
Selecting a Mounting Location for the DS-9C
The small corded device with the interleaved grid is the remote precipitation or "moisture" sensor. The
brass cylinder protruding from the bottom of the DS-9C enclosure is the temperature sensor. For reliable
rain and snow detection the moisture sensor must be exposed to a clear view of the sky. Reference Page 3
"Moisture Sensor Mounting & Termination" for guidance in mounting the DS-9C moisture sensor. For
proper temperature detection the DS-9C enclosure must be mounted outdoors, away from furnace vents,
dryer vents, and other sources of heat. When powered, the DS-9C moisture grid will always remain hot.
This is normal. This allows the sensor to continuously melt/evaporate rain and snow from the grid.
The DS-9C enclosure can be mounted by screwing the base conduit hub onto an appropriate size free-
standing conduit or by using the mounting holes in each corner of the enclosure.
DO NOT DRILL HOLE THROUGH THE ENCLO URE FOR MOUNTING!
Ne Font Pas Les Trous De Foret Par La Boîte Pour Le upport!
This can allow water into the enclosure causing a potential shock hazard. It is recommended that a
weatherproof junction box be mounted below the DS-9C for termination of the power and load pigtails to
the building wiring.
Use Care When Replacing the Front Cover. Do Not Pinch the Gasket or Overtighten the crews.
LOAD1 LOAD2 INPUT POWER
SWITCH JACK
CONTROL/MONITOR JACK
GRID JACK
SENSITIVITY ADJUST
DELAY OFF ADJUST
TEMPERATURE ADJUST
CONFIGURATION SWITCH
ALWAYS FOLLOW LOCAL AND NATIONAL ELECTRICAL CODES
Toujours Suivre Les Codes Électriques Locaux Et Nationaux
2
External Control/Monitor Operation
The DS-9C provides external control/monitor capability. Cable
rated 300V up to 18 AWG can be connected to TB2 to access this
feature. Connecting Black (4) to White (1) will activate the
“Manual On” function. Connecting Green (5) to White (1) will
activate the “Standby/Reset” function. See the “Manual Override
Switch Function” for a description of these modes. The
Red/Orange (2/3) leads are connected to an internal low power
monitor relay. This relay, rated at 24 VAC/VDC @ 400 mA, 10W maximum, will close with the load relays
and can be used to externally monitor activation of the sensor. This terminal block is also the connection
point for connecting a CDP-2. Use only tinned, stranded, shielded cable for a reliable connection.
Power & Activation Indicator
A green lamp shines through a lens on the cover of the DS-9C to indicate operational status. If this lamp is
OFF the DS-9C is not receiving power. If this lamp is steady ON the DS-9C is powered but not triggered.
If this lamp is FLA HING the DS-9C is powered on and triggered, the main relays are closed, and attached
equipment should be activated. Note that, even though snow or rain may have stopped, the DS-9C
indicator will continue to flash during the Delay-Off drying cycle.
Fine Adjustment for Efficient Operation
The DS-9C is shipped with the TRIG TEMP and DELAY OFF adjustments in the center position,
representing 39°F (3.9°C) and 60 minutes of Delay-Off time respectively. It is also set for highest
SENSITIVITY. Depending on local conditions the user may find that fine adjustment of the controls may
provide more satisfactory operation. If the sensor does not trigger during very wet snows the trigger
temperature may need to be adjusted higher. Constant triggers from snow falling from trees or overhangs
may be reduced by adjusting SENSITIVITY. The Delay-Off time can also be adjusted to provide clean
melt-off without excessive running time. Fine adjustment can both save operating expense and provide
more reliable operation. However, to keep reliability high, always make adjustments in small increments.
Moisture Grid Maintenance & Replacement
It is recommended that the DS-9C be powered down and the moisture grid wiped clean with clear water at
least once every 4 months. Heavy deposits may be removed using a non-metallic scouring pad (Scotch-
BriteTM or equivalent.) However, after a number of years, the corrosive elements left behind when water is
evaporated out of the moisture grid will eventually damage the grid rings. The moisture grid can be easily
replaced by ordering and installing a new MG-6 “Moisture Grid Assembly”. Reference the “Moisture
ensor Mounting & Termination” section for information on replacing the moisture grid.
Preseason Snow Detection Testing
It is always a good idea to test the operation of the DS-9C prior to the winter season. Procure some clean
water and, if the outdoor temperature is above the trigger point, a can of spray component cooler (Radio
Shack Part #64-4321 or equivalent.) Clean the moisture grid following the procedure outlined above and
allow it to dry. Apply power to the DS-9C, drip some of the water onto the moisture grid, then spray the
temperature sensor protruding from the base of the enclosure with the component cooler. Once the
temperature sensor has reached the trigger point with water still present on the grid the DS-9C will activate.
The user should hear the internal control relays close and see the green lamp blink. Proper operation has
been confirmed. Allow the grid to dry completely. To clear the Delay-Off timer place the override switch
into “Standby/Reset”, and then back to the “Automatic” position.
7
General Safety Instructions
1. THI UNIT HOULD BE IN TALLED, OPENED, AND REPAIRED BY QUALIFIED PER ONNEL
ONLY!
CETTE UNITÉ DEVRAIT ÊTRE IN TALLÉE, OUVERTE, ET RÉPARÉE PAR LE PER ONNEL
QUALIFIÉ EULEMENT!
2. To avoid shock hazard do not open the front cover with power connected to the DS-9C or any
controlled equipment.
Pour éviter la décharge électrique déconnectez toute la puissance avant d'ouvrir la couverture du DS-
9C.
Pin Color Function
1 White GND/Common
2 Red Deice On Mon A
3 Orange Deice On Mon B
4 Black Manual On
5 Green Standby/Reset