Installation
Manual
Contents
- General description
- Accessories
- Installation
- Electrical connections
- Electric safety
1DIN RAIL 35 x 7.5 (EN50022);
2X1: 2 poles plug to connect the power supply;
3X2: 5 poles plug to connect DI5... DI8 High Voltage Digital Inputs;
4X3: 4 poles plug to connect OP9... OP11 SPST-NO 5 A output relays;
5X4: 6 poles plug to connect DI1... DI4 Digital Inputs;
6X5: 5 poles plug to connect OP4, OP5 (SPST-NO 5 A) and OP6 (SPDT 8 A)
output relays;
7X6: 5 poles plug to connect AO1... AO4 analogue outputs (0/4... 20 mA,
PWM and Hz);
8X7: 5 poles plug to connect CN1... CN4 High speed Digital Inputs;
9
X8: 10 poles plug to connect AI1... AI4 Analogue Inputs (mA, TC, PT100,
PT1000, NTC)
10 X10: USB type A receptacle to connect a flash drive;
11 X11: RJ45 plug to connect the Ethernet TCP/IP network for programming
purposes or for the MODBUS through the TCP port;
12 X12: 3 poles plug to connect COM1 serial port (RS485);
13 -4 mswitches to configure the serial port parameters;
14 -Reset button;
15 -Status/diagnostic LEDs: COM1 (green, COM1 traffic), USB (white, USB
activity), MSG (red, message), RUN (green, program status run/stop),
PWR (blue, power supply ON);
General description
Accessories
Installation
24 Vdc Power supply
APS2ALEDR12024 (120 W, 5.0 A),
APS2ALNDR75-24 (75 W, 3.2 A),
APS2ALMDR20-24 (20 W, 1.0 A)
1Clip the upper part of the module to
the rail;
2Rotate the module downwards until
the lower hook engages the DIN rail;
Dimensions (mm)
Mounting the module
- Mount the module vertically;
- In order to help the ventilation flow
of air, respect the distances betwe-
en modules and walls or other
modules.
Mounting position Mounting/removing the modules
on/from the DIN rail
Removing the module
Operating conditions
Integrated system,
CPU module
with on-board I/O
SAT1 model
mod. SAT1
24/02 - Code: ISTR_I_SAT1_E_01_--
130
203 70
X81
X41
X51
X121
X1X2 1
Environmental conditionBSuggestion
Operating
conditions
TTemperature
0...+50°C
%Rh
Umidity:
5... 95% Rh non
condensing
Special
conditions
TTemperature
> 50°C
Use forced
ventilation
%Rh
> 95% RH Warm up
PConducting
atmosphere Use filter
Forbidden
conditions
CCorrosive
atmosphere
EExplosive
atmosphere
1
2
3
4
1
2
9
7
341617
18
515
6
8
12
14
13
19 1020
21 11
16 X13: 3 poles plug to connect OP3 (SPDT 16 A) output relay;
17
X14: 3 poles plug to connect OP2 (SPDT 16 A or SPST-NO 30 A) output relay;
18
X15: 3 poles plug to connect OP1 (SPDT 16 A or SPST-NO 30 A) output relay;
19 X16: 4 poles plug to connect OP14... OP16 SPST-NO 5 A output relays;
20 X17: 4 poles plug to connect OP12... OP13 (SPST-NO 5 A output relays or
12 V outputs for SSR drives or 4 A/250 Vdc SSR outputs);
21 X18: 4 poles plug to connect OP7... OP8 (SPST-NO 5 A output relays or 12 V
outputs for SSR drives or 4 A/250 Vdc SSR outputs).
E
Screw Terminal Blocks
KIT_SAT1_00
Disposal
The appliance (or the
product) must be
disposed of separately in
compliance with the local
standards in force on
waste disposal.
3Switch OFF the Power Supply
With two fingers, press in the area
indicated by the arrow until the
hook is freed from the DIN guide;
4Turn and lift the module upwards to
remove the CPU from the DIN rail.

