Ethernet connector (X11 connector)
X5
X11
X10
X11 - Ethernet RJ45 connector
Status/traffic LEDs
- Connector X11: The Ethernet con-
nection is made through a standard
J45 connector;
- The 2 green LEDs near the Ethernet
connector show the port status and
the communication traffic.
Serial Communications Port (X12 connector)
X4X5
X12
X12 - RS485 connector
D+ D- GND
X121
DIP switches
POL+
POL-
NONE
TERM
- Connector X12: RS485 port to con-
nect a fieldbus network using the
Modbus protocol (master/slave) or
serial ASCII;
- The line settings can be configured
using the specific DIP switches:
SW Description Default
1Line polarization Pull-Up OFF
2Line polarization Pull-Down OFF
3Not used
4110 Ωline termination OFF
- Insulation from other electronics:
1.6 kV.
Sytem Pushbutton and Status LEDs
X4X5
X12
COM
USB
MSG
RUN
PWR
Status LEDs System
pushbutton
- The 5 Status LEDs are:
COM (green), USB (white),
MSG (RED), RUN (green) and
PWR (blue).
- The meaning of the various LEDs
behaviours are fully described in
the “SAT1 User Manual”.
m The system pushbutton per-
forms different operations ac-
corndingly to the system status
but does not restart the CPU or
the 1131 application.
Digital Output: SPDT 16 A Relay (X13 connector)
X13
X6
X13 - SPDT 16A
relay terminals
NO
C
NC
X13 1
OP3
- Connector X13: OP3 SPDT relay
output;
- Rate: Nominal 16 A (for resistive
loads);
- Max. common (C) current: 8 A;
- Insulation: 2500 V beween channel
and Power Supply and between
channel and main electronics.
OP1 Digital Output: SPST-NO 30 A or SPDT 16 A Relay (X14 connector)
X14X15
X8X7X6
X4X5X16X17X18
X11
X10 X12
X14 - Configurable
NO
C
X14 1
OP2
First option:
SPST-NO 30A
- Connector X14: OP2 first option
SPST-NO relay output;
- Rate: Nominal 30 A (for resistive
loads);
- Max. common (C) current: 8 A;
- Insulation: 2500 V beween channel
and Power Supply and between
channel and main electronics.
m Verify the option ordered for
OP2 output.
X14X15
X8X7X6
X4X5X16X17X18
X11
X10 X12
X14 - Configurable
relay terminals
X14 1
OP2
NO
C
NC
SPDT 16A
Second option:
SPDT 16A
- Connector X14: OP2 second option
SPDT relay output.
- Rate: Nominal 16 A (for resistive
loads).
- Max. common (C) current: 8 A;
- Insulation: 2500 V beween channel
and Power Supply and between
channel and main electronics.
m Verify the option ordered for
OP2 output.
OP2 Digital output: SPST-NO 30 A or SPDT 16 A Relay (X15 connector)
X14X15
X8X7X6
X4X5X16X17X18
X11
X10 X12
X15 - Configurable
relay terminals
X15 1
OP1
First option:
SPST-NO 30A
NO
C
- Connector X15: OP1 first option
SPST-NO relay output.
- Rate: Nominal 30 A (for resistive
loads).
- Max. common (C) current: 8 A;
- Insulation: 2500 V beween channel
and Power Supply and between
channel and main electronics.
m Verify the option ordered for
OP1 output.
X14X15
X8X7X6
X4X5X16X17X18
X11
X10 X12
X15 - Configurable
relay terminals
X15 1
OP1
NO
C
NC
SPDT 16A
Second option:
SPDT 16A
- Connector X15: OP1 second option
SPDT relay output;
- Rate: Nominal 16 A (for resistive
loads);
- Max. common (C) current: 8 A;
- Insulation: 2500 V beween channel
and Power Supply and between
channel and main electronics.
m Verify the option ordered for
OP1 output.