. An additional voltage at TS2-8 and TS2-9, when an optional shunt is installed.
3. A current output of 1 Adc per 5 kA of bus current, at TS2-4 and TS2-5. The current
output is available by removing a jumper connected across the terminals (do not
remove the jumper while the system is energized). Maximum allowable voltage drop
across the terminals is 15 Vdc at the normal maximum current output of the bus.
4. A normally-open (N.O.) relay contact for the Metering Unit over-temperature alarm, rated
at 120 Vac, 6 A, at TS2-12 and TS2-13.
5. A normally closed relay contact for accuracy diagnostics output at TS2-12 through TS2-
14. This feature is only available when the accuracy diagnostics option is ordered.
6. Optional isolated shunt output. Scaling is per customer order: 0-10V, 4-20mA