Electrical connections
X1X2X3X13X14X15
X8X7X6
X4X5X16X17X18
X11
X10 X12
Terminals connections and plugs
Conn. Label Signals
X1 124 Vac/dc Power Supply
2
X2
1Neutral (high voltage input)
2
DI5 Line
(high voltage input)
3DI6
Line
(high voltage input)
4DI7
Line
(high voltage input)
5DI8
Line
(high voltage input)
X3
1NO pole of OP9 relay
2NO pole of OP10 relay
3NO pole of OP11 relay
4Common pole of the relays
Conn. Label Signals
X4
1Ground
2DI1
3DI2
4DI3
5DI4
624 V for Digital Inputs
X5
1
Common pole of the relays
2NC pole of OP6 relay
3NO pole of OP6 relay
4NO pole of OP5 relay
5NO pole of OP4 relay
X6
1AO4 Positive pole
2AO3 Positive pole
3AO2 Positive pole
4AO1 Positive pole
5
Common pole of the AOs
Conn. Label Signals
X7
1CN4 Positive pole
2CN3 Positive pole
3CN2 Positive pole
4CN1 Positive pole
5
Ground
X8
1Ground
2Transmitters PWS (12 V)
3AI1 Negative pole
4AI1 Positive pole (TC)
5AI2 Negative pole
6AI1 Positive pole (TC)
7AI3 Negative pole
8AI3 Positive pole (TC)
9AI4 Negative pole
10 AI4 Positive pole (TC)
X10 USB USB Type A port
X11 ETH RJ45 Ethernet port
Conn. Label Signals
X12
1RS485 D+ connection
2RS485 D- connection
3RS485 Ground connection
X13
1NC pole of OP3 relay
2Common pole of OP3
3NO pole of OP3 relay
X14
1
NC pole of OP2 SPDT relay.
Not connected for SPST-NO
30 A relay
2Common pole of OP2
3NO pole of OP2 relay (SPDT
16 A or SPST-NO 30 A)
Description Plugs of all terminals
Flexible cable section: 0.2... 2.5 mm
²
(AWG24... AWG12)
LStripped wire Screw: 7mm Spring: 10mm
Flat blade screwdriver 0.6 x 3.5 mm 0.4 x 2.5 mm
Tightening torque 0.5... 0.6 Nm -
Technical data:
- The green terminals are male connectors (pitch 3.5 or 5 mm), the corre-
sponding female plugs are snap-on connectors with screw or spring termi-
nals for connecting the wires. The connectors terminals are labelled;
- Made with self extinguishing material as required by UL94 V0 standard;
- Overvoltage cathegory/pollution degree II/2;
- Max. load current/section 8 A/2.5mm
²
at 65°C;
- Test pulse voltage: 4 kVp.
A
Make sure that the overall current absorption (modules and field devices)
matches the power supply;
AIn order to avoid excessive voltage drops, install the most power consum-
ing modules closer to the power supply.
Conn. Label Signals
X15
1
NC pole of OP2 SPDT relay.
Not connected for SPST-NO
30 A relay
2Common pole of OP2
3NO pole of OP2 relay (SPDT
16 A or SPST-NO 30 A)
X16
1NO pole of OP14 relay
2NO pole of OP15 relay
3NO pole of OP16 relay
4Common pole of the relays
X17
1
OP12 5 A relay common
Negative pole of OP12 SSR
Pole of OP12 SSR Drive
2
OP12 5 A relay NO pole
Positive pole of OP12 SSR
Pole of OP12 SSR Drive
Conn. Label Signals
X17
(cnt.)
3
OP13 5 A relay common
Negative pole of OP13 SSR
Pole of OP13 SSR Drive
4
OP13 5 A relay NO pole
Positive pole of OP13 SSR
Pole of OP13 SSR Drive
X18
1
OP7 5 A relay common
Negative pole of OP7 SSR
Pole of OP7 SSR Drive
2
OP7 5 A relay NO pole
Positive pole of OP7 SSR
Pole of OP7 SSR Drive
3
OP8 5 A relay common
Negative pole of OP8 SSR
Pole of OP8 SSR Drive
4
OP8 5 A relay NO pole
Positive pole of OP8 SSR
Pole of OP8 SSR Drive
Power supply (X1 connector)
X1X2
X3X13X14X15
X8
X7X6
X4X5X16X17X18
X11
X10 X12
X1 Power Supply
connector
Vac/Vdc
X1
- Connector X1: 24 Vac/dc
(–10...+10%), 15W max.;
- The power supply terminals
(X1-1 and X1-2) are not polarized as
the CPU acceps both the 24 Vac
and 24 Vdc.
High Voltage (mains) Digital Inputs (X2 connector)
X1X3X13X14X15
X8
X7X6
X4X5X16X17X18
X11
X10 X12
Line Neutral
X2 High voltage
Digital Inputs
CV
DI8
DI7
DI6
DI5
X2 1
- Connector X2: DI5... DI8 High
Voltage Digital Inputs;
- Terminal 1 (CV) is the common (neu-
tral) terminal of the 100... 240 Vac
digital inputs DI5... DI8;
- Respect the connection shown, the
common terminal is shared by the
4 digital inputs.
k Danger!
High voltage inputs, remove
the mains and pay extreme at-
tention while performing these
input connections.
Digital outputs: SPST-NO Relays (X3 connector)
X1X2
X3
X13X14X15
X8
X7X6
X4X5X16X17X18
X11
X10 X12
X3 - SPST-NO 5A
relay terminals
C
OP11
OP10
OP9
X3 1
- Connector X3: OP9... OP11
SPST-NO relays outputs;
- Rate: Nominal 5 A (for resistive
loads);
- Max. common (C) current: 6 A;
- Insulation: 2500 V beween channel
and Power Supply and between
channel and main electronics.

DI1... DI4 Digital Inputs (X4 connector)
X1X2X3X13X14X15
X8X7X6
X5
X16X17X18
X11
X10 X12
X4 - DI1... DI4
terminals
24 V
G
DI1
DI2
DI3
DI4
X41
- Connector X4: DI1... DI4 digital
inputs;
- Insulation: 800 V between channel
ad Power Supply.
OP4... OP6 Digital Outputs (X5 connector)
X1X2X3X13X14X15
X8X7X6
X4X5
X16X17X18
X11
X10
X12
X5 - OP4... OP6
relay output terminals
C
OP6
OP5
OP4
X51
- Connector X5:
2 SPST NO relays (OP4, OP5) +
1 SPDT relay (OP6);
- Rate: Nominal 5 A for SPST relays,
8 A for SPDT relay (for resistive
loads);
- Max. common (C) current: 6A;
- Insulation: 2500 V beween channel
and Power Supply and between
channel and main electronics.
AO1... AO4 Analogue Output (X6 connector)
X1X2
X3
X13X14X15
X8
X4X5X16X17X18
X11
X10 X12
X6 - AO1... AO4
terminals
G
+
+
+
+
G
AO4
AO3
AO2
AO1
X61
- Connector X6: AO1... AO4 analoue
outputs;
- For the analogue output, respect the
polarity shown;
- Type: 0/4... 20 mA, O/10 V, PWM
and Hz;
- Load: > 1kΩ;
- Resolution: 16 bit;
- Accuracy: 0.5%;
- Insulation:
800 V Channel-Power supply,
50 V channel-main electronics;
m These outputs are ordered in
pairs (AO1/AO2 and AO3/AO4).
Verify the option ordered for
AO1/AO2 and AO3/AO4 Inputs.
Special (High Speed) Digital Inputs (X7 connector)
X1X2
X3
X13X14X15
X8
X6
X4X5X16X17X18
X11
X10 X12
X7 - DI1... DI4 terminals
G
CN4
CN3
CN2
CN1
X71
24 Vdc
+
In the drawing are connected only 2
counter inputs as an example (CN2
and CN4).
Frequency meter input:
- The channels can manage up to 10
kHz signals having a duty-cycle that
guarantees minimum of ON signal
of 20 ms;
Impulse counter input:
- The minimum time of an impluse
must be 20 ms;
Digital input:
- The input circuit is internally closed
to System Ground.
m Verify the option ordered for
CN1... CN4 Inputs.
AI1... AI4 Analogue Input (X8 connector)
X1X2
X3X13X14X15
X8
X7X6
X4X5X16X17X18
X11
X10 X12
X8 Analogue input terminals
G
AI1
AI2
AI3
AI4
12Vdc
TC
X81
TCTCTCTC
- Connector X8: AI1... AI4 digital
inputs;
- Respect the polarity shown;
- Pay attention to correctly connect
the power source (12 Vdc);
- Type: 0/4... 20 mA, TC (J, K, L, N, R,
S, T) PT100 (2 wires), PT1000, NTC;
- Resolution: 16 bit;
- Accuracy: 0.5% of span (linear inputs),
0.5% (temp.) ±1°C (cold junction);
- Input impedance: 120 kΩ(V),
<200 Ω(mA).
m Verify the option ordered for
AI1... AI4 Inputs.
X1X2
X3X13X14X15
X8
X7X6
X4X5X16X17X18
X11
X10 X12
X8 Analogue input terminals
G
AI1
AI2
AI3
AI4
12Vdc
Pt100/Pt1000
2 wires input
A
B
b
A
B
b
A
B
b
A
B
b
X81
X1X2
X3X13X14X15
X8
X7X6
X4X5X16X17X18
X11
X10 X12
X8 Analogue input terminals
G
AI1
AI2
AI3
AI4
12Vdc
NPT inputs
X81
X1X2
X3X13X14X15
X8
X7X6
X4X5X16X17X18
X11
X10 X12
X8 Analogue input terminals
G
AI1
AI2
AI3
AI4
12Vdc
0/4... 20 mA
active transmitter
-
+
-
+
-
+
-
+
X81
X1X2
X3X13X14X15
X8
X7X6
X4X5X16X17X18
X11
X10 X12
X8 Analogue input terminals
G
AI1
AI2
AI3
AI4
12Vdc
0/4... 20 mA 2 wires
passive Transmitter
X81
USB port (X10 connector)
X1X2X3X13X14X15
X8X7X6
X4X5
X16
X17X18
X11
X10
X12
X10 - USB type A connector
USB
type A
- USB type A receptacle (X10) to
connect a flash drive (system files
upload or data logging download).

Ethernet connector (X11 connector)
X1X2X3X13X14X15
X8X7X6
X4
X5
X16X17X18
X11
X10
X12
X11 - Ethernet RJ45 connector
Status/traffic LEDs
- Connector X11: The Ethernet con-
nection is made through a standard
J45 connector;
- The 2 green LEDs near the Ethernet
connector show the port status and
the communication traffic.
Serial Communications Port (X12 connector)
X1X2X3X13X14X15
X8X7X6
X4X5
X16X17X18
X11
X10
X12
X12 - RS485 connector
D+ D- GND
X121
DIP switches
POL+
POL-
NONE
TERM
- Connector X12: RS485 port to con-
nect a fieldbus network using the
Modbus protocol (master/slave) or
serial ASCII;
- The line settings can be configured
using the specific DIP switches:
SW Description Default
1Line polarization Pull-Up OFF
2Line polarization Pull-Down OFF
3Not used
4110 Ωline termination OFF
DIP switch settings
- Insulation from other electronics:
1.6 kV.
Sytem Pushbutton and Status LEDs
X1X2X3X13X14X15
X8X7X6
X4X5
X16X17X18
X11
X10
X12
COM
USB
MSG
RUN
PWR
Status LEDs System
pushbutton
- The 5 Status LEDs are:
COM (green), USB (white),
MSG (RED), RUN (green) and
PWR (blue).
- The meaning of the various LEDs
behaviours are fully described in
the “SAT1 User Manual”.
m The system pushbutton per-
forms different operations ac-
corndingly to the system status
but does not restart the CPU or
the 1131 application.
Digital Output: SPDT 16 A Relay (X13 connector)
X1X2X3
X13
X14X15
X8X7
X6
X4X5X16X17X18
X11
X10 X12
X13 - SPDT 16A
relay terminals
NO
C
NC
X13 1
OP3
- Connector X13: OP3 SPDT relay
output;
- Rate: Nominal 16 A (for resistive
loads);
- Max. common (C) current: 8 A;
- Insulation: 2500 V beween channel
and Power Supply and between
channel and main electronics.
OP1 Digital Output: SPST-NO 30 A or SPDT 16 A Relay (X14 connector)
X1X2X3X13
X14X15
X8X7X6
X4X5X16X17X18
X11
X10 X12
X14 - Configurable
relay terminals
NO
C
X14 1
OP2
First option:
SPST-NO 30A
- Connector X14: OP2 first option
SPST-NO relay output;
- Rate: Nominal 30 A (for resistive
loads);
- Max. common (C) current: 8 A;
- Insulation: 2500 V beween channel
and Power Supply and between
channel and main electronics.
m Verify the option ordered for
OP2 output.
X1X2X3X13
X14X15
X8X7X6
X4X5X16X17X18
X11
X10 X12
X14 - Configurable
relay terminals
X14 1
OP2
NO
C
NC
SPDT 16A
Second option:
SPDT 16A
- Connector X14: OP2 second option
SPDT relay output.
- Rate: Nominal 16 A (for resistive
loads).
- Max. common (C) current: 8 A;
- Insulation: 2500 V beween channel
and Power Supply and between
channel and main electronics.
m Verify the option ordered for
OP2 output.
OP2 Digital output: SPST-NO 30 A or SPDT 16 A Relay (X15 connector)
X1X2X3X13
X14X15
X8X7X6
X4X5X16X17X18
X11
X10 X12
X15 - Configurable
relay terminals
X15 1
OP1
First option:
SPST-NO 30A
NO
C
- Connector X15: OP1 first option
SPST-NO relay output.
- Rate: Nominal 30 A (for resistive
loads).
- Max. common (C) current: 8 A;
- Insulation: 2500 V beween channel
and Power Supply and between
channel and main electronics.
m Verify the option ordered for
OP1 output.
X1X2X3X13
X14X15
X8X7X6
X4X5X16X17X18
X11
X10 X12
X15 - Configurable
relay terminals
X15 1
OP1
NO
C
NC
SPDT 16A
Second option:
SPDT 16A
- Connector X15: OP1 second option
SPDT relay output;
- Rate: Nominal 16 A (for resistive
loads);
- Max. common (C) current: 8 A;
- Insulation: 2500 V beween channel
and Power Supply and between
channel and main electronics.
m Verify the option ordered for
OP1 output.

Digital outputs: SPST Relays (X16 connector)
X1X2X3X13X14X15
X8X7X6
X4X5
X16
X17X18
X11
X10
X12
X161
C
OP16
OP15
OP14
X16 - SPST-NO 5A
relay terminals
- Connector X16: OP14... OP16
SPST-NO relays outputs;
- Rate: Nominal 5 A (for resistive
loads);
- Max. common (C) current: 6 A;
- Insulation: 2500 V beween channel
and Power Supply and between
channel and main electronics.
Digital outputs: Configurable Outputs (X17 connector)
X1X2X3X13X14X15
X8X7X6
X4X5
X16X17
X18
X11
X10 X12
X171
C
OP13
C
OP12
X17 - Configurable
output terminals
First option:
2 SPST-NO 5A
- Connector X17: OP12, OP13 first
option 2 relays outputs;
Relays:
- 2 SPST-NO relays;
- Rate: Nominal 5 A (for resistive
loads);
- Max. common (C) current: 4 A;
- Insulation: 2500 V beween channel
and Power Supply and between
channel and main electronics.
m Verify the option ordered for
OP12 and OP13 outputs.
X1X2X3X13X14X15
X8X7X6
X4X5
X16X17
X18
X11
X10 X12
X171
OP13OP12
X17 - Configurable
output terminals
Second option:
12VDC for SSR
+ +
LOAD
SSR
LOAD
SSR
- Connector X17: OP12, OP13 sec-
ond option: 2 x 12 Vdc for SSR.
SSR drives:
- Voltage output 0/12 Vdc;
- Respect the polarity shown;
- Outputs not isolated.
m Verify the option ordered for
OP12 and OP13 outputs.
X1X2X3X13X14X15
X8X7X6
X4X5
X16X17
X18
X11
X10 X12
OP13OP12
LOAD
Fuse
LOAD
Fuse
X171
X17 - Configurable
output terminals
Third option:
SSR 4A/250V
NO NO
- Connector X17: OP12, OP13 third
option: Solid State Relays.
SSR:
- Rate: 4 A, 250 Vac;
- Zero Crossing Function;
- Insulation: 2500 V between channe-
land main electronics.
m Verify the option ordered for
OP12 and OP13 outputs.
Digital outputs: Configurable Outputs (X18 connector)
X1X2X3X13X14X15
X8X7X6
X4X5X16X17
X18
X11
X10 X12
X181
C
OP8
C
OP7
X18 - Configurable
output terminals
First option:
2 SPST-NO 5A
- Connector X18: OP7, OP8 first
option 2 relays outputs;
Relays:
- 2 SPST-NO relays;
- Rate: Nominal 5 A (for resistive
loads);
- Max. common (C) current: 4 A;
- Insulation: 2500 V beween channel
and Power Supply and between
channel and main electronics.
m Verify the option ordered for
OP7 and OP8 outputs.
X1X2X3X13X14X15
X8X7X6
X4X5X16X17
X18
X11
X10 X12
X181
OP8OP7
X18 - Configurable
output terminals
Second option:
12VDC for SSR
+ +
LOAD
SSR
LOAD
SSR
- Connector X18: OP7, OP8 second
option: 2 x 12 Vdc for SSR;
SSR drives:
- Voltage output 0/12 Vdc;
- Respect the polarity shown;
- Outputs not isolated.
m Verify the option ordered for
OP7 and OP8 outputs.
X1X2X3X13X14X15
X8X7X6
X4X5X16X17
X18
X11
X10 X12
OP8OP7
LOAD
Fuse
LOAD
Fuse
X181
X18 - Configurable
output terminals
Third option:
SSR 4A/250V
NO NO
- Connector X18: OP7, OP8 third
option: Solid State Relays.
SSR:
- Rate: 4 A, 250 Vac;
- Zero Crossing Function;
- Insulation: 2500 V between channe-
land main electronics.
m Verify the option ordered for
OP7 and OP8 outputs.

SUGGESTED WIRES ROUTING
100 100
100
100
Conduit for low level sensor cables
Conduit for supply and output cables
Output cables
Power cables
AI and DI cables
AI and DO cables
X1X3X13X14X15
X8X7X6
X4X5X16X17X18
X11
X10 X12
ADespite the fact that the instrument has been designed to work in an
harsh and noisy environment, it is strongly recommended to follow
the following suggestions.
All the wiring must comply with the local regulations.
The supply wiring should be routed away from the power cables. Avoid to use
electromagnetic contactors, power relays and high power motors nearby.
Avoid power units nearby, especially if controlled in phase angle. Keep the low
level sensor input wires away from the power lines and the output cables.
Power lines and output cables must also be at 100 mm (min.) away from the CPU.
If this is not achievable, use shielded cables on the sensor input, with the shield
connected to earth.
AWarning!
Whenever a failure or a malfunction of the device may cause dan-
gerous situations for persons, things or animals, please remember
that the plant must be equipped with additional devices which will
guarantee safety.

How to Order
SAT1
SAT1 = CPU of the Programmable Logic Controller with 24 Vac/Vdc Power Supply
AI1: Analogue Input 1 Pre-Configured
A = mA
C = Pt100
M = PT1000
N = NTC
T = TC
AI2: Analogue Input 2 Pre-Configured
- = Not provided
A = mA
C = Pt100
M = PT1000
N = NTC
T = TC
AI3: Analogue Input 3 Pre-Configured
- = Not provided
A = mA
C = Pt100
M = PT1000
N = NTC
T = TC
AI4: Analogue Input 4 Pre-Configured
- = Not provided
A = mA
C = Pt100
M = PT1000
N = NTC
T = TC
AO1O2: Analogue Outputs 1 and 2
- = Not provided
A = mA Outputs
D = Digital Outputs
F = PWM/Frequency Outputs
V = Voltage Outputs
AO3O4: Analogue Outputs 3 and 4
- = Not provided
A = mA Outputs
D = Digital Outputs
F = PWM/Frequency Outputs
V = Voltage Outputs
DIGFI: High Speed Digital Inputs CN1... CN4
- = Not provided
T = 4 High Speed Digital Inputs
ID: Free of Voltage Digital Inputs DI1... DI4
- = Not provided
L = 4 Free of Voltage Digital Inputs
DIGVI: Main Voltage Digital Inputs DI5... DI8
- = Not provided
V = 4 Main Voltage Digital Inputs
OO1: Digital Output OP1
H = Relay SPST-NO 30 A
S = Relay SPDT 16 A
OO2: Digital Output OP2
H = Relay SPST-NO 30 A
S = Relay SPDT 16 A
OO3: Digital Output OP3
S = Relay SPDT 16 A
OO456: Digital Outputs OP4... OP6
R = 2 relays SPST-NO 5 A + 1 relay SPDT 8 A
OO78: Digital Outputs OP7... OP8
O = 2 digital outputs 12 VDC for SSR drive
Q = 2 SSR digital outputs
R = 2 relays SPST-NO 5 A
OO9AB: Digital Outputs OP8... OP11
- = Not provided
R = 3 relays SPST-NO 5 A
OOCD: Digital Outputs OP12 and OP13
- = Not provided
O = 2 digital outputs 12 VDC for SSR drive
Q = 2 SSR digital outputs
R = 2 relays SPST-NO 5 A
OOEFG: Digital Outputs OP14... OP16
- = Not provided
R = 3 relays SPST-NO 5 A
SCM: Serial Communications Port
- = Not provided
I = Insulated RS485
S = Not Insulated RS485

Connector map
m SAT1 is a complex instrument with a very limited space for the connection labels.
Refer to the image that follows to identify each connector and find the position of terminal 1.
All the connections previously described are based on these 2 details
X41
X1
X51
X1X2X3X13
X2 1
X3 1
X13 1
X14
X14 1
X15
X16X17 X4X5X18
X15 1
X121
X12
X161X171X181
X61 X71
X6 X7 X8
X81
This manual suits for next models
1
Table of contents
Other Ascon tecnologic Computer Hardware manuals